17
5.2
Connecting electronically
CAUTION
A socket with safety ground must be no further than 1 meter
from the unit.
The socket must be easily accessible.
When installing the unit in a damp space, a fixed connection is
obligatory, by means of an all-pole main switch with a
minimum contact gap of 3 mm.
If the mains cable is damaged or requires replacement for any
other reason, the replacement mains cable must be ordered
from the manufacturer or its representative. In case of any
doubt, contact the manufacturer or its representative.
1.
Remove the plug from the socket, when working on the electrical circuit.
2.
If there is a cover plate (A), remove it to the front.
3.
Unscrew both screws (1) behind the display window.
4.
Slide the bottom of the front panel (2) forwards, and remove it.
5.
Pull the boiler controller forward. The boiler controller will tip downwards in the
process.
6.
Consult par. 5.2.1 to make the connections.
7.
After the required connections have been made, slide the boiler controller back into
the unit and return the cover plate, if you are using one.
8.
After making the required connections, connect the unit to the socket with safety
ground.
5.2.1
Electrical connections
Temperature regulation
Connector X4 Comments
Room thermostat on/off
6 - 7
-
Modulating thermostat with
comfort function in use
11 - 12
Outdoor temperature
sensor
8 - 9
-
Frost thermostat
6 - 7
Parallel over room thermostat
Boiler Sensor
9 - 10
Remove yellow cable bridge
Summary of Contents for ROTEX GW-20 H12
Page 1: ...ROTEX 4P374380 1D 88554801 02 2016 4P374380 1D 88554801 02 2016...
Page 29: ...30...
Page 81: ...30...
Page 133: ...30...
Page 185: ...30...
Page 237: ...30...
Page 290: ...30...
Page 342: ...30...
Page 395: ...31...
Page 421: ...57...
Page 422: ...58...
Page 423: ...59...
Page 424: ...ROTEX 008 1548799_00 88554803 05 2018 4P374380 1D 88554801 02 2016...