• When using a central controller, see the installation manual or 

service manual which came with the central controller.

CAUTION

To the pipe-layer, To the electrician

After the test run, when handing the unit over to the customer, 
make sure the front panel on the unit and all screws are attached.

11. CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The follow-
ing standards may be applicable if local regulations are not 
available.

This system uses R410A as refrigerant. R410A itself is an entirely 
safe non-toxic, non-combustible refrigerant. Nevertheless care must 
be taken to ensure that air conditioning facilities are installed in a 
room which is sufficiently large. This assures that the maximum con-
centration level of refrigerant gas is not exceeded, in the unlikely 
event of major leak in the system and this in accordance to the local 
applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maxi-
mum concentration of refrigerant is directly related to the humanly 
occupied space in to which it could leak.

The unit of measurement of the concentration is lb./ft

3

 (kg/m

3

) (the 

weight in lb. (kg) of the refrigerant gas in 1 ft

3

 (0.028 m

3

) volume of the 

occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.

Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 
to 4 below and take whatever action is necessary to comply.

1.

Calculate the amount of refrigerant (lb. / kg) charged to each sys-
tem separately.

Note

Where a single refrigerant facility is divided into 2 entirely inde-
pendent refrigerant systems then use the amount of refrigerant
with which each separate system is charged.

2.

Calculate the smallest room volume (ft

3

/m

3

)

Incase like the following, calculate the volume of (A), (B) as a sin-
gle room or as the smallest room.

A.

Where there are no smaller room divisions

B.

Where there is a room division but there is an opening

between the rooms sufficiently large to permit a free flow of
air back and forth.

(Where there is an opening without a door or where there are
openings above and below the door which are each equivalent in
size to 0.15% or more of the floor area.)

3.

Calculating the refrigerant density using the results of the calcu-
lations in steps 1 and 2 above.

If the result of the above calculation exceeds the maximum con-
centration level then make similar calculations for the second then
third smallest room and so until the result falls short of the maxi-
mum concentration.

4.

Dealing with the situations where the result exceeds the maxi-
mum concentration level.
Where the installation of a facility results in a concentration in
excess of the maximum concentration level then it will be neces-
sary to revise the system. 
Please consult your Daikin supplier.

U2

Insufficient supply voltage

Check to see if the supply voltage is 
supplied properly.

U3

If a check operation has not 
been performed.

Perform a check operation.

U4

No power is supplied to an 
outdoor unit.

Turn the power on for the outdoor unit.

UA

If no dedicated indoor unit is 
being used.

Check the indoor unit. If it is not a ded-
icated unit, replace the indoor unit.

UF

The stop valve of an out-
door unit is left closed.

Open the gas-side stop valve and the 
liquid-side stop valve.

If the right indoor unit piping 
and wiring are not properly 
connected to the outdoor 
unit.

Make sure that the right indoor unit 
piping and wiring are properly con-
nected to the outdoor unit.

UH

If the inter-unit wiring has 
not be connected or it has 
shorted.

Make sure the inter-unit wiring is cor-
rectly attached to terminals (X2M) F1/
F2 (To BP unit) on the outdoor unit cir-
cuit board.

Direction of the refrigerant flow

BP unit

Room where 
refrigerant leak 
has occurred 
(outflow of all the 
refrigerant from 
the system)

amount of refriger-
ant in a single unit 
system (amount of 
refrigerant with 
which the system 
is charged before 
leaving the factory)

+

additional charging 
amount (amount of 
refrigerant added 
locally in accordance 
with the length or 
diameter of the refrig-
erant piping)

=

total amount 
of refriger-
ant (lb. / kg) 
in the system

total volume of refrigerant in the 
refrigerant system

maximum concen-
tration level (lb./ft

3

 / 

kg/m

3

)

size (ft

3

 / m

3

 ) of smallest room in 

which there is an indoor unit 
installed

BP unit

Opening 
between rooms

Partition 

BP unit

01_EN_3P329623-1.fm  Page 14  Friday, November 9, 2012  6:50 PM

Summary of Contents for RMXS48LVJU

Page 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Page 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Page 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Page 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Page 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Page 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Page 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Page 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Page 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Page 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Page 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Page 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Page 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Page 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Page 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Page 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Page 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Page 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Page 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...