Facility Setting*

(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). 

Never use it in a residence or offi ce (the space where there is a human).

*Only for RX, RK, and RXL models.

 

Cutting jumper 6 (J6)

 on the circuit board will expand the operation range down to 5°F (–15°C). However it will stop if the 

outdoor temperature drops below –4°F (–20°C) and start back up once the temperature rises again.

1)  Remove the top plate of the outdoor unit. (09/12 class: 3 screws, 15/18/24 class: 6 screws)
2)  Remove the front plate. (09/12 class: 4 screws, 15/18/24 class: 8 screws)
3)  Cut the jumper (J6) of the PCB inside. 

CAUTION

• 

If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.

• 

Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.

•  Do not place humidifi ers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifi er might cause dew jumping from the indoor unit outlet vent.

• 

Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1) Remove the valve cap from the liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

 

Using the indoor unit ON/OFF switch 

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.) 

• 

Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

Service port

 

Using the indoor unit’s remote controller

[For wall mounted units]

1) Press 

 , 

 and 

 at the same time.

2) Press 

 , then select   , press 

 .

3) Press 

 to turn on the system.

• 

Forced cooling operation will stop automatically after about 30 minutes.
To stop the operation, press 

HEAT PUMP model

COOLING ONLY model

[For fl oor standing units]

1) Press 

 and select the COOL operation.

2) Press 

 to turn on the system.

3) Press 

 , 

 and 

 at the same time. 

4) Press 

 , select “ 

 ”, and press 

 for confi rmation.

• 

Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press 

 .

CAUTION

• 

When pressing the switch, do not touch the terminal block. It has a high voltage, and touching it could cause electric shock.

01_EN_3P379970-6B.indd   11

11/13/2015   15:48:29

Summary of Contents for RX09NMVJU

Page 1: ...U RXN18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...re should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet ra...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 6B M15B135 1511 HT...

Reviews: