Specifications
SiAF341904E
40
Part 1 General Information
Model Name (Combination Unit)
RXQ58ANRY1
RXQ60ANRY1
Model Name (Independent Unit)
RXRXRXQ20ARY1
RXRXRXQ20ARY1
Power supply
3 phase, 380-415 V, 50/60 Hz
3 phase, 380-415 V, 50/60 Hz
1 Cooling capacity
kcal/h
139,000
144,000
Btu/h
553,000
573,000
kW
162
168
Casing color
Ivory white (5Y7.5/1)
Ivory white (5Y7.5/1)
Dimensions (H × W × D)
mm
(1,657×1,240×765)+(1,657×1,240×765)+
(1,657×1,240×765)
(1,657×1,240×765)+(1,657×1,240×765)+
(1,657×1,240×765)
Heat exchanger
Cross fin coil
Cross fin coil
Compressor
Type
Hermetically sealed scroll type
Hermetically sealed scroll type
Motor output ×
Number of units
kW
(4.0×1)+(4.0×1)+(3.8×1)+(6.3×1)+
(3.8×1)+(6.3×1)
(3.8×1)+(6.3×1)+(3.8×1)+(6.3×1)+
(3.8×1)+(6.3×1)
Starting method
Soft start
Soft start
Fan
Type
Propeller fan
Propeller fan
Motor output
kW
(0.75×2)+(0.75×2)+(0.75×2)
(0.75×2)+(0.75×2)+(0.75×2)
Airflow rate
m³/min
257+297+297
297+297+297
Drive
Direct drive
Direct drive
Connecting
pipes
Liquid pipe
mm
19.1 C1220T (Brazing connection)
19.1 C1220T (Brazing connection)
Gas pipe
mm
41.3 C1220T (Brazing connection)
41.3 C1220T (Brazing connection)
Mass
kg
260+285+285
285+285+285
2 Sound pressure level
dB(A)
69
70
Safety devices
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector,
Over/under voltage protection printed circuit board
Capacity control
%
7-100
7-100
Refrigerant
Refrigerant name
R-410A
R-410A
Charge
kg
8.4+11.8+11.8
11.8+11.8+11.8
Control
Electronic expansion valve
Electronic expansion valve
Refrigerator oil
Refer to the nameplate of compressor
Refer to the nameplate of compressor
Standard accessories
Installation manual, Operation manual,
Connection pipes, Clamps
Installation manual, Operation manual,
Connection pipes, Clamps
Drawing No.
Specifications
―
―
Sound level
―
―
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Conversion formulae
kcal/h = kW × 860
Btu/h = kW × 3412