![background image](http://html1.mh-extra.com/html/daikin/re25jv1/re25jv1_removal-procedure_2459793013.webp)
Si01-752
Removal of Compressor
Removal Procedure
11
4
Heat up the brazed part
of the discharge side
and disconnect.
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to burn
the compressor terminals,
the name plate, the heat
exchanger fin.
5
Heat up the brazed part
of the suction side and
disconnect.
6
Lift the compressor up
and remove it.
Step
Procedure
Points
(R1876)
Protective
sheet or
steel plate