Trial Operation and Testing

1. 

Trial operation and testing

•  Trial operation should be carried out in either COOL or HEAT operation.

1-1. 

Measure the supply voltage and make sure that it is within the specified range.

1-2. In COOL operation, select the lowest programmable temperature;  

in HEAT operation, select the highest programmable temperature.

1-3. Carry out the trial operation following the instructions in the operation manual to 

ensure that all functions and parts, such as the movement of the flap, are working 

properly.

• 

To protect the air conditioner, restart operation is disabled for 3 minutes after the system has been turned off.

1-4. After trial operation is complete, set the temperature to a normal level (78°F 

to 82°F (26°C to 28°C) in COOL operation, 68°F to 75°F (20°C to 24°C) in HEAT 
operation).

•  When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, activate trial operation 

mode by following the instructions in the installation manual for the indoor unit.

• 

The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some time after 
installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• 

If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode 
when the circuit breaker is opened again.

2. 

Test items

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly grounded.

Electrical leakage

The specified wires are used for inter-unit wiring.

No operation or burn damage

Indoor or outdoor unit’s air inlet or air outlet are unobstructed.

Incomplete cooling/heating 
function

Stop valves are opened.

Incomplete cooling/heating 
function

Indoor unit properly receives remote control commands.

No operation

English

01_EN_3P379970-6B.indd   12

11/13/2015   15:48:30

Summary of Contents for RX09NMVJU

Page 1: ...U RXN18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split...

Page 2: ...ts and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe s...

Page 3: ...re should be prevented from getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet ra...

Page 4: ...re more than 10ft 3m away depending on radio wave conditions 8 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditio...

Page 5: ...length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 1...

Page 6: ...w Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15 16 100 More than 13 3 4 350 More than 1 15 16 50 W...

Page 7: ...in order to guarantee its service life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut f...

Page 8: ...e than 550psi 3 8MPa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose t...

Page 9: ...on materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kca...

Page 10: ...Tighten the terminal screws securely It is recommended that a flathead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 Circuit breaker Ground fault...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...Pump Down Operation In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out f...

Page 13: ...the instructions in the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation...

Page 14: ...Two dimensional bar code is a manufacturing code 3P379970 6B M15B135 1511 HT...

Reviews: