background image

11

English

9.

REFRIGERANT PIPING

CAUTION

After completing installation, be sure to open the valves. 
(See 

9-9 Additional refrigerant charge

 for details) (Operating the

unit with the valves shut will break the compressor.)
Use R410A to add refrigerant. (The R410A refrigerant cylinder has
a pink stripe painted around it.)
All field piping must be installed by a licensed refrigeration techni-
cian and must comply with relevant local and national regulations.

CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING

Do not use flux when brazing copper-to copper refrigerant piping. 
(Particularly for the HFC refrigerant piping) Therefore, use the 
phosphor copper brazing filler metal (BCuP-2: JIS Z 3264/B-
Cu93P-710, 795: ISO 3677) which does not require flux.
(Flux has an extremely negative effect on refrigerant piping sys-
tems. For instance, if the chlorine based flux is used, it will cause 
pipe corrosion or, in particular, if the flux contains fluorine, it will 
damage the refrigerant oil.)

NOTE

Installation tools:

Gauge manifold, charge hose, etc.

Make sure to use installation tools that are exclusively used for 
R410A installations to withstand the pressure and to prevent for-
eign materials (e.g. mineral oils such as SUNISO and moisture) 
from mixing into the system.
(The screw specifications differ for R410A and R407C.)

Vacuum pump

 

1.

Use a 2-stage vacuum pump with a non-return valve.

2.

Make sure the pump oil does not flow oppositely into the system 
while the pump is not working.

3.

Use a vacuum pump which can evacuate to –14.6 psi.

9-1 Selection of piping material

1.

Foreign materials inside pipes (including oils for fabrication) must be 
9 mg/10 ft or less.

2.

Use the following material specification for refrigerant piping:

Construction material: Phosphoric acid deoxidized seamless 
copper for refrigerant.

Size: Determine the proper size referring to chapter “Example of 
connection”.

The wall thickness of the refrigerant piping should comply with 
relevant local and national regulations. For R410A the design 
pressure is 450 psi.

3.

Make sure to use the particular branches of piping that have been 
selected referring to chapter “Example of connection”.

4.

Refer to chapter “Stop valve operation procedure” in 9-10 about the 
stop valve operation procedure.

5.

Make sure to perform the piping installation within the range of the 
maximum allowable pipe length, allowable level difference and allow-
able length after branching as indicated in chapter “Example of con-
nection”

6.

For installation of the refrigerant branching kit, refer to the installation 
manual delivered with the kit.
And follow the conditions listed below.

Mount the REFNET joint so that it branches either horizontally or 
vertically.

Mount the REFNET header so that it branches horizontally.

(Refer to figure 22)

1.

Horizontal connections

2.

Up to ± 30° or vertically

3.

Horizontal connections

7.

To connect the piping between outside units, an optional piping kit 
(multi connection piping kit) is always required. When installing the 
piping, follow the instructions in the installation manual that comes 
with the kit.

Restriction for the installation of the outside unit multi connection 
piping kit

• Install the joint horizontally within a lean of ±15° with caution name-

plate on top. Refer to figure 23 (Fig. A)
Do not connect it vertically. Refer to figure 23 (Fig. B)

• Reserve the straight part of 19-11/16 in. or more to the branch pipe 

and do not bend the local pipe in that area.Straight part of 19-11/16 
in. or more can be reserved if a local pipe (straight pipe) of 4-3/4 in. 
or more is connected to the joint. Refer to figure 23 (Fig. C)

• Incorrect installation may cause breakage of outside unit.

(Refer to figure 23)

1.

Caution nameplate

2.

Horizontal line

3.

Ground

4.

Straight part of 19-11/16 in. or more

5.

Local pipe
(4-3/4 in. length or more)

Precautions when selecting branch piping.

• If the overall equivalent length of piping between the outside units 

and indoor units is 262.5 ft or more, be sure to enlarge the main pipe 
in the liquid-side branch piping.
Depending on the length of the refrigerant piping, the cooling/heat-
ing capacity may drop, but even in such cases it is ok to enlarge the 
main pipe.

(Refer to figure 21)

1.

Outside unit

2.

Main pipe

3.

Enlarge

4.

The first refrigerant branching kit.

5.

Indoor unit

[Liquid side]

RWEYQ72/84PTJU type: 

............................................ φ

3/8”

 

φ

1/2”

RWEYQ144PTJU type: 

............................................... φ

1/2”

 

φ

5/8”

RWEYQ168/216PTJU type: 

....................................... φ

5/8”

 

φ

3/4”

RWEYQ252PTJU type: 

............................................... φ

3/4”

 

φ

7/8”

9-2 Protection against contamination when install-

ing pipes

Take measures to prevent foreign materials like moisture and 
contamination from mixing into the system.

Great caution is needed when passing copper tubes through 
walls.

9-3 Pipe connection

Only use the flare nuts included with the unit.
Using different flare nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized film
on the inside of the pipes, adversely affecting valves and com-
pressors in the refrigerating system and preventing normal oper-
ation.)

Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazing (B-Cu93P-710/795: ISO 3677)
which does not require flux.
(Flux has an extremely negative effect on refrigerant piping sys-
tems. For instance, if chlorine based flux is used, it will cause pipe
corrosion. If the flux contains fluorine, it will damage the refriger-
ant oil.)

DANGER

Use of oxygen could cause an explosion resulting in severe injury 
or death. Only use nitrogen gas.

Refrigerant gas may produce toxic gas if it comes in contact with fire 
such as from a fan heater, stove or cooking device. Exposure to this 
gas could cause severe injury or death.

NOTE

The pressure regulator for the nitrogen released when doing the
brazing should be set to 2.9 psi or less.

(Refer to figure 18)

1.

Refrigerant piping

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Manual valve

6.

Regulator

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

Summary of Contents for RWEYQ144PTJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Page 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Page 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Page 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Page 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Page 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Page 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Page 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Page 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Page 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Page 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Page 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Page 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Page 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Page 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Page 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Page 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Page 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Page 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Page 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Page 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Page 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Page 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Reviews: