background image

English

12

8.

ADDITIONAL REFRIGERANT CHARGE

WARNING

• When leaving the unit with the power on, be sure to 

switch with another person doing the installation or 
close the front panel.

8-1 Before adding refrigerant

• Make sure the following work and inspection is complete, in 

accordance with the installation manual.
• Piping
• Wiring
• Airtightness test, Vacuum drying

8-2 Checking the refrigerant tank

• Check whether the tank has a siphon pipe before charging and 

place the tank so that the refrigerant is charged in liquid form. 
(See the figure below.)

8-3 Adding refrigerant

1.

Calculate the amount of refrigerant to add as described in “Calcu-
lating the amount of refrigerant to add” in “

7-7 Example of con-

nection (page 10)

”.

2.

After the vacuum drying is finished, open valve A and charge the 
calculated amount of refrigerant through the service port for the 
liquid-side stop valve.

3.

Close valve A after charging is complete.

Note:If all the refrigerant to be added cannot be charged using the 

above procedure, right-hand the procedure below and re-

charge the refrigerant.

If all the refrigerant could not be added

Add refrigerant using the following procedure. See the 

“Cautions on 

Service” plate

 on the back of the front panel for details on the set-

tings for adding refrigerant.
[Procedure]

1.

Close the front panel and turn on the power to all outdoor units 
and indoor units in the refrigeration system.

2.

Open the gas and liquid-side stop valve all the way and add the 
refrigerant. (Open valve A immediately after starting the compres-
sor.)

3.

Once the appropriate amount of refrigerant is in, press the confir-
mation button (BS3) on the outdoor unit PC board (A2P), and stop 
operation after adding the refrigerant.

4.

Close valve A after charging is complete.

9.

POST-WORK CHECKS

Perform the following checks after work is complete.
(1) Drain pipe connection, removal of transport clasp 

 

See “

5. PRECAUTIONS ON INSTALLATION (page 6)

”. 

(2) Incorrect power supply wiring, loose screws 

→ 

See “

6-3 How to connect the power supply wiring (page 7)

”.

(3) Incorrect inter-unit wiring, loose screws 

→ 

See “

6-4 Inter-unit wiring connection procedure (page 8)

”.

(4) Incorrect refrigerant piping connections 

→ 

See “

7. PRECAUTIONS ON REFRIGERANT PIPING (page 8)

”.

(5) Piping sizes, use of insulation 

→ 

See : “

7-2 Selecting piping material (page 8)

”.

7-6 Heat insulation of piping (page 9)

”.

(6) Stop valve check 

→ 

Make sure both the liquid-side and gas-side stop valves are 
open.

(7) Record of Amount of Refrigerant Added 

→ 

Record it on “Recording the additionally charged refrigerant 
quantity” on the 

“Cautions on Service” plate

.

(8) Measuring the insulation of the main power circuit 

→ 

• Use a 500V mega-tester. 
• Do not use the mega-tester for weak currents other than 208/

230V. (Inter-unit wiring)

CAUTION

To the pipe-layer

After completing installation, be sure to open the valve.
(Operating the unit with the valve shut will break the compressor.)

Filling after calculating the amount of refrigerant to add

Status of the stop valve and other valves when adding refrigerant

• See “Stop valve operation procedure” in “

7-8 Air tight test and 

vacuum drying (page 11)

” for details on how to use the stop valve.

(Refer to figure 28)

1. R410A Tank (Siphon system) 5. Stop valve service port   
2. Measuring instrument

6. Gas line stop valve   

3. Valve A

7.Outdoor unit   

4. BP unit

8.Liquid line stop valve

State of valve A and the stop 
valve

Valve A

Liquid line 
stop valve

Gas line 

stop valve

Before starting to charge the 
refrigerant

Close

Close

Close

During charging of the refrig-
erant

Open

Close

Close

Location of “Cautions on Service” plate.

The back of front panel

Front panel

Tank with siphon pipe

Other tanks

There is a siphon 
pipe inside, so the 
cylinder need not be 
upside-down to fill 
with liquid.
(Stand the cylinder 
upright when filling.)

Stand the tank 
upside down and 
charge.

Status of the stop valve and other valves when adding refrigerant 
operation

• See “Stop valve operation procedure” in “

7-8 Air tight test and 

vacuum drying (page 11)

” for details on how to use the stop 

valve.

• Connect the service port (for charging refrigerant) inside the 

unit.  When the unit is shipped from the factory, refrigerant is 
already charged, so be careful when connecting the charge 
hose.

• After adding the refrigerant, do not forget to close the lid of the 

service port (for adding refrigerant). The tightening torque of the 
lid is 8.5-10.3 ft·lbf (11.5-14.0 N·m)

(Refer to figure 29)

1. Gas line stop valve

2. Liquid line stop valve

3. Stop valve service port

4. BP unit

5. Measuring instrument

6. R410A Tank (Siphon

system)

7. Valve A

8. Service port

9.(For adding refrigerant)

10.Outdoor unit

State of valve A and the stop 
valve

Valve A

Liquid line 
stop valve

Gas line 

stop valve

Before starting to charge the 
refrigerant

Close

Open

Open

During charging of the refrig-
erant

Open

Open

Open

01_EN_3P329623-1.fm  Page 12  Friday, November 9, 2012  6:50 PM

Summary of Contents for RMXS48LVJU

Page 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Page 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Page 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Page 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Page 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Page 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Page 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Page 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Page 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Page 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Page 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Page 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Page 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Page 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Page 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Page 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Page 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Page 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Page 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...

Reviews: