SiAF341904E
Troubleshooting with Remote Controller
Part 6 Service Diagnosis
171
4.4 Error Codes and Descriptions
k
: ON
h
: OFF
l
: Blink
Error code Operation
lamp
Error contents
Reference
page
Indoor Unit
A0
l
External protection device abnormality
A1
l
Indoor unit PCB abnormality
A3
l
Drain level control system abnormality
A6
l
Indoor fan motor lock, overload
Indoor fan motor abnormality
A8
l
Power supply voltage abnormality
A9
l
Electronic expansion valve coil abnormality, dust clogging
AF
k
Humidifier system abnormality
AH
l
Auto grille unit error
AJ
l
Capacity determination device abnormality
C1
l
Transmission abnormality (between indoor unit PCB and fan PCB)
Transmission error
Transmission error (between indoor unit PCB and auto grille control PCB)
C4
l
Indoor heat exchanger liquid pipe thermistor abnormality
C5
l
Indoor heat exchanger gas pipe thermistor abnormality
C6
l
Combination abnormality (between indoor unit PCB and fan PCB)
Capacity setting abnormality
Indoor unit PCB abnormality
C9
l
Suction air thermistor (R1T) abnormality
CE
k
Infrared presence/floor sensor error
CJ
k
Remote controller thermistor abnormality
Outdoor Unit
E1
l
Outdoor unit main PCB abnormality
E2
l
Current leakage detection
Missing of leakage detection core
E3
l
Activation of high pressure switch
E4
l
Activation of low pressure sensor
E5
l
Inverter compressor motor lock
E7
l
Outdoor fan motor abnormality
E9
l
Electronic expansion valve coil abnormality
F3
l
Discharge pipe temperature abnormality
F4
l
Wet alarm
F6
l
Refrigerant overcharged
H3
l
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
l
Outdoor fan PCB abnormality
H9
l
Outdoor air thermistor (R1T) abnormality
J3
l
Discharge pipe thermistor (R21T, R22T) abnormality
Compressor body thermistor (R8T, R9T) abnormality
J5
l
Suction pipe thermistor (R3T) abnormality
J7
l
Subcooling heat exchanger liquid pipe thermistor (R5T) abnormality
J8
l
Heat exchanger liquid pipe thermistor (R4T) abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
Inverter PCB abnormality
L2
l
Momentary power failure during test operation
L4
l
Inverter radiation fin temperature rise abnormality
L5
l
Compressor instantaneous overcurrent
L8
l
Compressor overcurrent
L9
l
Compressor startup abnormality
LC
l
Transmission error between inverter PCB and outdoor unit main PCB
P1
l
Power supply voltage imbalance
P3
l
Reactor temperature abnormality
P4
l
Inverter radiation fin temperature abnormality
PJ
l
Field setting after replacing outdoor unit main PCB abnormality or
combination of PCB abnormality