R(Y)P200+250B8W1
Split System air conditioners
4PW23688-1B

Installation manual

1

 

C

ONTENTS

Page

Before installation .............................................................................. 1

Selecting installation site ................................................................... 2

Precautions on installation................................................................. 2

Installation servicing space ............................................................... 2

Refrigerant pipe size and allowable pipe length ................................ 2

Precautions on refrigerant piping....................................................... 3

Evacuating ......................................................................................... 4

Charging refrigerant........................................................................... 5

Electrical wiring work ......................................................................... 6

Test operation .................................................................................... 7

Disposal requirements....................................................................... 7

Wiring diagram .................................................................................. 7

B

EFORE

 

INSTALLATION

Precautions

The new refrigerant requires strict cautions for keeping the
system clean, dry and tight.
-

Clean and dry.

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read the chapter ‘Precautions on refrigerant piping’ carefully
and follow these procedures correctly.
Since design pressure is 3.3 MPa or 33 bar, pipes of larger wall
thickness may be required.

Since R407C is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).

The connected indoor units must be indoor units designed
exclusively for R407C. If indoor units for R22 are connected,
normal operation cannot be assured.

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.

Never operate the unit without the thermistor (R3T), burning of
the compressor may result.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

Accessories

Check if the following accessories (gas pipes) are included with your
unit.

Handling

The units are packed in a wooden crate and attached on a wooden
pallet.

At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Lift the unit preferably with a crane and 2 belts (1) of at least 8 m
long.

3.

When lifting the unit with a crane, always use protectors (2) to
prevent belt damage and pay attention to the position of the unit’s
centre of gravity. 

4.

Bring the unit as close to its final installation position in its original
package to prevent damage during transport.

RP200B8W1
RP250B8W1
RYP200B8W1
RYP250B8W1

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

2

1

Summary of Contents for RP200B8W1

Page 1: ...INSTALLATION MANUAL RP200B8W1 RP250B8W1 RYP200B8W1 RYP250B8W1 Split System air conditioners...

Page 2: ...500 Y B1 300 Y 2 H 1500 A 500 h 500 B2 100 H 1500 X A 500 X 2 h 500 Y B2 100 Y 2 h H A B1 B2 mm 10 10 10 20 20 B1 A B2 A 50 50 50 50 100 100 B2 A 2 2 H1 L1 3 3 H1 H2 L3 L1 L2 4 4 H1 H2 L4 L1 L3 L2 5...

Page 3: ...ck konstrukce A a pozitivn zji t no B v souladu s osv d en m C jak bylo uvedeno v souboru technick konstrukce D a pozitivn zji t no E pou it modul F G Kategorie rizik H Viz tak n sleduj c strana 15 ka...

Page 4: ...n Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar Izgatavo anas numurs un...

Page 5: ...operation system Refer to catalogues for details Never operate the unit without the thermistor R3T burning of the compressor may result When closing the service panels take care that the tightening to...

Page 6: ...et The unit must be installed on a solid longitudinal foundation steelbeam frame or concrete Maximum height of the foundation is 150 mm Lift the unit from the pallet and place it on its installation p...

Page 7: ...screw keys 2 Turn it all the way until the shaft stops 3 Tighten the cap firmly To close 1 Remove the cap and turn the shaft clockwise 2 Tighten the shaft firmly until it reaches the sealed area 4 of...

Page 8: ...vacuum pump which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 100 7 kPa After kee...

Page 9: ...e length exceeds 30 m the charging amount mentioned in the nameplate and that required for additional charging are to be totaled as the net charging amount Precaution for pumping down operation The ou...

Page 10: ...power supply line See figure 10 TEST OPERATION For the test run procedure refer to the indoor unit installation manual DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil...

Page 11: ...X1M TERMINAL STRIP Y1R 4 WAY VALVE A3P PRINTED CIRCUIT BOARD DS2 SELECTOR SWITCH VARIOUS SEE PCB DS3 SELECTOR SWITCH EMERGENCY HAP LIGHT EMITTING DIODE GREEN H1P H2P LIGHT EMITTING DIODE RED R3T THERM...

Page 12: ...NOTES NOTES...

Page 13: ...8 8 2 4 5 6 2 4 5 7 9 8 6 9 9 1 2 3 3 5 5 4 10 10 3 N 50 Hz 400 V 1 2 3 11 11 1 3 2 4 5...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW23688 1B...

Reviews: