background image

1 General safety precautions

Installer reference guide

4

ARXM25~35 RXM20~35 RXJ20~3

RXA20~35A3V1B

R32 split series

4P518023-5D – 2019.04

▪ In  places  where  there  is  a  risk  of  fire  due  to  the  leakage  of

flammable  gases  (example:  thinner  or  gasoline),  carbon  fibre,
ignitable dust.

▪ In  places  where  corrosive  gas  (example:  sulphurous  acid  gas)  is

produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.

Instructions for equipment using R32 refrigerant

If applicable.

WARNING

▪ Do NOT pierce or burn.

▪ Do  NOT  use  means  to  accelerate  the  defrosting

process  or  to  clean  the  equipment,  other  than  those
recommended by the manufacturer.

▪ Be  aware  that  R32  refrigerant  does  NOT  contain  an

odour.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

NOTICE

▪ Do NOT re-use joints which have been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

Installation space requirements

NOTICE

▪ Pipework shall be protected from physical damage.

▪ Installation of pipework shall be kept to a minimum.

WARNING

If  appliances  contain  R32  refrigerant,  the  floor  area  of  the
room  in  which  the  appliances  are  installed,  operated  and
stored  MUST  be  larger  than  the  minimum  floor  area
defined in table below A (m

2

). This applies to:

▪ Indoor  units 

without

  a  refrigerant  leakage  sensor;  in

case  of  indoor  units 

with

  refrigerant  leakage  sensor,

consult the installation manual

▪ Outdoor  units  installed  or  stored  indoors  (e.g.  winter

garden, garage, machinery room)

▪ Pipework in unventilated spaces

To determine the minimum floor area

1

Determine  the  total  refrigerant  charge  in  the  system  (=  factory
refrigerant  charge 

  + 

  additional  refrigerant  amount

charged).

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

1000

GWP × kg

=
=

+

kg

=

kg

=

GWP: xxx

R32

2

Determine which graph or table to use.

▪ For indoor units: Is the unit ceiling-mounted, wall-mounted or

floor-standing?

▪ For outdoor units installed or stored indoors, and field piping

in  unventilated  spaces,  this  depends  on  the  installation
height:

If the installation height is…

Then use the graph or table for…

<1.8 m

Floor-standing units

1.8≤x<2.2 m

Wall-mounted units

≥2.2 m

Ceiling-mounted units

3

Use the graph or table to determine the minimum floor area.

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

250

260

270

280

290

300

310

320

330

340

350

360

370

380

390

400

410

420

430

440

450

460

470

480

490

500

510

520

530

540

550

1.8

2

2.2

2.4

2.6

2.8

3

3.2

3.4

3.6

3.8

4

4.2

4.4

4.6

4.8

5

5.2

5.4

5.6

5.8

6

6.2

6.4

6.6

6.8

7

7.2

7.4

7.6

7.8

1.843

7.956

8.0

A

min

 (m

2

)

Floor-standing unit 

(c)

Wall-mounted unit 

(b)

Ceiling-mounted unit 

(a)

m (kg)

Summary of Contents for RXJ20M3V1B

Page 1: ...eference guide R32 split series English Installer reference guide R32 split series ARXM25N2V1B9 ARXM35N2V1B9 RXM20N2V1B9 RXM25N2V1B9 RXM35N2V1B9 RXJ20M3V1B RXJ25M3V1B RXJ35M3V1B RXA20A3V1B RXA25A3V1B...

Page 2: ...iping 15 6 5 3 To check for leaks 15 6 5 4 To perform vacuum drying 15 6 6 Charging refrigerant 16 6 6 1 About charging refrigerant 16 6 6 2 About the refrigerant 16 6 6 3 Precautions when charging re...

Page 3: ...ive gloves safety glasses when installing maintaining or servicing the system WARNING Tear apart and throw away plastic packaging bags so that nobody especially children can play with them Possible ri...

Page 4: ...nstallation of pipework shall be kept to a minimum WARNING If appliances contain R32 refrigerant the floor area of the room in which the appliances are installed operated and stored MUST be larger tha...

Page 5: ...gas leaks ventilate the area immediately Possible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into con...

Page 6: ...e fixed wiring WARNING ONLY use copper wires Make sure the field wiring complies with the applicable legislation All field wiring MUST be performed in accordance with the wiring diagram supplied with...

Page 7: ...latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin extranet authentication required 2 2 Installer r...

Page 8: ...y flammable 4 1 Overview About the unit This chapter contains information about Identification of the outdoor unit 4 2 Identification NOTICE When installing or servicing several units at the same time...

Page 9: ...ir outlet b Air inlet NOTICE The height of the wall on the outlet side of the outdoor unit MUST be 1200 mm NOTICE Do NOT stack the units on each other Do NOT hang the unit on a ceiling Strong winds 18...

Page 10: ...eral snowfall is possible make sure that the heat exchanger coil is NOT affected by the snow If necessary install a snow cover or shed and a pedestal 5 2 3 Refrigerant piping length and height differe...

Page 11: ...escribes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages 1 Opening the unit 2 Mounting the outdoor unit 3 Connecting...

Page 12: ...bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping see the following figure NOTICE If the unit is installed in a cold climate take adequate...

Page 13: ...ion period Protection method Outdoor unit 1 month Pinch the pipe 1 month Pinch or tape the pipe Indoor unit Regardless of the period INFORMATION Do NOT open the refrigerant stop valve before checking...

Page 14: ...panner on the stem cap as this could cause a refrigerant leak a b a Spanner b Torque wrench When it is expected that the operating pressure will be low e g when cooling will be performed while the out...

Page 15: ...ely Using the same pump for other refrigerants may damage the pump and the unit NOTICE Connect the vacuum pump to the service port of the gas stop valve Make sure that the gas stop valve and liquid st...

Page 16: ...Vacuum drying on the outdoor unit s internal refrigerant piping is performed NOTICE Before completely recharging perform vacuum drying on the outdoor unit s internal refrigerant piping as well Typical...

Page 17: ...CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label...

Page 18: ...A A a Curled single core wire b Screw c Flat washer Stranded conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c Flat washer O Allowed X NOT allowed Tightening torques...

Page 19: ...cally consists of the following stages 1 Checking the Checklist before commissioning 2 Performing a test run for the system 7 2 Precautions when commissioning DANGER RISK OF ELECTROCUTION DANGER RISK...

Page 20: ...sumes electricity When the power turns back on after a power break the previously selected mode will be resumed 7 6 Starting up the outdoor unit See the indoor unit installation manual for configurati...

Page 21: ...based on symptoms Before troubleshooting Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring 11 2 Precautions when troublesho...

Page 22: ...rate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still runn...

Page 23: ...DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE...

Page 24: ...rtain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Mainten...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P518023 5D 2019 04 Copyright 2018 Daikin...

Reviews: