Field Settings for Outdoor Unit
SiAF341904E
142
Part 5 Field Settings and Test Operation
: Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
: Once function is activated “t
01
” appears. To stop current function, press
Return (BS3)
button
once.
For detailed description about each setting, refer to
Details of Setting Mode (m2)
on page 143.
Indication
bold
means factory setting.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
41 Do not change contents.
2
.
4
1
—
—
—
—
42 Do not change contents.
2
.
4
2
—
—
—
—
43 Do not change contents.
2
.
4
3
—
—
—
—
44 Do not change contents.
2
.
4
4
—
—
—
—
45 Do not change contents.
2
.
4
5
—
—
—
—
46 Do not change contents.
2
.
4
6
—
—
—
—
47 Do not change contents.
2
.
4
7
—
—
—
—
48 Do not change contents.
2
.
4
8
—
—
—
—
49 Outdoor > 50 m
above indoor
Height difference setting max. 90 m.
2
.
4
9
OFF (max. 50 m)
ON (max. 90 m)
0
1
50 Do not change contents.
2
.
5
0
—
—
—
—
51
Sequence multi
outdoor
Sequence addressing between master
and slave units.
2
.
5
1
Automatic
Forced master
Forded slave 1
Forced slave 2
0
1
2
3
76
VRTsmart
control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRTsmart
control.
2
.
7
6
Low 1
Low 2
Low 3
Low 4
Low 5
Low 6
Standard
High
0
1
2
3
4
5
6
7
78
VRT control
Te upper limit
Used to change upper limit of target
evaporation temperature in VRT
control.
2
.
7
8
Standard
High
4
6
81
Cooling comfort
setting
Cooling comfort setting
2
.
8
1
ECO
Mild
Quick
Powerful
0
1
2
3
82 Do not change contents.
2
.
8
2
—
—
—
—
83 Master remote control setting when mix combination
2
.
8
3
VRV indoor
RA indoor
—
—
0
1
84 Do not change contents.
2
.
8
4
—
—
—
—
85 Do not change contents.
2
.
8
5
—
—
—
—
86 Do not change contents.
2
.
8
6
—
—
—
—
87 Do not change contents.
2
.
8
7
—
—
—
—
89 Do not change contents.
2
.
8
9
—
—
—
—
90
Indoor unit
without power
Possible for operate system when
some indoor units are temporary
without power supply.
2
.
9
0
Disabled
Enabled
0
1
95
Eco level setting for VRTsmart
2
.
9
5
Standard
Middle
High
0
1
2