background image

English

8

6-4 Inter-unit wiring connection procedure

• Between indoor units in the same system, pass the wiring 

between the units as shown in figure 17. (There is no polarity.)

(Refer to figure 17)

1.

Terminal block (X2M)

2.

Use balance type shield wire (with no polarity).

3.

BP unit

4.

Not used for this model. 

Never connect wires, or the 

entire system will be damaged.

Precautions regarding the length of wiring between units

Exceeding the following limits may cause transmission malfunctions, 
so observe them.
Max. wiring length

Max. 656 ft (200 m)

Total wiring length

Max. 984 ft (300 m)

Precautions regarding wiring between units

Do not connect 208/230V power wiring to terminals for the 
inter-unit wiring. Doing so would destroy the entire system.

• Wiring to the BP unit should be wired to F1 and F2 (To BP unit) on 

the outdoor unit’s terminal block (X2M).

Note

The above wiring should be wired using AWG 18-16 (0.75 – 1.25
mm

) shielded (balance type) wiring. 

(See figure 16 for how to ground the shielded parts.)

All inter-unit wiring is to be procured on site.

CAUTION

(Refer to figure 18)

1.

Branch

2.

Caution on branches in the wiring among BP units

3.

The following branches can not be performed

7.

PRECAUTIONS ON REFRIGERANT 
PIPING

CAUTION

To the pipe-layer

• Do not operate the unit with the transport clasp attached. This 

can cause abnormal shaking or noise. See “

5. PRECAUTIONS 

ON INSTALLATION

” and “How to remove the transport clasp”.

7-1 Installation tools

Use the right parts to ensure tolerance and to prevent foreign matter 
for entering.

Gauge manifold, charge hose, etc.

• Make sure to use installation tools that are exclusively used for 

R410A installations to withstand the pressure and to prevent for-
eign materials (e.g. mineral oils such as SUNISO and moisture) 
from mixing into the system.
(The screw specifications differ for R410A.)

Vacuum pump

• Use extreme caution to prevent pump oil from flowing back-

wards through the system when the pump is stopped.

• Use a vacuum pump which can evacuate to –14.6 PSI (–100.7 

kPa (5Torr, –755mmHg)).

7-2 Selecting piping material

• Use pipes that have no contaminants adhered to their inner surfaces 

(such as sulfur, iron oxide, dust, cutting chips, oil and moisture). (It is 
desirable that adhered oil inside the piping is 0.00006 lb. (30 mg) or 
less per 32.8 ft (10 m).)

• The wall thickness of the refrigerant piping should comply with local 

laws and regulations.  The design pressure for R410A is 478 PSI 
(3.3 MPa).

• Use the following material for the refrigerant piping. 

Material: Jointless phosphor-deoxidized copper pipe.

• Thickness and size: choose based on the piping size selection 

method on the “

7-8 Air tight test and vacuum drying

”.

• Make sure to use the separately sold refrigerant branch kit when 

branching the piping.

• Piping work should be done within the maximum length, height 

difference, and length after branches set out in “

7-8 Air tight test 

and vacuum drying

”.

• Install the refrigerant branch kit while observing the following con-

dition and referring to the installation manual offered as an acces-
sory of the kit.

(Refer to figure 19)

1.

Install the REFNET joint so it splits horizontally or vertically.

2.

Horizontal surface

3.

A-arrow view

4.

±30° or less

5.

Level

6.

Vertical is also OK

7-3 Protection against contamination when 

installing pipes

• Wrap the piping to prevent moisture, dirt, dust, etc. from entering 

the piping.

• Exercise caution when passing copper piping through the 

through-holes and when passing them out to the outside.

7-4 Pipe connection

• See “Stop valve operation procedure” in “

7-8 Air tight test and 

vacuum drying

” regarding handling of the stop valve.

• Only use the flare nuts included with the unit. Using different flare 

nuts may cause the refrigerant to leak.

Be sure to perform a nitrogen blow when brazing.

(Brazing without performing nitrogen replacement or releasing 
nitrogen into the piping will create large quantities of oxidized film 
on the inside of the pipes, adversely affecting valves and compres-
sors in the refrigerating system and preventing normal operation.)

Note

The nitrogen used when brazing while flowing the nitrogen should be 
set to 2.9 PSI (0.02 MPa) (2.8 PSI / 0.019 MPa: just enough to feel a 
breeze on your cheek) with the decompression valve.

• Do not mix any refrigerant other than that specified into the refrig-

erant system.

• Do not mix air into the refrigerant system.

CAUTION

Do not use a flux when brazing the refrigerant pipe joints. 
Use phosphor copper brazing (BCuP-2/B-Cu93P-710/795) which 
does not require flux.
(Using a chlorine flux may cause the pipes to corrode, and if it 
contains fluoride it may cause the refrigerant lubricant to deterio-
rate, adversely affecting the refrigerant piping system.)

(Refer to figure 20)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Regulator

4.

Nitrogen

5.

Manual valve

6.

Taping

7-5 Connecting the refrigerant piping

• The local inter-unit piping is connectable in four directions.

(Refer to figure 21)

1.

Front panel

2.

Pipe outlet panel

3.

Backward

4.

Sideways

5.

Downward

6.

Pipe outlet panel screw

7.

Forward

8.

Screw for front panel

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

01_EN_3P329623-1.fm  Page 8  Friday, November 9, 2012  6:50 PM

Summary of Contents for RMXS48LVJU

Page 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Page 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Page 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Page 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Page 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Page 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Page 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Page 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Page 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Page 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Page 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Page 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Page 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Page 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Page 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Page 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Page 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Page 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Page 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...

Reviews: