background image

5

English

SAFETY PRECAUTIONS

!

 WARNING

!

 CAUTION

 Installation and maintenance should be performed by qualified 
persons who are familiar with local code and regulation, and 
experienced with this type of appliance.
 All field wiring must be installed in accordance with the national 
wiring regulation.
 Ensure that the rated voltage of the unit corresponds to that of 
the name plate before commencing wiring work according to 
the wiring diagram.
 The unit must be GROUNDED to prevent possible hazard due 
to insulation failure.
 All electrical wiring must not touch the refrigerant piping, or 
any moving parts of the fan motors.
 Confirm that the unit has been switched OFF before installing 
or servicing the unit.
 Disconnect from the main power supply before servicing the 
air conditioner unit.
 DO NOT pull out the power cord when the power is ON. This 
may cause serious electrical shocks which may result in fire 
hazards.
 Keep the indoor and outdoor units, power cable and transmission 
wiring, at least 1m from TVs and radios, to prevent distorted 
pictures and static. (Depending on the type and source of the 
electrical waves, static may be heard even when more than 
1m away).

Please take note of the following important points when 
installing.

 Do not install the unit where leakage of flammable gas 
may occur.

 

 If gas leaks and accumulates around the unit, it may cause 
fire ignition.

Ensure that drainage piping is connected properly.

 

 If the drainage piping is not connected properly, it may 
cause water leakage which will dampen the furniture.

Do not overcharge the unit.

 

This unit is factory pre-charged. 

 

 Overcharge will cause over-current or damage to the 
compressor.

 Ensure that the unit’s panel is closed after service or 
installation.

 

 Unsecured panels will cause the unit to operate noisily.

 Sharp edges and coil surfaces are potential locations which 
may cause injury hazards.

 

Avoid from being in contact with these places.
 Before turning off the power supply, set the remote 
controller’s ON/OFF switch to the “OFF” position to prevent 
the nuisance tripping of the unit.
 If this is not done, the unit’s 
fans will start turning automatically when power resumes, posing 
a hazard to service personnel or the user.
Do not install the units at or near doorway.
 Do not operate any heating apparatus too close to the air 
conditioner unit or use in room where mineral oil, oil vapour 
or oil steam exist, this may cause plastic part to melt or 
deform as a result of excessive heat or chemical reaction.
 When the unit is used in kitchen, keep flour away from 
going into suction of the unit.
 This unit is not suitable for factory used where cutting oil 
mist or iron powder exist or voltage fluctuates greatly.
 Do not install the units at area like hot spring or oil refinery 
plant where sulphide gas exists.
 Ensure the color of wires of the outdoor unit and the 
terminal markings are same to the indoors respectively.
 IMPORTANT: DO NOT INSTALL OR USE THE AIR 
CONDITIONER UNIT IN A LAUNDRY ROOM.
 Don’t use joined and twisted wires for incoming power 
supply.
 The equipment is not intended for use in a potentially 
explosive atmosphere.


INSTALLATION MANUAL

NOTICE

Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed 
with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil 
and of other parts must be done by a qualified installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product 
is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please 
contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national 
legislation.

This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by 
lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack 
of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person 
responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.

1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i5   5

1-IM-5CC(HA)-1115(9)-DAIKIN-EN.i5   5

6/10/21   12:38:06 PM

6/10/21   12:38:06 PM

Summary of Contents for RR20AV1K

Page 1: ...N50AV1K9 RR50AY1K9 FDMRN60AV1K RR60AY1K R410A SPLIT SERIES IM 5CC HA 1115 9 DAIKIN Part No R08019044313J FDMRN20AV1KU RR20AV1KU RR20AV1KRE FDMRN25AV1KU RR25AV1KU RR25AV1KRE FDMRN30AV1KU RR30AV1KU RR30...

Page 2: ...CVR IM 5CC HA 1115 9 DAIKIN EN2 2 CVR IM 5CC HA 1115 9 DAIKIN EN2 2 6 10 21 12 39 03 PM 6 10 21 12 39 03 PM...

Page 3: ...Indoor Unit FDMRN All dimensions are in mm Dimension Model A B C D E F G H I J K L M N O 25 30A 359 1115 1076 1030 467 378 541 256 180 306 119 170 234 234 462 36A 359 1369 1326 1287 594 378 541 256 1...

Page 4: ...30 328 520 182 44 93 149 101 113 603 126 164 17 34 3 23 73 75 362 Indoor Unit FDMRN All dimensions are in mm B C H O K N M L J I A G F E D Dimension Model A B C D E F G H I J K L M N O 60A 1372 1264 7...

Page 5: ...141 83 23 49 26 28 80 All dimensions are in mm Outdoor Unit RR All dimensions are in mm Dimension Model A B C D E F G H I J K L M N O 50A 1030 826 400 740 40 90 40 746 142 448 22 32 26 72 57 H I K K...

Page 6: ...ns are in mm Dimension Model A B C D E F G H I J K L M 60A 930 1067 880 880 902 569 1006 61 150 84 184 195 84 C H J M D K A I F I 1 IM 5CC HA 1115 9 DAIKIN EN i4 4 1 IM 5CC HA 1115 9 DAIKIN EN i4 4 6...

Page 7: ...plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen keep flour away from going into suction of the unit This unit is not suitable for fac...

Page 8: ...e distance between a door and unit In cases where the temperature above the ceiling might reach 30 C or the humidity RH80 reinforce the drain pan insulation 10mm or thicker or adding secondary Drain P...

Page 9: ...THE RELEASE PAPER AND WRAP THE ADHESIVE SIDE AROUND THE INSULATION TUBE PLACE THE PIPING INSULATION FIELD SUPPLIED NEXT TO THE INSULATION TUBE ACCESSORY COVER UP THE GAP IN BETWEEN THE PIPING INSULAT...

Page 10: ...nit Ceiling Concealed Drain Piping Work Unit mm 10 mm 0 39 Bottom of the unit Insulate securely 100 100 Drain trap or more or more Do not leave in water S l a n t UNIT DRAIN PIPE KI UNIT DRAIN PIPE KA...

Page 11: ...sufficient space for maintenance around the unit Ensure that there is no obstruction of air flow into or out of the unit Remove obstacles which block air intake or discharge The location must be well...

Page 12: ...tdoor air throw direction changing method 3 4 5 1 2 2 1 2 1 2 1 2 3 3 1 ROTATE 180 ROTATE 180 1 IM 5CC HA 1115 9 DAIKIN EN i10 10 1 IM 5CC HA 1115 9 DAIKIN EN i10 10 6 10 21 12 38 07 PM 6 10 21 12 38...

Page 13: ...g must be carefully made so as not to crush the pipe Use a pipe bender to bend a pipe where possible RR20A 25A 30A 36A 50A A B C D Minimum Distance mm 300 1000 300 500 INSTALLATION CLEARANCE The outdo...

Page 14: ...per pipes The exact length of pipe protruding from the top surface of the swaging block is determined by the flaring tool See Figure III Fix the pipe firmly on the swaging block Match the centers of b...

Page 15: ...oor unit Terminal Block L N N There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm Model Indoor FDMRN 30A 36A Outdoor RR 30A 36A Voltage range Indoor 2...

Page 16: ...Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal block Connect the wires by matching to the indication on...

Page 17: ...r unit Open the gas cylinder and low pressure charging valve When the required refrigerant quantity is pumped into the unit close the low pressure side and the gas cylinder valve Disconnect the servic...

Page 18: ...in the first few hours or the damage done during field charging may show up some time later Other typical field charging problems include undercharging overcharging moisture or air in the system etc...

Page 19: ...charging The protection module will trip and lock the compressor out for 30 minutes It is not normally necessary to wait 30 minutes for the module to reset When the compressor has cooled down the mod...

Page 20: ...his reason a protective device phase sequential is fitted to prevent incorrect wiring of the electrical phases When the three phases are not connected correctly the phase sequential operates and the u...

Page 21: ...bstances or chemical to clean the indoor unit 1 2 At least once every 2 weeks More frequently when necessary Indoor Fan Check for any abnormal noise 1 When necessary Fault Causes Action 1 The compress...

Page 22: ...AE Standard 0 98 0 95 0 96 0 98 NET WEIGHT INDOOR UNIT kg 26 44 44 50 OUTDOOR UNIT kg 47 51 75 92 REFRIGERANT R410A kg 1 75 2 0 2 6 2 8 COUNTRYOF ORIGIN INDOOR UNIT Malaysia OUTDOOR UNIT Malaysia MODE...

Page 23: ...CVR IM 5CC HA 1115 9 DAIKIN EN3 3 CVR IM 5CC HA 1115 9 DAIKIN EN3 3 6 10 21 12 39 03 PM 6 10 21 12 39 03 PM...

Page 24: ...daikinmea com Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza Kucukbakkalkoy Mah Kay sdagi Cad No 1 34750 Atasehir ISTANBUL TURKIYE Head office Umeda Center Bldg 2 4 12...

Page 25: ...Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 60334 Persiaran Bukit Rahman Putra 3 Taman P...

Page 26: ...CVR IM 5CC HA 1115 9 DAIKIN AR3 3 CVR IM 5CC HA 1115 9 DAIKIN AR3 3 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...

Page 27: ...0 27000 32000 4 62 6 01 7 91 9 38 EER 8 75 8 72 8 85 9 01 1800 2350 3050 3550 0 98 0 95 0 96 0 98 26 44 44 50 47 51 75 92 R410A 1 75 2 0 2 6 2 8 FDMRN36AV1K FDMRN50AV1K9 FDMRN60AV1K FDMRN50AV1KU FDMRN...

Page 28: ...40 1 2 3 40 1 2 1 3 1 3 4 2 3 4 5 6 0 IM 5CC HA 1115 9 DAIKIN AR i19 19 0 IM 5CC HA 1115 9 DAIKIN AR i19 19 6 10 21 1 11 54 PM 6 10 21 1 11 54 PM...

Page 29: ...23 1 2 3 1 3 3 2 a b c 1 2 3 LED PW P_S P_T 3 T 3 S 3 R 3 52 50 19 14 19 23 RR20AV1KRE RR60A RR50A RR30AV1KRE RR25AV1KRE 0 IM 5CC HA 1115 9 DAIKIN AR i18 18 0 IM 5CC HA 1115 9 DAIKIN AR i18 18 6 10 21...

Page 30: ...A 1 2 3 4 5 6 A 2 30 30 1 E1 2 E2 3 E3 4 E4 5 E5 6 E6 7 MS E7 8 E8 A 0 IM 5CC HA 1115 9 DAIKIN AR i17 17 0 IM 5CC HA 1115 9 DAIKIN AR i17 17 6 10 21 1 11 55 PM 6 10 21 1 11 55 PM...

Page 31: ...R22 300 4 1 5 2 6 3 1 Hg 760 CONTROLLED 1 7 psig 25 FDMRN 20A 25A 30A 36A 50A 60A RR 20A 25A 30A 36A 1PH 36A 3PH 50A 60A 20 20 45 45 45 23 23 0 IM 5CC HA 1115 9 DAIKIN AR i16 16 0 IM 5CC HA 1115 9 DAI...

Page 32: ...A PVE POE R22 R410A PVE POE R22 R410A R410A R22 R410A R410A 760mmHg 760mmHg 30 760mmHg 760mmHg 3 2 4 Allen HI LO 3 HI LO 3 3 0 IM 5CC HA 1115 9 DAIKIN AR i15 15 0 IM 5CC HA 1115 9 DAIKIN AR i15 15 6 1...

Page 33: ...T L3 FDMRN36 50 60A RR36 50 60A 3PH 3 FDMRN 36A 50 60A RR 36A 50 60A 220 240V 50Hz 380 415V 3N 50Hz 2 2 5 5 2 5 5 2 2 5 4 2 5 4 A 16 16 0 IM 5CC HA 1115 9 DAIKIN AR i14 14 0 IM 5CC HA 1115 9 DAIKIN A...

Page 34: ...A RR30 36A 1PH 3 FDMRN 20A 25A RR 20A 25A 220 240V 50Hz 220 240V 50Hz 2 2 5 3 2 5 3 2 1 0 4 1 0 4 A 20 32 FDMRN 30A 36A RR 30A 36A 220 240V 50Hz 220 240V 50Hz 2 4 0 3 6 0 3 2 2 5 4 2 5 4 A 32 40 0 IM...

Page 35: ...5 8 15 88 2 2 1 7 3 4 19 05 2 5 2 0 15 I II III IV ft lb Nm 6 35 1 4 18 13 3 9 52 3 8 42 31 0 12 70 1 2 55 40 6 15 88 5 8 65 48 0 19 05 3 4 78 57 6 FDMRN60A ESP ESP 0 IM 5CC HA 1115 9 DAIKIN AR i12 1...

Page 36: ...4 FDMRN 20A 25A 30A 36A 50A 60A RR 20A 25A 30A 36A 1PH 36A 3PH 50A 60A 50 50 50 50 50 50 50 30 30 30 30 30 30 30 6 35 1 4 6 35 1 4 9 52 3 8 9 52 3 8 9 52 3 8 9 52 3 8 9 52 3 8 12 70 1 2 15 88 5 8 15 8...

Page 37: ...3 4 5 1 2 2 1 2 1 2 1 2 3 3 1 180 180 0 IM 5CC HA 1115 9 DAIKIN AR i10 10 0 IM 5CC HA 1115 9 DAIKIN AR i10 10 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...

Page 38: ...2000 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 0 IM 5CC HA 1115 9 DAIKIN AR i9 9 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...

Page 39: ...KI KA KI KA 2 KA F KI 1 KI KA KI KA KI KA 1 KI KA F KI KA F 2 F 2 F 1 2 3 4 5 1 A A KI KI 20A 25A 30A 36A 50A 0 IM 5CC HA 1115 9 DAIKIN AR i8 8 0 IM 5CC HA 1115 9 DAIKIN AR i8 8 6 10 21 1 11 58 PM 6...

Page 40: ...36A 50A 60A L A L FDMRN20A 46 3 1176 8 43 214 FDMRN25A 42 4 1076 10 1 256 FDMRN30A 42 4 1076 10 1 256 FDMRN36A 52 2 1326 10 1 256 FDMRN50A 60 1 1526 10 1 256 FDMRN60A 49 8 1264 26 2 665 0 IM 5CC HA 1...

Page 41: ...A A 30 80 10 0 IM 5CC HA 1115 9 DAIKIN AR i6 6 0 IM 5CC HA 1115 9 DAIKIN AR i6 6 6 10 21 1 11 58 PM 6 10 21 1 11 58 PM...

Page 42: ...OFF 1 1 ON OFF OFF 0 IM 5CC HA 1115 9 DAIKIN AR i5 5 0 IM 5CC HA 1115 9 DAIKIN AR i5 5 6 10 21 1 11 59 PM 6 10 21 1 11 59 PM...

Page 43: ...D E F G H I J K L M 60A 930 1067 880 880 902 569 1006 61 150 84 184 195 84 B G L E C H J M D K A I F I 0 IM 5CC HA 1115 9 DAIKIN AR i4 4 0 IM 5CC HA 1115 9 DAIKIN AR i4 4 6 10 21 1 11 59 PM 6 10 21 1...

Page 44: ...852 428 410 412 827 72 196 91 488 448 142 141 83 23 49 26 28 80 RR A B C D E F G H I J K L M N O 50A 1030 826 400 740 40 90 40 746 142 448 22 32 26 72 57 H I K K J E C A L D B M N O F G 0 IM 5CC HA 1...

Page 45: ...17 34 3 23 73 75 362 FDMRN N L K L T N M A D O P B Q R S C H G F E I J A B C D E F G H I J K L M N O 60A 1372 1264 741 1148 665 292 33 60 53 784 626 338 430 180 60 B C H O K N M L J I A G F E D 0 IM...

Page 46: ...I J K L M N O 25 30A 359 1115 1076 1030 467 378 541 256 180 306 119 170 234 234 462 36A 359 1369 1326 1287 594 378 541 256 180 306 256 170 234 234 462 50A 359 1569 1526 1487 694 378 541 256 180 306 3...

Page 47: ...CVR IM 5CC HA 1115 9 DAIKIN AR2 2 CVR IM 5CC HA 1115 9 DAIKIN AR2 2 6 10 21 1 15 18 PM 6 10 21 1 15 18 PM...

Page 48: ...RN36AV1K RR36AY1K FDMRN50AV1K9 RR50AY1K9 FDMRN60AV1K RR60AY1K FDMRN20AV1KU RR20AV1KU RR20AV1KRE FDMRN25AV1KU RR25AV1KU RR25AV1KRE FDMRN30AV1KU RR30AV1KU RR30AV1KRE FDMRN36AV1KU RR36AV1KU FDMRN50AV1KU...

Reviews: