R(Y)P200+250B8W1
Split System air conditioners
4PW23688-1B
Installation manual
3
2.
Allowable pipe length
See the table below concerning lengths and heights. Refer to figures
. Assume that the longest line in the figure corresponds with the
actual longest pipe, and the highest unit in the figure corresponds
with the actual highest unit.
The minimal piping length should be 7.5
m. If installation is
performed with less field piping, the system will be overcharged
(abnormal HP, etc.). If the distance between indoor and outdoor unit
is less than 7.5 m, please make sure that the piping length is
≥
7.5 m
by additional bending of the pipes.
P
RECAUTIONS
ON
REFRIGERANT
PIPING
When a heat pump outdoor unit is installed below the indoor unit, the
following can occur:
■
when the unit stops, oil will return to the discharge side of the
compressor. When starting the unit, this can cause liquid (oil)
hammer.
■
the oil circulation will decrease
To solve these phenomena, provide oil traps in the gas pipe every
15 m if the level difference (H) is more than 15 m. See
Connecting the refrigerant piping
Installation of refrigerant piping is possible as front connection, side
connection and bottom connection.
Remarks:
Front connection:
■
Make sure to close the piping intake hole again after installation
work.
Bottom Connection:
■
Remove the knock out hole by drilling the 2 concave recesses
with a Ø6 mm drill (see figure). Afterwards, paint the edges to
avoid rusting.
■
Liquid side:
■
Gas side:
Cut the gas side accessory pipe and make connection using an
elbow (field supply).
Operating stop valve: refer to
To open:
1.
Remove the cap (1) and turn the shaft (2) counterclockwise with
hexagon socket screw keys.
2.
Turn it all the way until the shaft stops.
3.
Tighten the cap firmly.
To close:
1.
Remove the cap and turn the shaft clockwise.
2.
Tighten the shaft firmly until it reaches the sealed area (4) of the
body.
3.
Tighten the cap firmly.
Maximum allowable piping length
(Parenthesized figure represents
equivalent length)
Pair
L1
50 m
(70 m)
Twin/Triple
L1+L2
Double twin
L1+L2+L4
Maximum total one-way pipe
length
Twin
L1+L2+L3
60 m
Triple
L1+L2+L3+L4
Double twin
L1+L2+L3+L4+L5+L6+L7
Maximum branch pipe length
Twin/Triple
L2
20 m
Double Twin
L2+L4
Maximum difference between
branch lengths
Twin
L2–L3
10 m
Triple
L2–L4
Double Twin
(L2+L4)–(L3+L7)
Maximum difference between
each 1st branch
Double Twin
L2–L3
10 m
Maximum difference between
each 2nd branch
Double Twin
L4–L5, L6–L7
10 m
Maximum height between indoor
and outdoor
All
H1
30 m
Maximum height between indoors
Twin/Triple/
Double Twin
H2
0.5 m
A
outdoor unit
B
indoor unit
C
gas pipe
D
liquid pipe
E
oil trap
NOTE
if the outdoor unit is installed above the indoor unit, oil
traps are not necessary.
Use R407C only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge
hose, etc.) that are exclusively used for R407C installa-
tions to withstand the pressure and to prevent foreign
materials (e.g. mineral oils and moisture) from mixing into
the system. Vacuum pump (use a 2-stage vacuum pump
with a non-return valve):
Make sure the pump oil does not flow oppositely into the
system while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa
(5 Torr, –755 mm Hg).
1
Flange
2
Flare nut
3
Gas side (attached pipe)
4
Liquid side
5
Brazing
6
Knock out hole
A
Knock out hole
B
Drill
C
Concave recess
Provide a liquid side pipe (field supply),
and connect it to the stop valve. Take
care not to allow it to touch the gas side
pipe.
A
cutting position
A
B
C
±
100 mm
±
167 mm
A
Summary of Contents for RP200B8W1
Page 1: ...INSTALLATION MANUAL RP200B8W1 RP250B8W1 RYP200B8W1 RYP250B8W1 Split System air conditioners...
Page 12: ...NOTES NOTES...
Page 13: ...8 8 2 4 5 6 2 4 5 7 9 8 6 9 9 1 2 3 3 5 5 4 10 10 3 N 50 Hz 400 V 1 2 3 11 11 1 3 2 4 5...
Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23688 1B...