background image

7

English

Outdoor Unit Installation

5. 

Pressure test and evacuating system

WARNING

• 

Make sure that air or any matter other than refrigerant (R410A) does not get into the refrigeration cycle.

• 

If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.

• 

R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.

•  Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum 

pump or the unit.

• 

When piping work is complete, it is necessary to perform a pressure test 
and evacuate system with a vacuum pump.

• 

If using additional refrigerant, purge the air from the refrigerant pipes and 
indoor unit using a vacuum pump, then charge additional refrigerant.

•  Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• 

All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 
pressure gauge

Pressure 
meter

High-pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 550psi (3.8MPa) (do not pressurize 

more than 550psi (3.8MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 
make repairs and perform the pressure test again.

2) Connect the gauge manifold's charging hose to the gas stop valve’s service port.
3) Fully open the gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi). 

(High-pressure valve will require no further operation.)

4) 

Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.

5) Close the gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. 

(Maintain this condition for 4-5 minutes to make sure that the compound pressure gauge pointer does not swing back.)*

1

6) Remove the valve caps from the liquid stop valve and gas stop valve.
7) 

Turn the liquid stop valve’s rod 90° counter-clockwise with a hexagonal wrench to open the valve.

 

Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.

8) Disconnect the charging hose from the gas stop valve’s service port, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rod further than it can go.)

9) 

Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified 

torques. 
Refer to 

“4. Refrigerant piping”

 on page 6 for details.

*

1

  If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose 

pipe joint. 
Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).

01_EN_3P500432-5E.indd   7

10/17/2019   4:40:24 PM

Summary of Contents for RX15RMVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n MODELS RX15RMVJU RX18RMVJU9 RX24RMVJU RX15RMVJUA RX18RMVJU9A RX24RMVJ...

Page 2: ...hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting i...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...ble gas leaks in the surrounding area 7 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will...

Page 5: ...lt in reduced performance The suggested shortest pipe length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit i...

Page 6: ...all facing one side Walls facing two sides Top view Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15...

Page 7: ...vice life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is...

Page 8: ...ssure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose to the gas stop valve s service port 3 Fully open the gauge manifold s low pres...

Page 9: ...insulation materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to...

Page 10: ...2 3 1 2 3 Follow local codes for wiring and safety devices between outdoor unit and power source Ground Firmly x the wires with the terminal screws Recommend using AWG14 stranded and insulated wire fo...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...tion In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out forced cooling o...

Page 13: ...ter about 30 minutes To stop the operation press Trial Operation and Testing 1 Trial operation and testing Refer to the installation manual for the indoor unit 2 Test items Test items Symptom Check In...

Page 14: ...Two dimensional bar code is a manufacturing code 3P500432 5E M19B232 1912 HT...

Reviews: