ELECTRICAL CONNECTION
FDMRN20/25A - RR20/25A
IMPORTANT:
* These values are for information only, they should be checked and selected to comply with the local and/or national
codes and regulations. They are also subjected to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
Model
Indoor (FDMRN)
20A
25A
Outdoor (RR)
20A
25A
Voltage range**
Indoor
220-240V/~/50Hz +
!
Outdoor
220-240V/~/50Hz +
!
Power supply cable size*
mm
2
Number of conductors
2.5
3
2.5
3
Interconnection cable size*
mm
2
Number of conductors
1.0
4
1.0
4
Recommended time delay fuse*
A
20
32
COMP
L1
N1
L
Outdoor unit
Terminal Block
COMP
Interconnection cable
Indoor unit
Terminal Block
L
N
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
!
Model
Indoor (FDMRN)
30A
36A
Outdoor (RR)
30A
36A
Voltage range**
Indoor
220-240V/~/50Hz+
!
Outdoor
220-240V/~/50Hz+
!
Power supply cable size*
mm
2
Number of conductors
4.0
3
6.0
3
Interconnection cable size*
mm
2
Number of conductors
2.5
4
2.5
4
Recommended time delay fuse*
A
32
40
Interconnection cable
Outdoor unit
Terminal Block
Indoor unit
Terminal Block
FDMRN30/36A - RR30/36A (1PH)
COMP
L
N
S
R
COMP
L
N
L
N
Power
Supply
N / L2
L / L1
Main
Switch
Fuse /
Circuit
Breaker
Power
Supply
Cable
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
!
Power Supply
N / L2
L / L1
Main
Switch
Fuse /
Circuit
Breaker
Power
Supply
Cable