4 Installation

Installation manual

6

RXF50~71(A)(B)2V1B + RXP50~71L2V1B

R32 split series

3P512025-4C – 2018.01

3.2

Preparing refrigerant piping

3.2.1

Refrigerant piping requirements

Piping material:

 Phosphoric acid deoxidised seamless copper.

Piping diameter:

Liquid piping

Ø6.4 mm (1/4")

Gas piping

Ø12.7 mm (1/2")

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.

3.2.2

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

30 m

Minimum allowable pipe length

3 m

Maximum allowable height distance

20 m

3.2.3

Refrigerant piping insulation

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

12.7 mm (1/2")

14~16 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

4

Installation

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

353

600

240

(mm)

240

>300

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  In  this  case,  it  is
recommended to construct a pedestal.

353

600

240

240

(mm)

>300

100

a

a

Maximum snowfall height

If the unit is installed on brackets fixed to the wall, install the unit as
follows:

Summary of Contents for RXF50B2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B RXP50L2V1B RXP60L2V1B RXP71L2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ore commissioning 11 5 2 Checklist during commissioning 11 5 3 To perform a test run 11 6 Troubleshooting 12 6 1 Fault diagnosis using LED on outdoor unit PCB 12 7 Disposal 12 7 1 To pump down 12 7 2...

Page 5: ...it with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a b...

Page 6: ...istance 20 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 12 7 mm 1 2 14 16 mm i i t p p If the temperature is...

Page 7: ...drain holes and attach the drain socket NOTICE In cold areas do NOT use a drain socket hose and caps 1 2 with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT freeze 1...

Page 8: ...hat the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 4 3 Checking the refrigerant piping 4 3 1 To check for lea...

Page 9: ...gerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuou...

Page 10: ...qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical pa...

Page 11: ...mounted The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The p...

Page 12: ...air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the...

Page 13: ...V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIG...

Page 14: ...uT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffl...

Page 15: ...uT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffler Gas s...

Page 16: ...3P512025 4C 2018 01 Copyright 2018 Daikin...

Reviews: