5 Preparation

Installer reference guide

10

ARXM25~35 RXM20~35 RXJ20~3

RXA20~35A3V1B

R32 split series

4P518023-5D – 2019.04

Install the outdoor unit away from direct sea winds.

Example: 

Behind the building.

b

c

a

If the outdoor unit is exposed to direct sea winds, install a
windbreaker.

▪ Height of windbreaker≥1.5×height of outdoor unit

▪ Mind  the  service  space  requirements  when  installing  the

windbreaker.

a

b

c

d

c

d

a

Sea wind

b

Building

c

Outdoor unit

d

Windbreaker

The  outdoor  unit  is  designed  for  outdoor  installation  only,  and  for
ambient  temperatures  ranging  from  –10~50°C  in  cooling  mode  and
from –20~24°C in heating mode.

5.2.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"6.3  Mounting  the

outdoor unit" on page 11

 for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

5.2.3

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

20 m

Minimum allowable pipe length

1.5 m

Maximum allowable height difference

15 m

5.3

Preparing refrigerant piping

5.3.1

Refrigerant piping requirements

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

Piping material:

 Phosphoric acid deoxidised seamless copper.

Piping diameter:

Liquid piping

Ø6.4 mm (1/4")

Gas piping

Ø9.5 mm (3/8")

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

5.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

Summary of Contents for RXJ20M3V1B

Page 1: ...eference guide R32 split series English Installer reference guide R32 split series ARXM25N2V1B9 ARXM35N2V1B9 RXM20N2V1B9 RXM25N2V1B9 RXM35N2V1B9 RXJ20M3V1B RXJ25M3V1B RXJ35M3V1B RXA20A3V1B RXA25A3V1B...

Page 2: ...iping 15 6 5 3 To check for leaks 15 6 5 4 To perform vacuum drying 15 6 6 Charging refrigerant 16 6 6 1 About charging refrigerant 16 6 6 2 About the refrigerant 16 6 6 3 Precautions when charging re...

Page 3: ...ive gloves safety glasses when installing maintaining or servicing the system WARNING Tear apart and throw away plastic packaging bags so that nobody especially children can play with them Possible ri...

Page 4: ...nstallation of pipework shall be kept to a minimum WARNING If appliances contain R32 refrigerant the floor area of the room in which the appliances are installed operated and stored MUST be larger tha...

Page 5: ...gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into con...

Page 6: ...e fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with...

Page 7: ...latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 2 2 Installer r...

Page 8: ...y flammable 4 1 Overview About the unit This chapter contains information about Identification of the outdoor unit 4 2 Identification NOTICE When installing or servicing several units at the same time...

Page 9: ...ir outlet b Air inlet NOTICE The height of the wall on the outlet side of the outdoor unit MUST be 1200 mm NOTICE Do NOT stack the units on each other Do NOT hang the unit on a ceiling Strong winds 18...

Page 10: ...eral snowfall is possible make sure that the heat exchanger coil is NOT affected by the snow If necessary install a snow cover or shed and a pedestal 5 2 3 Refrigerant piping length and height differe...

Page 11: ...escribes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages 1 Opening the unit 2 Mounting the outdoor unit 3 Connecting...

Page 12: ...bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping see the following figure NOTICE If the unit is installed in a cold climate take adequate...

Page 13: ...ion period Protection method Outdoor unit 1 month Pinch the pipe 1 month Pinch or tape the pipe Indoor unit Regardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking...

Page 14: ...panner on the stem cap as this could cause a refrigerant leak a b a Spanner b Torque wrench When it is expected that the operating pressure will be low e g when cooling will be performed while the out...

Page 15: ...ely Using the same pump for other refrigerants may damage the pump and the unit NOTICE Connect the vacuum pump to the service port of the gas stop valve Make sure that the gas stop valve and liquid st...

Page 16: ...Vacuum drying on the outdoor unit s internal refrigerant piping is performed NOTICE Before completely recharging perform vacuum drying on the outdoor unit s internal refrigerant piping as well Typical...

Page 17: ...CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label...

Page 18: ...A A a Curled single core wire b Screw c Flat washer Stranded conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c Flat washer O Allowed X NOT allowed Tightening torques...

Page 19: ...cally consists of the following stages 1 Checking the Checklist before commissioning 2 Performing a test run for the system 7 2 Precautions when commissioning DANGER RISK OF ELECTROCUTION DANGER RISK...

Page 20: ...sumes electricity When the power turns back on after a power break the previously selected mode will be resumed 7 6 Starting up the outdoor unit See the indoor unit installation manual for configurati...

Page 21: ...based on symptoms Before troubleshooting Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring 11 2 Precautions when troublesho...

Page 22: ...rate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still runn...

Page 23: ...DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE...

Page 24: ...rtain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Mainten...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P518023 5D 2019 04 Copyright 2018 Daikin...

Reviews: