Outdoor Unit Installation Drawings

1.

Precautions for humidifying hose installation work.

• Moisture on the outdoor unit is brought to the indoor unit together with air around the outdoor unit during humidifying 

operation. Install the outdoor unit in a clean and calm location.

• When embedding   humidifying hose: 

1) Cannot be installed to the existing embedded piping. Embedding work is separately necessary.

• The length of the   humidifying hose is marked on the hose packing material.

1) Use an extension hose (sold separately) when extending the   humidifying hose.
2) The length of the   humidifying hose needs to be set to ensure humidifying capacity. Cut off any excess hose. 

Use the remote controller to set the hose length.

• When it is difficult to install without cutting the   humidifying hose, cut the hose and join it with included   joint or   elbow 

after the installation. When doing this, bind the hose using included   binding band so that there is no air leakage. 
(Refer to 

Connecting the Humidifying Hose

 on page 8.)

• When laying the   humidifying hose inside the wall, block the ends of the   humidifying hose with tape or the like to 

prevent water or anything else from entering it until it is connected to the indoor unit and outdoor unit ducts.

• Do not bend the   humidifying hose more than 90°. 

C

C

C

C

C

D

E

F

C

C

C

Wrap the insulation pipe with 
the finishing tape from bottom 
to top.

In sites with poor drainage, use 
block bases for outdoor unit.  
Adjust foot height until the unit 
is leveled.  Otherwise, water 
leakage or pooling of water may 
occur.

574

(Foot bolt-hole centres)

(From unit’

s side)

Where there is a danger of the unit 
falling, use foot bolts, or wires.

(Foot bolt-hole 

centres)

311

250mm from w

all

Unit: mm

How to remove the stop valve cover.

Remove the screw on the 
stop valve cover.
Slide the lid downward 
to remove it.

How to attach the stop valve cover.

Insert the upper part of the 
stop valve cover into the 
outdoor unit to install.
Tighten the screws.

Stop valve cover

O.D. 9.5mm

Gas pipe

Liquid pipe

O.D. 6.4mm

8m

10m

Max. allowable length

Max. allowable height

*

 No refrigerant needs to be added if the piping does not 

exceed the maximum length. 

105.5

Humidifying hose

C

Allow space for piping 
and electrical servicing.

01_EN_3P177302-2.fm  Page 3  Thursday, May 25, 2006  6:21 PM

Summary of Contents for RXR28EV1B

Page 1: ...V1B Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syste...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EM...

Page 3: ...or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After all installation is complete check to make sur...

Page 4: ...they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Sinc...

Page 5: ...age 8 When laying the humidifying hose inside the wall block the ends of the humidifying hose with tape or the like to prevent water or anything else from entering it until it is connected to the indo...

Page 6: ...undation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If...

Page 7: ...them fully with the torque wrenches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on...

Page 8: ...gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operati...

Page 9: ...to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the g...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0605 HT 3P177302 2 M05B201...

Reviews: