background image

9

English

When connecting the pipings downward, remove the knock-
out by making 4 holes in the middle on the each side of the 
knockout with a drill.

(Refer to figure 22)

1.

Dril

2.

Center area around knockout hole

3.

Knockout hole

4.

Slit

• After knocking out the knock-out, it is recommended to apply 

repair paint to the edge and the surrounding end surfaces to pre-
vent rusting.

(Refer to figure 23)

1.

Bottom frame

2.

Inter-unit piping

Note

Cutting out the 2 slits makes it possible to install as shown in fig-
ure 23. (Use a metal saw to cut out the slits.)

<Precautions when connecting pipes>

• Please refer to the Table 1 for the dimensions for processing 

flares.

• When connecting the flare nut, coat 

the inner surface of the flare 

with refrigeration oil and initially tighten by hand 3 or 4 turns 
before tightening firmly.

• Please refer to the Table 1 for the tightening torque. (Too much 

tightening will end up in splitting of the flare.)

Table 1

 

• If a torque wrench is not available, there is a place where the tight-

ening torque will suddenly increase if a normal wrench is used to 
tighten the flare nut.
From that position, further tighten the flare nut the angle shown 
below.

• After all the piping has been connected, use nitrogen to perform a 

gas leak check.

(Refer to figure 24-[1])

1.

Front connection

2.

Gas side accessory pipe (1)

3.

Gas side accessory pipe (3)

4.

Gas side piping (field supply)

5.

Cut at an appropriate length.

6.

Gas side accessory pipe (2)

(Refer to figure 24-[2])

1.

Rear-side connection

2.

Gas side accessory pipe (1)

3.

Gas side accessory pipe (2)

4.

Gas side accessory pipe (3)

5.

Gas side piping (field supply)

(Refer to figure 24-[3])

1.

Side connection

2.

Gas side accessory pipe (2)

3.

Cut at an appropriate length.

4.

Gas side piping (field supply)

5.

Gas side accessory pipe (3)

6.

Gas side accessory pipe (1)

(Refer to figure 24-[4])

1.

Bottom connection

2.

Cut at an appropriate length.

3.

Gas side piping (field supply)

4.

Gas side accessory pipe (3)

5.

Gas side accessory pipe (1)

Precautions for connecting pipes

• Be careful not to let the inter-unit 

piping come into contact with the 

compressor terminal cover.
Adjust the height of the insulation material on liquid pipe when it 
has the possibility of getting in contact with the terminal.  Also 
make sure that the inter-unit piping does not touch the mounting 
bolt of the compressor. 

(Refer to figure 26)

1.

Terminal cover

2.

Compressor

3.

Corking, etc.

4.

Insulation material

5.

Bolts

6.

Inter-unit piping

• If installing the outdoor unit higher than the indoor unit, caulk the 

space around insulation and tubes because condensation on the 
check valve can seep through to the indoor unit side.

[Preventing foreign objects from entering]

• Plug the pipe through-holes with putty or insulating material (pro 

cured locally) to stop up all gaps, as shown in figure 25.
(Insects or small animals entering the outdoor unit may cause a 
short in the control box.)

(Refer to figure 25)

1.

Putty or insulating material

2.

(field supply)

7-6 Heat insulation of piping

• If you think the humidity inside the ceiling might exceed 86°F 

(30°C) and RH80%, reinforce the insulation on the cooling piping. 
(At least 0.78 inch (20 mm) thick) (Condensation may form on the 
surface of the insulation.)

• Be sure to insulate the inter-unit piping (liquid and gas-side) and 

the refrigerant branch kit. (Not insulating them may cause leak-
ing.)

(The highest temperature that the gas-side piping can reach is 
around 248°F (120°C), so be sure to use insulating material which is 
very resistant.)

CAUTION

For local insulation, be sure to insulate all the way to the pipe con-
nections inside the machine.
Exposed piping may cause leaking or burns on contact.

Pipe size

Tightening 

torque

A dimen-

sions for 

processing 

flares

Flare shape

φ

 3/8 inch

(

φ 

9.5mm)

24.1-29.4 ft·lbf

(32.7-39.9N·m)

0.504-0.520 inch

(12.8-13.2mm)

φ 

5/8 inch

(

φ 

15.9mm) 

45.6-55.6 ft·lbf

(61.8-75.4N·m)

0.760-0.776 inch

(19.3-19.7mm)

φ 

3/4 inch

(

φ 

19.1mm)

71.7-87.5 ft·lbf

(97.2-118.6N·m)

0.929-0.944 inch

(23.6-24.0mm)

Pipe size

Further tightening angle

Recommended arm length 
of tool

φ

 3/8 inch 

(

φ 

9.5mm)

60°- 90 °

Approx. 7-7/8 inch 
(200 mm)

φ

 5/8 inch

(

φ

15.9mm)

30°- 60°

Approx. 11-13/16 inch
(300 mm)

φ

 3/4 inch

(

φ

 19.1mm)

20° - 35°

Approx. 17-11/16 inch
(450 mm)

A

45

˚

± 2

˚

90

˚

± 2

˚

R0.016-0.031 inch

(R0.4-0.8mm)

Refrigeration oil

01_EN_3P329623-1.fm  Page 9  Friday, November 9, 2012  6:50 PM

Summary of Contents for RMXS48LVJU

Page 1: ...INSTALLATION MANUAL Model RMXS48LVJU English Espa ol Fran ais Installation manual Manuel d installation Manual de instalaci n 00_CV_3P329623 1 fm Page 1 Friday November 9 2012 6 43 PM...

Page 2: ...mpleting installation test the unit to check for installation errors Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual Never attempt DAN...

Page 3: ...igerant circuit free from all substances other than the specified refrigerant R410A such as air Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure ri...

Page 4: ...l only A Outdoor temperature FDB CDB B Indoor temperature FWB CWB C Outdoor temperature FWB CWB D Indoor temperature FDB CDB Range for continuous operation Range for pull down operation Range for warm...

Page 5: ...ence or windbreak screen 2 Air inlet grille 3 Ensuring there is enough space for installing the unit 4 Set the outlet side at a right angle to the direction of the wind 5 Strong wind 6 Blown air 3 In...

Page 6: ...ght limit for obstructions on the intake side When nothing is obstructing the top 1 Installation of single unit Refer to figure 7 5 2 In case of installing multiple units 2 units or more in lateral co...

Page 7: ...any electrical wiring Only proceed with wiring work after blocking off all power Make sure the ground resistance is no greater than 4 Attach a ground fault circuit interrupter Ground the indoor and o...

Page 8: ...luded clamping material to prevent out side pressure being exerted on the terminal block Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip th...

Page 9: ...pipe Thickness and size choose based on the piping size selection method on the 7 8 Air tight test and vacuum drying Make sure to use the separately sold refrigerant branch kit when branching the pipi...

Page 10: ...g come into contact with the compressor terminal cover Adjust the height of the insulation material on liquid pipe when it has the possibility of getting in contact with the terminal Also make sure th...

Page 11: ...the first junction 16 4 ft 5 m or longer Refrigerant branch kit selection refrigerant branch kits can only be used with R410A How to calculate the additional refrigerant to be charged Additional refri...

Page 12: ...ocurement 11 Outdoor unit 12 BP unit Note The stop valve must always be turned to closed Otherwise the refrigerant in the outdoor unit will pour out The names of parts needed to operate the stop valve...

Page 13: ...page 9 6 Stop valve check Make sure both the liquid side and gas side stop valves are open 7 Record of Amount of Refrigerant Added Record it on Recording the additionally charged refrigerant quantity...

Page 14: ...On Check Operation Indoor unit displays malfunction sign Check on a remote controller connected to the indoor unit For details see the operation manual which comes with indoor unit 1 Close the outdoor...

Page 15: ...there is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth Where there is an opening without a door or where there are openings a...

Page 16: ...r more 12 300 or more figure 5 1 2 3 4 20 500 or more 20 500 or more 20 500 or more 20 500 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more 40 1 000 or more unit inch mm figure 6 1 2 L L L A...

Page 17: ...0 or more 120 3 000 or more H A L unit inch mm 1 15 16 20 unit inch mm figure 10 1 2 7 3 4 6 5 1 2 3 5 1 2 140 5 1 2 140 16 5 8 421 1 3 4 45 24 1 8 612 24 3 8 140 13 3 4 350 8 5 8 219 4 5 8 117 1 3 16...

Page 18: ...7 8 figure 28 1 2 3 4 4 5 6 figure 29 figure 20 figure 30 1 1 2 3 F1F2 F1F2 F1F2 F1F2 F1F2 F1F2 figure 17 figure 18 1 2 3 4 5 6 A figure 19 1 2 3 4 4 1 2 figure 21 figure 22 figure 23 1 2 1 2 3 4 5 6...

Page 19: ...HT Two dimensional bar code is a code for manufacturing 3P329623 1 M12B276 1211 00_CV_3P329623 1 fm Page 5 Friday November 9 2012 6 43 PM...

Reviews: