10
3P362438-9N English
7 .3 . Selection of piping size
Determine the proper size referring to following tables and reference
figure (only for indication).
A
D
a
E
b
1
2
E
5
6
D
E
b
E
7
8
E
E
4
3
B
B
B
C
x
y
1
Multi Branch Selector unit
2
Single Branch Selector unit
3-8 VRV indoor units
a, b Refrigerant branch kits
x, y
Outdoor unit multi connection piping kits
7 .3 .1 .
Piping between outdoor units and (first) refrigerant
branch kit: A, B, C
Choose from the following table in accordance with the outdoor unit
total capacity type, connected downstream.
Outdoor unit
capacity type
Piping outer diameter size
Suction gas
pipe
High/low
pressure gas
pipe
liquid pipe
REYQ 72 T type
3/4 in.
(19.1 mm)
5/8 in.
(15.9 mm)
3/8 in.
(9.5 mm)
REYQ 96 T type
7/8 in.
(22.2 mm)
3/4 in.
(19.1 mm)
REYQ 120 T type
1-1/8 in.
(28.6 mm)
1/2 in.
(12.7 mm)
REYQ 144 T type
7/8 in.
(22.2 mm)
REYQ 168 T type
5/8 in.
(15.9 mm)
REYQ 192 T type
1-1/8 in.
(28.6 mm)
REYQ 216 T type
REYQ 240 T type
1-3/8 in.
(34.9 mm)
REYQ 264-336
T type
3/4 in.
(19.1 mm)
REYQ 360,384
T type
1-5/8 in.
(41.3 mm)
1-3/8 in.
(34.9 mm)
7 .3 .2 . Piping between refrigerant branch kits or refrigerant
branch kits and Branch Selector units: D
Choose from the following table in accordance with the indoor unit
total capacity, connected downstream. Do not let the connection pip-
ing exceed the refrigerant piping size chosen by the general system
model name.
Indoor unit
capacity index
Piping outer diameter size
Suction gas
pipe
High/low
pressure gas
pipe
liquid pipe
< 54
5/8 in.
(15.9 mm)
1/2 in.
(12.7 mm)
3/8 in.
(9.5 mm)
54 ≤
×
< 72
3/4 in.
(19.1 mm)
5/8 in.
(15.9 mm)
72 ≤
×
< 111
7/8 in.
(22.2 mm)
3/4 in.
(19.1 mm)
111 ≤
×
< 162
1-1/8 in.
(28.6 mm)
1/2 in.
(12.7 mm)
162 ≤
×
< 230
1-1/8 in.
(28.6 mm)
5/8 in.
(15.9 mm)
230 ≤
×
< 300
1-3/8 in.
(34.9 mm)
3/4 in.
(19.1 mm)
> 300
1-5/8 in.
(41.3 mm)
Example:
Downstream capacity for D = capacity index of (unit 3 + unit 4 + unit 5
+ unit 6)
7 .3 .3 . Piping between refrigerant branch kits or Branch Selec-
tor units and indoor units: E
Pipe size for direct connection to indoor units must be the same as the
connection size of the VRV indoor units.
Indoor unit
capacity index
Piping outer diameter size
Gas pipe
liquid pipe
07, 09, 12, 18
1/2 in. (12.7 mm)
1/4 in. (6.4 mm)
24, 30, 36, 42,
48, 54
5/8 in. (15.9 mm)
3/8 in. (9.5 mm)
72
3/4 in. (19.1 mm)
96
7/8 in. (22.2 mm)