background image

9

English

Connect the wire to the terminal block on PC board with care since too 
much pressure may cause breakage of the PC board.
Field line connection: transmission wiring, interlock circuit, pump oper-
ation output and COOL/HEAT selector
Power and transmission line: Connect it using conduit mounting plates.

[In case of single outside unit]

(Refer to figure 10)

1.

COOL/HEAT selector

2.

Outside unit PC board (A1P)

3.

Take care of the polarity

4.

Use the conductor of sheathed wire (2 wire)(no polarity)

5.

Terminal board (field supply)

6.

Indoor unit

7.

Never connect the power wire.

8.

BS unit A

9.

BS unit B

10.

Last BS unit

11.

Cool-only unit

[In case of multiple outside units]

(Refer to figure 11)

1.

Unit A (Master unit)

2.

Unit B

3.

Unit C

4.

TO IN/D UNIT

5.

TO OUT/D UNIT

6.

TO MULTI UNIT

7.

To COOL/HEAT selector (only Heat pump system)

8.

To indoor unit

9.

To other systems

• The transmission wiring between the outside units in the same pipe 

line must be connected to the Q1/Q2 (Out Multi) terminals.
Connecting the wires to the (Out-Out) terminals results in system 
malfunction.

• The wiring for the other lines must be connected to the F1/F2 (Out-

Out) terminals of the PC board in the outside unit to which the trans-
mission wiring for the indoor units is connected.

• The outside unit to which the transmission wiring for the indoor units 

is connected is master unit.

• The transmission wiring between the outside units must be 100 ft. in 

length at maximum.

NOTE

• Be sure to keep the power  line and transmission line apart from 

each other.
Be careful about polarity of the transmission line.
Make sure that the transmission line is clamped as shown in the fig-
ure in chapter “Field line connection”.
Check that wiring lines do not make contact with refrigerant piping.
Firmly close the lid and arrange the electric wires so as to prevent 
the lid or other parts from coming loose.

[Setting the interlock circuit and pump operation output.]

Pump operation output [high voltage]

• Use insulated wires of the size as mentioned below having rated volt-

age of 250 V or more:
For single core: AWG16 or larger (conduit pipe work)
For multiple cores: AWG18 or larger

 *The wiring for pump operation output is to be procured locally.

(Refer to figure 12)

1.

Pump operation output terminal (X2M).
When water pump is linked with system operation, water 
pump operation circuit shall be set between terminals (1) 
and (2).
Contact specification --- 220 VAC, 3mA-0.5A

2.

PC board (A1P)

3.

Mount an insulation sleeve.

4. Connection of interlock circuit

Do not forget to connect an interlock circuit (an auxiliary a-
contact of electromagnetic switch for the water pump) to 
each outside unit.
(Select without fail an auxiliary a-contact able to switch min-
imum load of DC15V, 1mA.)

When connecting for each outside unit

Connect to the terminal block (X3M) as shown in the bottom 
right of the sketch.

When connecting multiple outside units as 1 single unit 

(centralized interlock)

For this unit, it is possible to make a centralized interlock of 
multiple outside units using an adapter (sold separately as 
an accessory) for external control of outside units.
For details of wiring connection, refer to “

How to central-

ized interlock wiring

”.

How to the centralized interlock wiring

• When centralized interlock is done, see “

8-5 In case of a local set-

ting

” -(3)

• No wiring to terminal block X3M is necessary when centralized inter-

lock is employed

• For multiple outside units, external/external connection wiring shall 

be done for master unit only.

(Refer to figure 13)

1.

Outside unit A

2.

Outside unit B

3.

Outside unit C

4.

Adapter for external control

5.

Interlock circuit of water pump

6.

Out-Out connection wiring

7.

Use the conductor of sheathed wire (2 wire)(no polarity)

[Setting the cool/heat operation type]

1.

Performing cool/heat setting with the remote controller con-
nected to the indoor unit.
Keep the COOL/HEAT selector switch (DS1) on the outside unit 
PC board (A1P) at the factory setting position OFF.

(Refer to figure 16)
1.

 Remote controller

2.

Performing cool/heat setting with the COOL/HEAT selector.
Connect the COOL/HEAT selector (optional) to the A/B/C termi-
nals and set the COOL/HEAT selector switch (DS1) on the out-
side unit PC board (A1P) to ON.

(Refer to figure 17)
1.

 COOL/HEAT selector

• The wiring from the indoor units must be connected to the F1/F2

(In-Out) terminals on the PC board in the outdoor unit.

• For the above wiring, always use sheathed vinyl cords with AWG18-

16 sheath or cables (2 core wires). (3 core wire are allowable for the 
COOL/HEAT selector only.)

NOTE

• All transmission wire is field supply.
• Be sure to follow the limits below. If the transmission wiring is beyond 

these limits, it may result in malfunction of transmission.
Maximum wiring length:

3280 ft.

Total wiring length:

6560 ft.

Max. branches No. of branches:

16

Wire length between outside units:98 ft.

Up to 16 branches are possible for transmission wiring. No branch-
ing is allowed after branching.

Never connect the power supply to transmission wiring terminal 
block. Otherwise the entire system may break down.

(Refer to figure 14)

1.

Branch

2.

Subbranching

For low-noise operation, it is necessary to get the optional “Exter-
nal control adaptor for outdoor unit”.
For details, see the installation manual attached to the adaptor.

Top plate

Conduit 
(field supply)

Lock nut 
(field supply)

Conduit 
mounting 
plate 
(accessory)

Top plate

Summary of Contents for RWEYQ144PTJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Page 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Page 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Page 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Page 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Page 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Page 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Page 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Page 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Page 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Page 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Page 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Page 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Page 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Page 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Page 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Page 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Page 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Page 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Page 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Page 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Page 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Page 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Reviews: