29

3P362438-9N

English

 NOTE

• 

If the power of some units is turned off, the charging procedure can-

not be finished properly.

• 

In case of a multiple outdoor system, turn on the power of all out-
door units.

• 

Make sure to turn ON the power 6 hours before starting the opera-
tion. This is necessary to warm the crankcase by the electric heater.

• 

If operation is performed within 12 minutes after the indoor and 
outdoor units are turned on, the compressor will not operate before 
the communication is established in a correct way between outdoor 
unit(s) and indoor units.

• 

Before starting charging procedures, check if the segment display 
indication of the main printed circuit board (A1P) is as normal (see 
functions of the push button switches which are located on the main 
printed circuit board (A1P) on page 24). If a malfunction code is 

present, see 15.5. Malfunction code list on page  38.

• 

Make sure all connected indoor units are recognized (see  

15.2. Monitoring function and field settings on page 31).

• 

Close the front panel before any refrigerant charge operation is 

executed. Without the front panel attached the unit cannot judge 

correctly whether it is operating properly or not.

14 .3 .2 .  Charging method

As explained during vacuum drying method, once vacuum drying is 
finished, additional refrigerant charging can start. 

A flow chart is available which gives an overview of the possibilities 
and actions to be taken (see 14.3.1. Flow chart on page 28).

To speed up the process of pre-charging refrigerant for large systems, 

it is recommended to first charge a portion of the refrigerant before 

performing refrigerant charging operation of outdoor unit. This step is 
included in below procedure. This step can be skipped, but charging 
will take longer in such a case.

Follow the steps as described below.

Calculate the additional amount of refrigerant to be added using 
the formula mentioned in 14.2. Calculating the additional refriger-

ant charge on page 26.

The first 22 lbs. (10 kg) of additional refrigerant can be charged 

without outdoor unit operation.
If the additional refrigerant amount is smaller than 22 lbs. (10 kg), 

perform the pre-charging procedure as explained in step 3 and 4a 

below.
If the additional refrigerant charge is larger than 22 lbs. (10 kg), 
perform step 3 till the end of the procedure.

Pre-charging can be done without compressor running by con-
necting the refrigerant tank only to the liquid stop valve service port 
(open valve C). Make sure that all outdoor unit stop valves, as well 
as valves A and C are closed.

1

2

3

4

5

6

B

9

8

11

11

12

10

14

13

15

16

A

C

7

1  Pressure reducing valve
2  Nitrogen

3  Measuring instrument
4  Refrigerant R410A tank (siphon system)
5  Vacuum pump
6  Charge hose
7  High/low pressure gas pipe stop valve
8  Suction gas pipe stop valve
9  Liquid pipe stop valve
10 Refrigerant charge port
11 Outdoor unit
12  To Branch Selector unit (indoor unit)
13  Stop valve
14  Field piping
15 

Gas flow

16 Stop valve service port
A  Valve A
B  Valve B
C  Valve C

a)   If the calculated additional refrigerant amount is reached by 

above pre-charging procedure, close valve B.

b)   If the total amount of refrigerant could not be charged by pre-

charging, then close valve B and go to step 5. 

 INFORMATION

If the total additional refrigerant amount was reached in step 4 (by 
pre-charging only), record the amount of refrigerant that was added 
on the additional refrigerant charge label provided with the unit and 
attach it on the back side of the front panel. Perform the test procedure 

as described in 15.4. Test operation on page 37.

After pre-charging, perform the refrigerant charge operation as 
shown below and charge the remaining refrigerant of the additional 
charging amount through valve A.
Open all outdoor units stop valves. Valves A, B and C must remain 
closed!

 NOTE

• 

The refrigerant charging port is connected to the piping inside the 
unit. The unit’s internal piping is already factory charged with refrig-
erant, so be careful when connecting the charge hose.

• 

After adding the refrigerant, do not forget to close the cover of the 
refrigerant charging port. The tightening torque for the cover is 8.48 
to 10.3 ft

lbf (11.5 to 13.9 N

m).

• 

In order to ensure uniform refrigerant distribution, it may take the 
compressor ±10 minutes to start up after the unit has started opera-
tion. This is not a malfunction.

6

    The remaining additional refrigerant charge can be charged by 

operating the outdoor unit by means of the refrigerant charge 
operation mode:

• 

Turn on the power of the indoor units and outdoor unit.

• 

Take all the precautions mentioned in 

start-up and configura

-

tion

 into account.

•  Activate outdoor unit setting [2-20]=1 to start refrigerant 

charge mode. Refer to page 32 for details.

Result: 

The unit will start operation. Valve A can be opened.

Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount 
is added, close valve A and push BS3 to stop the refrigerant 
charging procedure.

01_EN_3P362438-9N.indb   29

12/11/2019   2:36:00 PM

Summary of Contents for REYQ72TAYC Series

Page 1: ...event of conflicting information the online installation instruction is to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instruc...

Page 2: ...nnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installi...

Page 3: ...only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil...

Page 4: ...piping 14 8 1 Caution for brazing 14 8 2 Connecting the refrigerant piping 14 8 3 Guidelines for handling stop valve 17 9 Field wiring 18 9 1 Power circuit safety device and cable requirements 19 9 2...

Page 5: ...Q 192 384 consists of multiple REYQ 72 168 modules as indi cated 72 96 120 144 168 REYQ72TAYC 1 REYQ96TAYC 1 REYQ120TAYC 1 REYQ144TAYC 1 REYQ168TAYC 1 REYQ192TAYC 2 REYQ216TAYC 1 1 REYQ240TAYC 2 REYQ2...

Page 6: ...y For additional information see technical engineering data 1 4 Scope of the manual This manual describes the procedures for handling installing and connecting the VRV IV REYQ T series outdoor units T...

Page 7: ...nough to support the weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance...

Page 8: ...mproper installation may result in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will dist...

Page 9: ...igure below and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A...

Page 10: ...ions can be found in the Engineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carr...

Page 11: ...tion bolts until their length remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the...

Page 12: ...ational regulations After piping work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 18 and 12 Checking of device and installation conditions on page 24 ar...

Page 13: ...in 34 9 mm 7 3 2 Piping between refrigerant branch kits or refrigerant branch kits and Branch Selector units D Choose from the following table in accordance with the indoor unit total capacity connect...

Page 14: ...Indoor unit capacity index Kit name for 3 pipes for 2 pipes 72 KHRP25M33H9 KHRP25M33HA KHRP26M22H9 KHRP26M22HA maximum 4 indoor units or KHRP26M33H9 KHRP26M33HA maximum 8 indoor units 72 111 KHRP26M33...

Page 15: ...ing length from the first outdoor unit multi connection piping kit to the outdoor unit 33 ft 10 m Equivalent piping length from the first outdoor unit multi connection piping kit to the outdoor unit 4...

Page 16: ...e as fol lows 3 8 in 9 5 mm 1 2 in 12 7 mm 1 2 in 12 7 mm 5 8 in 15 9 mm 5 8 in 15 9 mm 3 4 in 19 1 mm 3 4 in 19 1 mm 7 8 in 22 2 mm C REFNET joints G b d m B f A c D 9 H e g 6 h n F i 4 Outdoor unit...

Page 17: ...vents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and prevents proper operation...

Page 18: ...he burner flame Liquid pipe stop valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched pip...

Page 19: ...of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection pip...

Page 20: ...ally or vertically Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints h...

Page 21: ...refer to 8 3 2 How to use the stop valve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec tr...

Page 22: ...z f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 575V 15 1 16 8 18 2 22 3 24 9 16 8 16...

Page 23: ...multi system And the other units are Sub unit In this figure outdoor unit A is the Master unit Check operation in installation work onsite settings and so on are done by operating the printed circuit...

Page 24: ...e accessory CAUTION Be sure to use crimp style terminal with insulating sleeves for con nections See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated po...

Page 25: ...OTE Always use nitrogen gas for the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is op...

Page 26: ...ze the system to 375 000 microns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to...

Page 27: ...e front panel see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switches 3 1 2 1 Front panel 2 Inspect...

Page 28: ...indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will re...

Page 29: ...ing the additional refrigerant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant...

Page 30: ...s BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 1 36 1 54 2 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 15 ft r f1 2 10 ft b f5 8 20 ft f f3 8 10...

Page 31: ...is a mixed refrigerant adding it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a sipho...

Page 32: ...d stop valve service port open valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B 9 8 11 11 12 10 14 13 15 16 A C 7 1 Pressure reducing valve 2 Nitr...

Page 33: ...top valves after pre charging the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this ch...

Page 34: ...e selected time frames The second method is to enable low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption lim...

Page 35: ...ly be effective when the optional external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase...

Page 36: ...tation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumption limitation that will be applied continuously The...

Page 37: ...e target temperature upper limit Default value 1 Value 2 92 Te target temperature upper limit 0 L 1 M 2 H If Auto Te then use this setting to address different load pro files If the frequent operation...

Page 38: ...ting 2 8 and 2 47 To activate the powerful comfort setting under heating opera tion change field setting 2 82 3 This setting is used in conjunction with setting 2 9 Quick Overshoot during heating oper...

Page 39: ...D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46 C 36 F 2 C A Virtual lo...

Page 40: ...MATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour run elapse before reaching smoot...

Page 41: ...ion code which is displayed on the outdoor unit will indi cate a main malfunction code and a sub code The sub code indicates more detailed information about the malfunction code The malfunc tion code...

Page 42: ...ction R10T A1P X29A Check connection on printed circuit board or actuator J6 01 02 03 Temperature sensor malfunction R11T A7P X15A Check connection on printed circuit board or actuator 08 09 10 Temper...

Page 43: ...iring between units Check indoor unit amount and total capacity con nected Check connection U9 01 System mismatch Wrong type of indoor units com bined R407C Mini split etc Indoor unit malfunction Chec...

Page 44: ...Pull out junction connectors X1A X2A X3A X4A for the fan motors in the outdoor unit before starting service operation on the inverter equipment Be careful not to touch the live parts If a fan rotates...

Page 45: ...tions and standards for the maximum allowable concentration level is required 2 1 1 Direction of the refrigerant flow 2 Room where refrigerant leak has occurred outflow of all the refrigerant from the...

Page 46: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P362438 9N EM16A003B 1912 HT 00_CV_3P362438 9N indd 2 2019 09 12 11 44 31...

Reviews: