Field Settings for Indoor Unit
SiAF341904E
118
Part 5 Field Settings and Test Operation
1.4.9 Compensating the Temperature around People
(For units with the infrared floor sensor)
Change the ratio between the suction air temperature and floor temperature used to calculate
the temperature around people.
The temperature around people is calculated using the values of the suction air thermistor and
the infrared floor sensor. The factory setting is "Normal" (the average value of the suction air
temperature and the floor temperature is applied). However, the rate at which the suction air
thermistor and the infrared floor sensor affect the temperature around people can be changed
with this setting.
To reflect the effect of the temperature around the ceiling, select the "Priorities given on the
suction air temperature" (the Second code No.
02
).
To reflect the effect of the temperature around the floor, select the "Priorities given on the
floor temperature" (the Second code No.
04
).
The infrared floor sensor can be disabled by selecting "Suction air temperature only" (the
Second code No.
01
).
: Factory setting
1.4.10 Optional Accessories Output Selection
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals X1 and X2 of "adaptor for wiring", an optional
accessory.
: Factory setting
1.4.11 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block in the electrical
component box.
: Factory setting
Mode
No.
First
Code No.
Second
Code No.
Contents
11 (21)
8
01
Suction air temperature only
02
Priority given on the suction air temperature
03
Standard
04
Priority given on the floor temperature
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided
.
02
—
03
Output linked with ON/OFF of remote controller is provided.
04
In case of Error Display appears on the remote controller, output is
provided.
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced OFF (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Operation
ON
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The
other indoor units indicate
U9.
F2 T1 T2
Forced OFF
Input A