Troubleshooting by Error Code
SiAF341904E
208
Part 6 Service Diagnosis
5.16 Capacity Setting Abnormality
Applicable
Models
FXFSQ
Error Code
C6-01
Method of Error
Detection
This error is detected by checking communication between the PCB (A1P) and the fan
microcomputer.
Error Decision
Conditions
Based on the communication data, decide whether the combination of capacity setting and the
type of fan driver is correct.
Supposed
Causes
Defective connection of the capacity setting adaptor
Wrong field setting
Troubleshooting
Is the indoor
unit PCB (A1P) replaced by
the spare PCB?
After transmission between
the indoor and the outdoor
PCBs is established, perform
operation again and then
perform diagnosis again.
After transmission between
the indoor and the outdoor
PCBs is established, perform
operation again and then
perform diagnosis again.
Is a proper
capacity setting adaptor
installed when replaced by the
space PCB?
Install a proper capacity
setting adaptor.
NO
NO
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.