Refrigerant Circuit (Piping Diagrams)
SiAF341904E
46
Part 2 Refrigerant Circuit
1.2
VRV
Indoor Unit
No. in piping
diagram
Name
Electric
symbol
Applicable model
Function
(1)
Electronic expansion valve
Y1E
All indoor units
Used for gas superheated degree
control while in cooling.
(2)
Suction air thermistor
R1T
All indoor units
Used for thermostat control.
(3)
Indoor liquid pipe thermistor
R2T
All indoor units
Used for gas superheated degree
control while in cooling.
(4)
Indoor gas pipe thermistor
R3T
All indoor units
Used for gas superheated degree
control while in cooling.
FXFSQ-AR
FXMQ-PB
FXMQ-AR
FXAQ-P
C: 4D024460P
(4)
(3)
Indoor heat exchanger
Fan
Filter
Filter
(1)
Gas piping
connection port
Li
qu
id piping
connection port
(2)
(3)
(2)
(1)
(4)
C: 4D110285
C: 4D097585B
(2)
(1)
(3)
(4)
Indoor heat exchanger
Fan
Filter
Filter
(4)
(2)
(1)
(3)
Gas piping
connection port
Liquid piping
connection port
C: 4D034245R