background image

English

16

10. CHECKS AFTER INSTALLATION

WARNING

• Never connect power supply wiring to the terminal block for remote 

controller wiring as this could damage the entire system.

Attach the power wire securely.

To avoid injury, always make sure that the circuit breaker on the power 
supply panel of the installation is switched off before doing any work.

After the installation, check the following before switching on the circuit
breaker:

1.

The position of the switches that requires an initial setting
Make sure that switches are set according to your application needs 
before turning the power supply on.

2.

Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and make 
sure that it has been carried out according to the instructions 
described in this manual, the wiring diagrams and local and national 
regulations.

3.

Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the insulation 
work is properly executed.

4.

Additional refrigerant charge
The amount of refrigerant to be added to the unit should be written 
on the included “Additional Refrigerant” label, and attach it to the 
rear side of the front cover.

5.

Measurement of insulation in main power circuit
Using a megatester for 500V, check that the insulation resistance of 
2M

 or more is attained by applying a voltage of 500V DC between 

power terminals and earth. Never use the megatester for the trans-
mission wiring.

6.

Installation date
Be sure to keep record of the installation date on the “Additional 
Refrigerant” label.

11. TEST RUN

CAUTION

After completing installation, be sure to open the valves.
(Operating the unit with the valves shut will break the compressor.)

11-1 Air discharge

• Running the heat source water pump, carry out air discharge 

process until the water comes out from the air discharge hole of local 
piping.
(For the operation to be done for the first time after installation, you 
need to perform a checking operation.)

11-2 Before turn on the power supply

• Close the electrical components lid securely before turning on power.
• Make settings for outside unit PC board (A1P) after power-on and 

check the LED display from inspection door that is on the electrical 
components box lid.

11-3 Check operation

When running the unit for the first time after installation, be sure to per-
form a test operation following these steps. (Not performing a test oper-
ation when the unit is first installed may prevent the unit from operating 
properly.)

• During the operation, monitor the outdoor unit operation status and 

check for any incorrect wiring.

(Refer to figure 27)

1.

Electrical components box

2.

Electrical components box lid

3.

Service lid

4.

Inspection cover

5.

[Service precaution] Label

(1) Check the connection of interlock

circuit

The outside unit cannot be operated if the 
interlock circuit has not been connected.

(2) • As necessary, configure the system 

settings onsite by using the 
dipswitch (DS1) on the outside unit 
PC-Board (A1P) and push button 
switches (BS1 to 5).

• When the system is in the multiple-

outside unit configuration (Out Multi), 
perform the configuration on the 
main unit. (Any settings made on a 
sub unit will be ignored.)

After this, close the electrical compo-
nents box lid.

Always perform configuration after turning 
ON the power. To learn the setting method, 
refer to the [Service Precautions] label 
attached at the position shown in the figure 
on the right
(Electric box lid in outside unit).
(Remember, the actual settings you have 
made must be recorded on the [Service 
Precautions] label.)

(3) Turn ON the power to the outside 

units and indoor units.

Make sure to turn ON the power 6 hours 
before starting the operation. This is neces-
sary to warm the crankcase preliminarily by 
the electric heater.

(4) Start the heat source water pump 

and fill the heat source water in the 
outside unit.

The outside unit cannot be operated if the 
heat source water pump is not running.

(5) Make sure that the temperature of 

heat source water is kept within the 
operation range (60 - 100 °F).

The outside unit cannot be operated at a 
temperature outside the operation range.

(6) Check the LED on the PC board (A1P) in the outside unit to see if the data trans-

mission is performed normally.

(7) • Using the push button switches 

(BS1 - 5) on the PC board (A1P) of 
outside unit, carry out a local set-
ting, if necessary.

• When the system is in the multiple-

outside unit configuration (Out 
Multi), perform the configuration on 
the main unit. (Any settings made 
on a sub unit will be ignored.)

Always perform configuration after turning 
ON the power. To learn the setting method, 
refer to the [Service Precautions] label 
attached at the position shown in the figure 
on the right
(Electric box lid in outside unit).
(Remember, the actual settings you have 
made must be recorded on the [Service 
Precautions] label.)

(8) Check all stop valves are opened. 

If some stop valve is closed, open 
them.
(Refer to “

9-10 Stop valve operation 

procedure

”.)

[CAUTION]

Do not leave any stop valve closed. 
Otherwise the compressor will fail.
For Heat recovery system of cooling and 
heating:
Open all stop valves on the suction side, 
discharge gas side and liquid side.
For cooling and heating switching operation 
system:
Open the stop valves on discharge gas side 
and liquid side. 

(Keep the stop valve on 

suction side fully closed.)

(9)Perform the check operation following 

the instructions printed on the
[Service Precautions] label.

If you push the test run button (BS4) on the 
PC board (A1P) of the outside unit for 5 
seconds, the test run starts.
If you want to interrupt the test run, push 
the RETURN button (BS3) on PC board 
(A1P) of the outside unit. The system con-
tinues residual operation for about 1 minute 
(maximum 10 minutes) and then stops.
(During test run, you cannot stop it by a 
command from a remote controller.)

You need to perform the above settings 
on the PCB by accessing the PCB 
through the inspection cover on the 
switch box cover.

Bulk
(main)

Bulk
(sub)

Multi

Demand

(

) The base (main) unit is the outside unit to which the interconnecting wiring for the

indoor units is connected. The other outside units are sub units.

LED display 
(Default status 
before delivery)

One outside unit installed

When multiple 
outside unit 
installed (

)

Master station
Sub station 1

Sub station 2

Microcomputer 
operation 
monitor

Page

HAP

H1P

H2P

H3P

H4P

H5P

H6P

H7P

H8P

Ready/
Error

Cooler/heater changeover

Individual

Low 
noise

LED display:

OFF

ON

Blinking

Summary of Contents for RWEYQ144PTJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Page 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Page 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Page 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Page 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Page 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Page 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Page 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Page 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Page 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Page 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Page 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Page 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Page 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Page 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Page 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Page 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Page 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Page 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Page 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Page 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Page 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Page 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Reviews: