3 Preparation

Installation manual

5

RXF50~71(A)(B)2V1B + RXP50~71L2V1B
R32 split series
3P512025-4C – 2018.01

3

Preparation

3.1

Preparing the installation site

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

▪ Choose  the  installation  location  with  sufficient  space  for  carrying

the unit in and out of the site.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

>100

>50

>350

(mm)

b

a

>100

>50

b

a

>100

b

a

b

a

>350

>350

>50

b

a

a

Air outlet

b

Air inlet

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

It  is  recommended  to  install  a  baffle  plate  when  the  air  outlet  is
exposed to wind.

It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.

b

a

b

c

a

Baffle plate

b

Prevailing wind direction

c

Air outlet

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

3.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"4.1  Mounting  the

outdoor unit" on page 6

 for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

Summary of Contents for RXF50B2V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXF50B2V1B RXF60B2V1B RXF71A2V1B RXP50L2V1B RXP60L2V1B RXP71L2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...ore commissioning 11 5 2 Checklist during commissioning 11 5 3 To perform a test run 11 6 Troubleshooting 12 6 1 Fault diagnosis using LED on outdoor unit PCB 12 7 Disposal 12 7 1 To pump down 12 7 2...

Page 5: ...it with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet Do NOT install the unit in sound sensitive areas e g near a b...

Page 6: ...istance 20 m 3 2 3 Refrigerant piping insulation Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 12 7 mm 1 2 14 16 mm i i t p p If the temperature is...

Page 7: ...drain holes and attach the drain socket NOTICE In cold areas do NOT use a drain socket hose and caps 1 2 with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT freeze 1...

Page 8: ...hat the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 4 3 Checking the refrigerant piping 4 3 1 To check for lea...

Page 9: ...gerant type R32 Global warming potential GWP value 675 WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuou...

Page 10: ...qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical pa...

Page 11: ...mounted The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The p...

Page 12: ...air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the...

Page 13: ...V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIG...

Page 14: ...uT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffl...

Page 15: ...uT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Muffler Compressor Accumulator Muffler Muffler Muffler Gas s...

Page 16: ...3P512025 4C 2018 01 Copyright 2018 Daikin...

Reviews: