6

English

2. 

Drain work

•  If the drain port is covered by a mounting base or floor 

surface, place additional foot bases of at least 1-1/4 
inch (30mm) in height under the outdoor unit’s feet.

• 

In cold areas, do not use a drain socket, drain caps 
(1,2) and a drain hose with the outdoor unit. (Drain 
water may freeze, impairing heating performance.)

1) Attach 

C

 drain cap (1) and 

D

 drain cap (2).

2) Attach 

B

 drain socket.

• 

When attaching 

B

 drain socket to the bottom 

frame, make sure to connect the drain hose to the 

drain socket first.

3. 

Flaring the pipe end

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward, so that the filings do not enter the 

pipe.

3) 

Put the flare nut on the pipe.

4) Flare the pipe.
5) 

Check that the flaring has been done correctly.

Check

The flare's 
inner surface 
must be 
flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Set exactly at the position shown below.

Flaring

A

Die

A

0-0.020 inch 

(0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch 

(1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch 

(1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Cut exactly at 
right angles.

 Remove burrs.

WARNING

•  Do not apply mineral oil to the flare.
• 

Prevent mineral oil from getting into the system as this would reduce the service life of the units.

• 

Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.

• 

Never install a dryer to this R410A unit in order to guarantee its service life.

• 

The drying material may dissolve and damage the system.

•  Incomplete flaring may result in refrigerant gas leakage.

4. 

Refrigerant piping

CAUTION

•  Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)
•  To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
•  Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

•  Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration  
oil only to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 
with excessive torque.

Apply oil

Flare nut tightening torque

Gas side

3/8 inch (9.5mm)

1/2 inch (12.7mm)

24-1/8 –

29-1/2lbf • ft

(32.7-39.9N • m)

36-1/2 –

44-1/2lbf • ft

(49.5-60.3N • m)

5/8 inch (15.9mm)

45-5/8 –

55-5/8lbf • ft

(61.8-75.4N • m) 

10-1/2 –

12-3/4lbf • ft

(14.2-17.2 N

 • 

m)

Liquid side

1/4 inch (6.4mm)

Service port cap tightening torque

8 –

10-7/8lbf • ft (10.8-14.7N • m)

Width across flats

11/16 inch (17mm)

(14.2-17.2N • m)

10-1/2–12-5/8lbf • ft

3/4 inch (19mm)

(17.1-20.9N • m)

12-5/8–

15-3/8lbf • ft

7/8 inch (22mm)

(21.6-27.4N • m)

16–

20-1/4lbf • ft

1-1/16 inch (27mm)

(48-59.8N • m)

35-3/8–

44-1/8lbf • ft

Valve cap 

tightening torque

Bottom frame

Drain cap

Pinch the bottom 
frame in.

Drain cap (1)

Drain cap (1)

Air outlet side

C

C

Drain cap (2)

D

Drain 
socket

B

Drain cap (1)

Drain cap (2)

D

Drain cap (2)

Air outlet side

B

Drain 
socket

C

D

09/12 class

15/18/24 class

Bottom frame

 Drain socket

Hose (available commercially,
inner dia. 5/8 ” (16mm))

B

English

01_EN_3P500432-5E.indd   6

10/17/2019   4:40:24 PM

Summary of Contents for RX15RMVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n MODELS RX15RMVJU RX18RMVJU9 RX24RMVJU RX15RMVJUA RX18RMVJU9A RX24RMVJ...

Page 2: ...hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting i...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...ble gas leaks in the surrounding area 7 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will...

Page 5: ...lt in reduced performance The suggested shortest pipe length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit i...

Page 6: ...all facing one side Walls facing two sides Top view Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15...

Page 7: ...vice life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is...

Page 8: ...ssure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose to the gas stop valve s service port 3 Fully open the gauge manifold s low pres...

Page 9: ...insulation materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to...

Page 10: ...2 3 1 2 3 Follow local codes for wiring and safety devices between outdoor unit and power source Ground Firmly x the wires with the terminal screws Recommend using AWG14 stranded and insulated wire fo...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...tion In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out forced cooling o...

Page 13: ...ter about 30 minutes To stop the operation press Trial Operation and Testing 1 Trial operation and testing Refer to the installation manual for the indoor unit 2 Test items Test items Symptom Check In...

Page 14: ...Two dimensional bar code is a manufacturing code 3P500432 5E M19B232 1912 HT...

Reviews: