R(Y)P200+250B8W1
Split System air conditioners
4PW23688-1B

Installation manual

3

2.

Allowable pipe length

See the table below concerning lengths and heights. Refer to figures

2

~

5

Assume that the longest line in the figure corresponds with the

actual longest pipe, and the highest unit in the figure corresponds
with the actual highest unit.

The minimal piping length should be 7.5 

m. If installation is

performed with less field piping, the system will be overcharged
(abnormal HP, etc.). If the distance between indoor and outdoor unit
is less than 7.5 m, please make sure that the piping length is 

7.5 m

by additional bending of the pipes.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

When a heat pump outdoor unit is installed below the indoor unit, the
following can occur:

when the unit stops, oil will return to the discharge side of the
compressor. When starting the unit, this can cause liquid (oil)
hammer.

the oil circulation will decrease

To  solve these phenomena, provide oil traps in the gas pipe every
15 m if the level difference (H) is more than 15 m. See 

figure 6

.

Connecting the refrigerant piping

Installation of refrigerant piping is possible as front connection, side
connection and bottom connection.

Remarks:

Front connection:

Make sure to close the piping intake hole again after installation
work.

Bottom Connection:

Remove the knock out hole by drilling the 2 concave recesses
with a Ø6 mm drill (see figure). Afterwards, paint the edges to
avoid rusting.

Liquid side:

Gas side:
Cut the gas side accessory pipe and make connection using an
elbow (field supply).

Operating stop valve: refer to 

figure 7

To open:

1.

Remove the cap (1) and turn the shaft (2) counterclockwise with
hexagon socket screw keys.

2.

Turn it all the way until the shaft stops.

3.

Tighten the cap firmly.

To close:

1.

Remove the cap and turn the shaft clockwise.

2.

Tighten the shaft firmly until it reaches the sealed area (4) of the
body.

3.

Tighten the cap firmly.

Maximum allowable piping length 
(Parenthesized figure represents 
equivalent length)

Pair

L1

50 m

(70 m)

Twin/Triple

L1+L2

Double twin

L1+L2+L4

Maximum total one-way pipe 
length

Twin

L1+L2+L3

60 m

Triple

L1+L2+L3+L4

Double twin

L1+L2+L3+L4+L5+L6+L7

Maximum branch pipe length

Twin/Triple

L2

20 m

Double Twin

L2+L4

Maximum difference between
branch lengths

Twin

L2–L3

10 m

Triple

L2–L4

Double Twin

(L2+L4)–(L3+L7)

Maximum difference between 
each 1st branch

Double Twin

L2–L3

10 m

Maximum difference between 
each 2nd branch

Double Twin

L4–L5, L6–L7

10 m

Maximum height between indoor
and outdoor

All

H1

30 m

Maximum height between indoors

Twin/Triple/
Double Twin

H2

0.5 m

A

outdoor unit

B

indoor unit

C

gas pipe

D

liquid pipe

E

oil trap

NOTE

if the outdoor unit is installed above the indoor unit, oil
traps are not necessary.

Use R407C only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge
hose, etc.) that are exclusively used for R407C installa-
tions to withstand the pressure and to prevent foreign
materials  (e.g. mineral oils and moisture) from mixing into
the system.  Vacuum pump (use a 2-stage vacuum pump
with a non-return valve):

Make sure the pump oil does not flow oppositely into the
system while the pump is not working.

Use a vacuum pump which can evacuate to –100.7 kPa
(5 Torr, –755 mm Hg).

1

Flange

2

Flare nut

3

Gas side (attached pipe)

4

Liquid side

5

Brazing

6

Knock out hole

A

Knock out hole

B

Drill

C

Concave recess

Provide a liquid side pipe (field supply),
and connect it to the stop valve. Take
care not to allow it to touch the gas side
pipe.

A

cutting position

A

B

C

±

100 mm

±

167 mm

A

Summary of Contents for RP200B8W1

Page 1: ...INSTALLATION MANUAL RP200B8W1 RP250B8W1 RYP200B8W1 RYP250B8W1 Split System air conditioners...

Page 2: ...500 Y B1 300 Y 2 H 1500 A 500 h 500 B2 100 H 1500 X A 500 X 2 h 500 Y B2 100 Y 2 h H A B1 B2 mm 10 10 10 20 20 B1 A B2 A 50 50 50 50 100 100 B2 A 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5...

Page 3: ...ck konstrukce A a pozitivn zji t no B v souladu s osv d en m C jak bylo uvedeno v souboru technick konstrukce D a pozitivn zji t no E pou it modul F G Kategorie rizik H Viz tak n sleduj c strana 15 ka...

Page 4: ...n Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar Izgatavo anas numurs un...

Page 5: ...operation system Refer to catalogues for details Never operate the unit without the thermistor R3T burning of the compressor may result When closing the service panels take care that the tightening to...

Page 6: ...et The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete Maximum height of the foundation is 150 mm Lift the unit from the pallet and place it on its installation p...

Page 7: ...screw keys 2 Turn it all the way until the shaft stops 3 Tighten the cap firmly To close 1 Remove the cap and turn the shaft clockwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of...

Page 8: ...vacuum pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 100 7 kPa After kee...

Page 9: ...e length exceeds 30 m the charging amount mentioned in the nameplate and that required for additional charging are to be totaled as the net charging amount Precaution for pumping down operation The ou...

Page 10: ...power supply line See figure 10 TEST OPERATION For the test run procedure refer to the indoor unit installation manual DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil...

Page 11: ...X1M TERMINAL STRIP Y1R 4 WAY VALVE A3P PRINTED CIRCUIT BOARD DS2 SELECTOR SWITCH VARIOUS SEE PCB DS3 SELECTOR SWITCH EMERGENCY HAP LIGHT EMITTING DIODE GREEN H1P H2P LIGHT EMITTING DIODE RED R3T THERM...

Page 12: ...NOTES NOTES...

Page 13: ...8 8 2 4 5 6 2 4 5 7 9 8 6 9 9 1 2 3 3 5 5 4 10 10 3 N 50 Hz 400 V 1 2 3 11 11 1 3 2 4 5...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23688 1B...

Reviews: