background image

English

8

8.

FIELD WIRING

NOTE

• All field wiring and components must be installed by a licensed elec-

trician and must comply with relevant local and national regulations.

• The field wiring must be carried out in accordance with the wiring 

diagrams and the instructions given below.

• Be sure to use a dedicated power circuit. Never use a power supply 

shared by another appliance.

• Do not operate until refrigerant piping work is completed.

(If operated before complete the piping work, the compressor may 
be broken down.)

• Never remove thermistor, sensor or etc. when connecting power wir-

ing and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compressor 
may be broken down.)

• Be sure to install a ground fault circuit interrupter.

(This unit uses an inverter, so install a ground fault circuit interrupter 
that be capable of handling high harmonics in order to prevent mal-
functioning of a ground fault circuit interrupter itself.)

• This product have reversed phase protection detector only works 

when the product started up.

• Replace two of the three phases (L1, L2, and L3) during reverse-

phase protection circuit operation.
Reversed phase detection is not performed while the product is 
operating.

• Do not run the unit by short cutting the protection device (S1PH).

If there exists the possibility of reversed phase, lose phase, momen-
tary black out or the power goes on and off while the product is oper-
ating, attach a reversed phase protection circuit locally. Running the 
product in reversed phase may break the compressor and other 
parts.

• Attach the power wire securely.

8-1 Optional parts

COOL/HEAT Selector
S1S ...............................Selector switch (fan, cool/heat)
S2S ...............................Selector switch (cool/heat)

NOTE

Use copper conductors only.

When using the adaptor for sequential start, refer to chapter “Exam-
ples”.

For connection wiring to outdoor-outdoor transmission F1-F2, out-
door-indoor transmission F1-F2, refer to chapter “Examples”.

For connection wiring to the central remote controller, refer to the
installation manual of the central remote controller.

Use insulated wire for the power cord.

8-2 Power circuit and cable requirements

A power circuit (see table below) must be provided for connection of the 
unit. This circuit must be protected with the required safety devices, i.e. 
a main switch, a slow blow fuse on each phase and a ground fault circuit 
interrupter.

NOTE

Select the power supply cable in accordance with relevant local and
national regulations.

Wire size must comply with the applicable local and national code.

Specifications for local wiring power cord and branch wiring are in
compliance with local cord.

8-3 General

• Make sure to connect the power source wire to the power source ter-

minal block and to clamp it as shown in figure 8, chapter “Field line 
connection”.

• As this unit is equipped with an inverter, installing a phase advancing 

capacitor will not only reduce the power factor improvement effect, 
but also may cause the capacitor to overheat due to high-frequency 
waves. Therefore, never install a phase advancing capacitor.

• Keep power imbalance within 2% of the supply rating.

1.

Large imbalance will shorten the life of the smoothing capacitor.

2.

As a protective measure, the product will stop operating and an 
error indication will be made, when power imbalance exceeds 4% 
of the supply rating.

• Follow the “electrical wiring diagram” when carrying out any electri-

cal wiring.

• Only proceed with wiring work after blocking off all power.
• Always ground wires. (In accordance with national regulations of the 

pertinent country.)

This unit uses an inverter, and therefore generates noise, which will
have to be reduced to avoid interfering with other devices. The outer
casing of the product may take on an electrical charge due to leaked
electrical current, which will have to be discharged with the ground-
ing.

This unit has a negative phase protection circuit. (If it operates, only
operate the unit after correcting the wiring.)

WARNING

• Do not ground units to gas pipes, sewage pipes, lightning rods, or 

telephone ground wires because incomplete grounding could 
cause a severe shock hazard resulting in severe injury or death.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

8-4 Examples

System example (Refer to figure 8)

1.

Field power supply

2.

Main switch

3.

Disconnect switch

4.

Fuse

5.

Ground fault circuit interrupter

6.

Remote controller

7.

Outside unit

8.

BS unit

9.

Indoor unit

10.

Cool / heat selector

power supply wiring (sheathed cable)

transmission wiring (sheathed cable)

CAUTION

• Use a power wire pipe for the power wiring.
• Outside the unit, make sure the low-voltage electric wiring (i.e. for the 

remote controller, tarnsmission, etc.) and the high-voltage electric wir-
ing do not pass near each other, keeping them at least 5 in. apart. Prox-
imity may cause electrical interference, malfunctions, and breakage.

• Be sure to connect the power wiring to the power wiring terminal 

block and secure it as described in 

Field line connection

.

• Transmission wiring should be secured as described in

 Field line 

connection.

• Secure the wiring with the accessory clamps so that it does not touch 

the piping.

• Make sure the wiring and the electrical components box lid do not 

stick up above the structure, and close the cover firmly.

WARNING

Never connect power supply wiring to the terminal block for remote 
controller wiring as this could damage the entire system.

Picking power line and transmission line

(Refer to figure 9)

1.

Power supply wiring and wiring for pump operation 
(High voltage)

2.

Connection wiring
(Low voltage)

3.

Set apart

Phase and 

frequency

Voltage

Minimum 

circuit amp.

Recommended 

fuses

Transmission 
line selection

RWEYQ72/84PTJU

φ

 3, 60 Hz

208-230V

22.4A

40A

AWG18-16

RWEYQ144/168PTJU

φ

 3, 60 Hz

208-230V

44.8A

40+40A

AWG18-16

RWEYQ216/252PTJU

φ

 3, 60 Hz

208-230V

67.1A

40+40+40A

AWG18-16

Summary of Contents for RWEYQ144PTJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...6 13 16 3 15 16 9 13 16 21 5 8 30 11 16 9 9 8 10 8 9 7 7 6 6 6 9 7 8 5 8 15 3 8 4 3 1 2 11 13 16 39 3 8 35 7 16 19 11 16 1 2 3 4 4 10 5 6 5 4 9 6 7 7 10 8 1 2 3 4 9 Heat recovery system Heat pump syst...

Page 3: ...figure 13 figure 12 figure 11 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT 3 A B C F1 F1 F2 F2...

Page 4: ...very system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 16 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N TO IN D UNIT F1 F2 A1P A1P DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 1 2 6 3 3 4 5...

Page 5: ...4 5 6 Heat pump system Heat recovery system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3...

Page 6: ...sult in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive leak can lead to oxygen depletion especially in base ments and an asphyxiat...

Page 7: ...on tribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrig erant piping installation Read the chapter Refrigerant Pip ing and follow...

Page 8: ...itches off automatically in order to protect the unit from freezing Hold ambient temperature at 35 95 F Heat release from the unit 0 64 kW hour Model 72 84 It is therefore recommended to always ventil...

Page 9: ...emale Thread 1 2FPS 2 female Thread General RWEYQ216PTJU RWEYQ252PTJU Nominal cooling capacity 2 MBh 216 252 Nominal cooling capacity 3 MBh 243 283 5 Nominal input cooling heating 4 kW 12 60 12 00 16...

Page 10: ...ower without fail Open type tower cannot be used 4 Strainer Install the strainer accessory without fail at the inlet of water pip ing If sands wastes rust particles etc are mixed in the water cir cula...

Page 11: ...manner 7 1 When designing the equipment 1 Install the strainer accessory at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust sand etc from ente...

Page 12: ...within the standard 2 Clean the strainer 3 Make sure that the flow rate is correct 4 Make sure that the operational conditions pressure flow rate outlet temperature etc are normal 2 Because the plate...

Page 13: ...fect but also may cause the capacitor to overheat due to high frequency waves Therefore never install a phase advancing capacitor Keep power imbalance within 2 of the supply rating 1 Large imbalance w...

Page 14: ...electromagnetic switch for the water pump to each outside unit Select without fail an auxiliary a contact able to switch min imum load of DC15V 1mA When connecting for each outside unit Connect to the...

Page 15: ...erminals for connections to the power terminal block When none is available follow the instructions below Do not connect wiring of different thicknesses to the power termi nal block Slack in the power...

Page 16: ...s always required When installing the piping follow the instructions in the installation manual that comes with the kit Restriction for the installation of the outside unit multi connection piping kit...

Page 17: ...cal piping with the provided insulation to prevent it from coming into contact with the casing Precautions for installation of units NOTE The outside unit multi connection piping kit that is sold sepa...

Page 18: ...c d e f r s t g h j k l m n o p i 23 3 lbs Total length ft of liquid piping size at 7 8 0 235 lbs ft Total length ft of liquid piping size at 3 8 Total length ft of liquid piping size at 1 4 Total len...

Page 19: ...etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be sure to...

Page 20: ...refrigerant 9 10 Stop valve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without...

Page 21: ...onfiguration on the main unit Any settings made on a sub unit will be ignored After this close the electrical compo nents box lid Always perform configuration after turning ON the power To learn the s...

Page 22: ...rding to local regulations or standards The following standards may be applicable if local regulations are not available The VRV System like other air conditioning systems uses R410A as refrigerant R4...

Page 23: ...e open ings above and below the door which are each equivalent in size to 0 15 or more of the floor area 3 Calculating the refrigerant density using the results of the calcula tions in steps 1 and 2 a...

Page 24: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P153897 12P EM09A022 0910 FS...

Reviews: