5 Commissioning

Installation manual

11

RXF50~71(A)(B)2V1B + RXP50~71L2V1B
R32 split series
3P512025-4C – 2018.01

50 Hz

220-240 V

c

d

f

a

b

e

a

Interconnection cable

b

Power supply cable

c

Field fuse

d

Earth leakage circuit breaker

e

Power supply

f

Earth

4

Tighten  the  terminal  screws  securely.  We  recommend  using  a
Phillips screwdriver.

5

Install the switch box cover.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn off the power supply before servicing.

▪ Install the switch box cover before turning on the power

supply.

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.7

About the compressor

DANGER: RISK OF EXPLOSION

▪ Use a pipe cutter to remove the compressor.

▪ Do NOT use the brazing torch.

▪ Use approved refrigerants and lubricants only.

DANGER: RISK OF BURNING

Do NOT touch the compressor with bare hands.

5

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

5.1

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between
the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The indoor unit receives the signals of the 

user interface

.

The  specified  wires  are  used  for  the 

interconnection

cable

.

5.2

Checklist during commissioning

To perform an 

air purge

.

To perform a 

test run

.

5.3

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Test run should be performed in accordance with the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.

Summary of Contents for RXF50B2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B RXP50L2V1B RXP60L2V1B RXP71L2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ore commissioning 11 5 2 Checklist during commissioning 11 5 3 To perform a test run 11 6 Troubleshooting 12 6 1 Fault diagnosis using LED on outdoor unit PCB 12 7 Disposal 12 7 1 To pump down 12 7 2...

Page 5: ...it with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a b...

Page 6: ...istance 20 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 12 7 mm 1 2 14 16 mm i i t p p If the temperature is...

Page 7: ...drain holes and attach the drain socket NOTICE In cold areas do NOT use a drain socket hose and caps 1 2 with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT freeze 1...

Page 8: ...hat the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 4 3 Checking the refrigerant piping 4 3 1 To check for lea...

Page 9: ...gerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuou...

Page 10: ...qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical pa...

Page 11: ...mounted The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The p...

Page 12: ...air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the...

Page 13: ...V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIG...

Page 14: ...uT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffl...

Page 15: ...uT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffler Gas s...

Page 16: ...3P512025 4C 2018 01 Copyright 2018 Daikin...

Reviews: