6 Troubleshooting

Installation manual

12

RXF50~71(A)(B)2V1B + RXP50~71L2V1B

R32 split series

3P512025-4C – 2018.01

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

6

Troubleshooting

6.1

Fault diagnosis using LED on
outdoor unit PCB

LED is…

Diagnosis

flashing

Normal.

▪ Check the indoor unit.

ON

▪ Turn  the  power  OFF  and  back  ON,  and

check  the  LED  within  approximately  3
minutes.
If  the  LED  is  ON  again,  the  outdoor  unit
PCB is faulty.

OFF

1

Supply voltage (for power saving).

2

Power supply fault.

3

Turn  the  power  OFF  and  back  ON,  and
check  the  LED  within  approximately  3
minutes.
If the LED is ON again, the outdoor unit
PCB is faulty.

DANGER: RISK OF ELECTROCUTION

▪ When  the  unit  is  not  operating,  the  LEDs  on  the  PCB

are turned off in order to save power.

▪ Even when the LEDs are off, the terminal block and the

PCB may be powered.

7

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

7.1

To pump down

Example: 

To  protect  the  environment,  pump  down  when  relocating

the unit or when disposing of the unit.

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

  If  you  want  to  pump

down  the  system,  and  there  is  a  leak  in  the  refrigerant
circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the
system  into  the  outdoor  unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor
because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

NOTICE

During pump down operation, stop the compressor before
removing  the  refrigerant  piping.  If  the  compressor  is  still
running and the stop valve is open during pump down, air
will be sucked into the system. Compressor breakdown or
damage to the system can result due to abnormal pressure
in the refrigerant cycle.

Pump down operation will extract all refrigerant from the system into
the outdoor unit.

1

Remove  the  valve  cap  from  the  liquid  stop  valve  and  the  gas
stop valve.

2

Carry  out  forced  cooling.  See 

"7.2  To  start  and  stop  forced

cooling" on page 12

.

3

After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<−10°C)), close the liquid stop valve
with a hexagonal wrench.

4

Check on the manifold if the vacuum is reached.

5

After  2-3  minutes,  close  the  gas  stop  valve  and  stop  forced
cooling.

c

b

e

d
d

a

a

Gas stop valve

b

Closing direction

c

Hexagonal wrench

d

Valve cap

e

Liquid stop valve

7.2

To start and stop forced cooling

There are 2 methods to perform forced cooling.

Method 1.

 Using the indoor unit ON/OFF switch (if present on the

indoor unit).

Method 2.

 Using the indoor unit user interface.

7.2.1

To start/stop forced cooling using the
indoor unit ON/OFF switch

1

Press the ON/OFF switch for at least 5 seconds.

Result: 

Operation will start.

Note: 

 Forced cooling stops automatically after 15 minutes.

2

To stop operation sooner, press the ON/OFF switch.

7.2.2

To start/stop forced cooling using the
indoor unit user interface

1

Set the operation mode to 

cooling

.

For the procedure, refer to "To perform a test run" in the installation
manual of the indoor unit.

Note: 

  Forced  cooling  will  stop  automatically  after  around

30 minutes.

2

To stop operation sooner, press the ON/OFF switch.

INFORMATION

If  forced  cooling  is  used  and  the  outside  temperature  is  <
−10°C, the safety device may prevent operation.

▪ Warm  the  outside  temperature  thermistor  on  the

outdoor unit to ≥−10°C. 

Result: 

 Operation will start.

Summary of Contents for RXF50B2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B RXP50L2V1B RXP60L2V1B RXP71L2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ore commissioning 11 5 2 Checklist during commissioning 11 5 3 To perform a test run 11 6 Troubleshooting 12 6 1 Fault diagnosis using LED on outdoor unit PCB 12 7 Disposal 12 7 1 To pump down 12 7 2...

Page 5: ...it with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a b...

Page 6: ...istance 20 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 12 7 mm 1 2 14 16 mm i i t p p If the temperature is...

Page 7: ...drain holes and attach the drain socket NOTICE In cold areas do NOT use a drain socket hose and caps 1 2 with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT freeze 1...

Page 8: ...hat the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 4 3 Checking the refrigerant piping 4 3 1 To check for lea...

Page 9: ...gerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuou...

Page 10: ...qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical pa...

Page 11: ...mounted The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The p...

Page 12: ...air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the...

Page 13: ...V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIG...

Page 14: ...uT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffl...

Page 15: ...uT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffler Gas s...

Page 16: ...3P512025 4C 2018 01 Copyright 2018 Daikin...

Reviews: