background image

7

English

6-2 How to lay the power supply wiring and trans-

mission wiring

Let the power supply wiring and transmission wiring with a conduit 
pass through one of the knockout holes on the front or side cover, 
and let the transmission wiring with a conduit pass through another 
knockout hole.

• For protection from uninsulated live parts, thread the power sup-

ply wiring and the transmission wiring through the included insu-
lation tube and secure it with the included binding band.

Precautions when knocking out knock holes

• Open the knock holes with a hammer or the like.
• After knocking out the holes, we recommend you remove burrs in 

the knock holes and paint the edges and areas around the edges 
using the repair paint to prevent rusting.

• When passing wiring through knock holes, make sure there are 

no burrs, and protect the wiring with protective tape.

(Refer to figure 15)

1.

Screw

2.

Unfasten the screw and open the cover.

(Refer to figure 16)

1.

Stop valve attachment plate

2.

Power supply wiring (including ground wire) or transmis-
sion wiring.

3.

Backward

4.

Knockout hole

5.

Sideways

6.

Forward

7.

Electrical Component Box

8.

Terminal block (X2M)

9.

Binding band (accessory)

10.

Connecting power supply wiring

11.

Ground wire (yellow/green)

12.

Terminal block (X1M)

13.

Transmission wiring

14.

(To X2M [To BP unit] (F1, F2))

15.

Insulation tube (large) (accessory)

16.

Insulation tube (small) (accessory)

17.

Cut off the insulation tube sticking out of the outdoor unit.

<Precautions when laying power wiring>

• Wiring of different thicknesses cannot be connected to the power 

terminal block. 
(Slack in the power wiring may cause abnormal heat.)

• Use sleeve-insulated round pressure terminals for connections to 

the power terminal block. When none are available, connect wire 
of the same diameter to both sides, as shown in the figure.

Follow the instructions below if the wiring gets very hot due to 
slack in the power wiring.

• For wiring, use the designated power wire and connect firmly, 

then secure using the included clamping material to prevent out-
side pressure being exerted on the terminal block.

• Use an appropriate screwdriver for tightening the terminal screws.

A screwdriver with a small head will strip the head and make 
proper tightening impossible.

• Over-tightening the terminal screw may break it.

See the table below the tightening torque of the terminal screws.

6-3 How to connect the power supply wiring

CAUTION

Attach a ground-fault circuit interrupter.

• A ground-fault circuit interrupter is required in order to prevent 

electric shock and fires.

CAUTION

• The wiring should be selected in compliance with local specifi-

cations. See the table above.

• Always turn off the power before doing wiring work.
• Grounding should be done in compliance with local laws and 

regulations.

• Attach a ground-fault circuit interrupter.

(This unit has an inverter, so an interrupter capable of handling 
high frequencies is needed to prevent malfunction of the inter-
rupter itself.)

• As shown in figure 16, when connecting the power supply wiring 

to the power supply terminal block, be sure to clamp securely.

• Once wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the control box.

Insulation tube
(accessory)

Binding band
(accessory)

Power supply 
wiring

3 inch 

(76mm)

5/8 inch 
(15 mm)

2 inch 
(50 mm) 
or more

5/8 inch 
(15 mm)

Insulation tube
(accessory)

Binding band
(accessory)

Transmission
wiring

3 inch (76mm)

<Power supply wiring>

<Transmission wiring>

Ground wire

If small animals might enter the 
unit, block the knock holes with an 
appropriate material (field supply).

Burr

Tightening torque

M5

Power terminal

1.76-2.15 ft·lbf

(2.39-2.91 N·m)

M4

Shield ground

0.87-1.06 ft·lbf

(1.18-1.44 N·m)

M3

Transmission wiring terminal block

0.58-0.72 ft·lbf
(0.8-0.97 N·m)

Model name

Frequency

Voltage

Rated 

current 

for fuses

Maximum 

outdoor unit 

operating 

current

RMXS48LVJU

60Hz

208/230V

30A

27A

Insulating sleeve 

Round crimp-style 
terminal

Electric Wire

Connect wires 
of the same gauge 
to both side.

Do not connect 
wires of different 
gauges.

Do not connect 
wires of the same 
gauge to one side.

Good

Wrong

Wrong

01_EN_3P329623-1.fm  Page 7  Friday, November 9, 2012  6:50 PM

Summary of Contents for RMXS48LVJU

Page 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Page 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Page 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Page 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Page 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Page 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Page 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Page 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Page 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Page 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Page 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Page 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Page 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Page 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Page 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Page 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Page 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Page 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Page 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...

Reviews: