background image

Page 24 of 48  

 

IM 934-5

Operation

Memory Recall

The digital control shall start with the last settings used prior 

to power down. These settings are saved in a non-volatile 

memory. Factory set mode is OFF. 

On/Off Triggering 

Control can be turned On/Off via LUI, Remote T’stat, or 

Sleep feature. The control will show the temperature set 

point when the mode is Cool, Cool Dry, or Heat. The display 

will be blank in Fan mode.

1.

 

On/Off triggering with LUI

 

  Control shall turn On or Off when the On/Off button is 

pressed in LUI. Once turned on control shall start on the 

last mode used before it was turned Off.

2.

 

On/Off triggering with the Remote T’stat 

  Control shall be turned On if it was Off from the Remote 

T’stat when it is set up to be controlled by a Remote 

T’stat. A call for heat or cool from the Remote T’stat will 

be used to turn the control on. Control remains on until 

manually turned Off.

3.

 

On/Off triggering with the Sleep feature

  Sleep feature works in combination with the Timer 

setting. Sleep time setting shall be user adjustable from 

1 to 15 hours via the Touchpad. The timer will count 

down and when it reaches “0” it will turn the control Off 

if control was previously On and vice versa, if it was 

Off it will turn On after time expires. As mentioned in 

protections

 section of this spec the Sleep operation is 

overridden by room freeze protection.

Control Off

When the control is in the Off Mode, relay outputs will be 

disabled with the exception of the indoor fan (blower).  It 

will stay on to meet the 

Hot Keep 

specification. Indicator 

LED’s are all off.

Temperature Range

The maximum operating temperature range is selectable via 

the Touchpad and is 60°F to 85°F with the limits included. 

The Remote Thermostat selectable operating range is 60°F 

to 90°F with limits included. The range is set in the Set-up 

menu.

Indoor and Outdoor Fan Operation

The indoor fan can be set to operate on High or Low speed 

with the Fan Speed Button on the touchpad. It can also be set 

for Continuous or Cycle operation on the touchpad. When 

set for Continuous, the “CONT” LED will be on and the fan 

will run continuously. When set for Cycle, the “CYCLE” 

LED will be on and the fan will turn on at a call for heat or 

cooling.

Fan Cycle Operation 

On a call for Heating or Cooling, the indoor fan and the 

heating source or the compressor will be activated. When the 

call is satisfied and the heating source or the compressor is 

deactivated, the indoor fan will repeatedly run for 2 minutes 

on and the number of minutes selected on the PC Board off, 

until the next cut-in cycle. The number of cycles with timing 

as described above is determined based on the OFF FAN 

CYCLE jumper setting. 

Remote T’Stat Mode

The unit can be jumper configured to take commands from 

a Remote Thermostat. The Remote Thermostat will call for 

Heat and Cool through the electronic controller. 
1.  The Remote T’stat will control through the board the 

work of the compressor, indoor and outdoor fans, the 

reversing valve, and the heater 

2.  System will run in Cool mode when Y signal is high. In 

cool mode compressor (therefore outdoor fan) shall turn 

on

3.  Cold start feature (see Modes of Operation – Cold Start), 

Cool dry mode (see Cold Dry Mode) and Sleep feature 

(see Sleep Feature) are not available in Remote T’stat 

cool mode

4.  In T'STAT mode, the fan speed can be changed at the 

Touchpad and the fan mode is dictated by the Remote 

t'stat.

System Select Operation Using Remote 
Thermostat

System will run in Heat mode and engage certain outputs 

based on the system selection (jumper) as described below 

(see Standard Digital Control Board Wiring Diagram on 

page 31).

AC/ELE

•  If AC/ELE is selected then a signal on W terminal will 

call for heating. 

HP or HP/ELE

•  If HP or HP/ELE is selected then signals on Y and B 

terminals will call for heating.

NOTES:

  1. Hot start and Sleep features are not available in  

    Remote T’stat heat mode.

 

  2. Control’s operation is subject to its own    

    protection features when controlled by a Remote  

    T’stat

 

  3. Indoor fan mode and the speed will default  

    to “cycle” and “high” when unit is controlled by  

    Remote T’stat

 

  4. The indoor fan is turned on when G signal is  

    high. When there is no signal on G terminal then  

    the indoor fan will be turned off.

Summary of Contents for McQuay IM 934-5

Page 1: ...type of equipment Caution Sharp edges and coil surfaces are potential injury hazards Installation Maintenance Data IM 934 5 Group PTAC Part Number 910146417 Date August 2013 Applied Packaged Terminal...

Page 2: ...Operation 24 System Select Operation Using Remote Thermostat 24 Sequence of Operation 25 Heat Mode 26 Standard or Programmable Digital Touchpad LUI Control Set Up Mode Selection 26 Thermistor Error C...

Page 3: ...Unit terminals are not designed to accept other types of conductors Failure to do so can damage equipment Inspection When the equipment is received all items should be care fully checked against the b...

Page 4: ...g Type E Electric Heat H Hydronic A Hydronic w Intermediate Electric Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type T Steam Subbase Normally Closed J Hot Water Subbase Normally Ope...

Page 5: ...existing buildings The self contained refriger ant system delivers cooling to the desired space Heating can be accomplished with electric resistance with hydronic wa ter or steam hydronic with interme...

Page 6: ...1mm to 349mm See Electric Subbase on page 8 Hydronic 0 to 133 4 0mm to 349mm See Hydronic Subbase on page 9 Subbase Height Dimension Electric 3 to 4 76mm to 102mm with 0 to 1 0mm to 25m leveling screw...

Page 7: ...o 4 above the finished floor includ ing carpeting to match the height of the subbase selected The subbase is available in 3 or 4 heights and has adjust able leveling legs that provide up to an additio...

Page 8: ...wall sleeve using the clips provided with the subbase 5 The wiring should be roughed in and the conduit connected to the subbase junction box Complete the installation by wiring the receptacle to the...

Page 9: ...annels are predrilled to allow infinite adjustment 2 Subbase shown with louvered front panel removed Front panel is hinged to allow access to valve coil filter electrical junction box 3 Leveling legs...

Page 10: ...y the design engineer in the space provided under the heating coil Electrical The electrical supply can also be roughed in to the subbase heat section either through the holes provided in the base or...

Page 11: ...Place the drain kit against the chosen drain hole and fasten securely with screws provided Use either the 90 elbow or 6 straight fitting as required 4 Cover the unused drain hole with the block off p...

Page 12: ...s are supplied to assemble the chassis and the louver to the wall sleeve Wall Sleeve Extension for Thick Wall Construction Types The standard wall sleeve will accommodate a maximum wall thickness desc...

Page 13: ...and tagged to match the proper unit Be sure to check tagging of the extension against that of the unit Install the wall sleeve extension as follows 1 Position the extension with standard wall sleeve s...

Page 14: ...on the sides 6 Secure by anchoring with appropriate fastener s A 5 16 8mm hole is provided on each side 2 51 mm down from the top and 2 51mm in from the rear of the wall sleeve Additional holes may b...

Page 15: ...e The wall sleeve is not intended to replace the lintel 5 Level wall sleeve left to right and pitch 1 4 front to back pitch to the outside Secure by anchoring with appropriate fasteners A 5 16 8mm hol...

Page 16: ...be used for this purpose 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level wall sleeve left to right and pitch 1 4 front to back to the outside Secure by...

Page 17: ...g of all debris that may interfere with installation 2 If the unit is to be supplied with a subbase install subbase before installing wall sleeve See IM 936 x 3 If the optional drain kit is to be empl...

Page 18: ...unting Screws by installer Caulk Perimeter Steel Lintel by others Table 2 Maximum Wall Thickness Louver Type Stamped Architectural No Subbase Standard Subbase Hydronic Subbase Maximum Wall Thickness 1...

Page 19: ...ding facade treat ments that may affect normal operation of the unit or restrict free air discharge of condenser airflow A louver design that restricts the passage of condenser air or causes condenser...

Page 20: ...ng carton to cover installed conditioner until construction is complete 3 Check nameplate data on chassis to insure that the correct job site distribution has been made with respect to heating cooling...

Page 21: ...rvice or the like in the price of its equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected acciden...

Page 22: ...e Freely Without Striking Fan Housing Condenser Air Free of Obstruction Cycle Continuous Fan if so equipped Other Conditions Found ___________________________________________________________ _________...

Page 23: ...Slave Unit Touchpad Display Indicates Unit is Controlled by a Master Occurs when Slave Control Select Jumper is on SEC Pins rT Remote Thermostat Control tP Touchpad Control t Time Ts Temperature Setpo...

Page 24: ...eration on the touchpad When set for Continuous the CONT LED will be on and the fan will run continuously When set for Cycle the CYCLE LED will be on and the fan will turn on at a call for heat or coo...

Page 25: ...he unit will run in the regular cool mode The indoor fan will operate according to the user settings for mode Continuous or Cycle and Speed Cold start is not available with the Sleep feature Sleep Fun...

Page 26: ...Up Mode are as follows 1 Temperature Scale Selection Once in the Set Up Mode the temperature scale will be displayed To change the temperature scale to degree Celsius press the Up or Down button The d...

Page 27: ...once The display will show return air temperature 6 Indoor Coil Sensor Reading To advance from Indoor Air Sensor Reading to Indoor Coil Sensor Reading press the Mode Button once The display will show...

Page 28: ...indications of 5 F above or below set point will be consistent with the set up mode settings for minimum and maximum temperatures Temperature Limit Settings 1 To adjust the lower operating temperatur...

Page 29: ...from Cooling to Heating Heating to Cooling AUTO Available with the Programmable LUI 668003802 and Pre mium Board 667997303 only The Auto Changeover board has a new control set with a touchpad label th...

Page 30: ...shows both HEAT and COOL icons Temperature set point displays between the HEAT and COOL icons Setpoint is adjusted with Up and Down arrows Heating initiates when the room temperature falls one degree...

Page 31: ...mmed daily settings will be re tained in memory However the clock must be reset to the current time for the programmed daily settings to resume the correct schedule of operation See Clock Set Menu ins...

Page 32: ...ion with the compressor When requested all necessary relays and transformers are factory mounted and ready for attachment to field supplied low voltage wires All thermostats are 24 volt type and have...

Page 33: ...hangeover Two Stage Heat Two Stage Cool Specs Daikin McQuay Part No 910116774 1 Pk White with Wall Plate Specifications Electrical Rating 24 VAC 18 to 30 VAC 1 amp maximum per terminal 4 amp maximum t...

Page 34: ...emote must be aimed in a line of sight of the window in the upper right corner on the front panel at less than a 45 angle from center of the window T9000 Wireless Temperature Control The T9000 Wireles...

Page 35: ...t be in the SEC position If secondary units are to be employed see wiring connections in Figure 39 The number of secondary units that can be connected is limited to 32 units Remote Mounted Thermostat...

Page 36: ...Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SLAVE to select SLAVE Control by a master unit C Place jumper across T STAT to select remote wall mou...

Page 37: ...or Fan Motor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Reversing Valve EHC Electric Heat Contactor Standard Non Programma...

Page 38: ...nections can be spliced to substitute for the missing jumpers Legend DM Damper Motor HYV Hydronic Valve CM Compressor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS...

Page 39: ...nnections can be spliced to substitute for the missing jumpers Legend DM Damper Motor HYV Hydronic Valve CM Compressor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS...

Page 40: ...reas with high dirt and lint content or heavy usage of units require more frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction will occur...

Page 41: ...Chassis 2 Compressor Overload Device 2 Compressor Running Capacitor 2 Fan Motor Capacitor 2 Control Board 2 Thermostat 2 Control Relay if used 2 Damper Motor if auto damper 2 Electric Resistance Heat...

Page 42: ...board or heating medium 250 F Check for installation connection of HFLO sensor Should be on coil return line Protection Description Cause for the fault code CF Coil Freeze Protection Indoor coil tempe...

Page 43: ...mode and outdoor air 25 Compressor will cut out Slave Unit Set to be When slave unit jumper for Control Select is positioned over SEC slave unit is set to be controlled by Controlled by a Master Unit...

Page 44: ...cted discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e Wi...

Page 45: ...ustments to components f Check for proper adjustment Apply silicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap pa...

Page 46: ......

Page 47: ......

Page 48: ...2013 McQuay International 800 432 1342 www daikinmcQuay com IM 934 5 8 13 Page 48 of 48...

Reviews: