Figure 14: Louver Frame Dimensions
42
3
/
16
"
(1072mm)
16
3
/
16
"
(411mm)
3
3
/
4
"
(92mm)
44
3
/
16
"
(1122mm)
18
3
/
16
"
(1072mm)
Note:
Wall Sleeve rough opening when using a Louver
Frame must be 16-5/8" x 42-5/8"
Installing Recessed Louver Wall
Sleeve
Installation Requirements for Recessed
Louver Wall Sleeve
1. The Recessed Louver Wall Sleeve must extend a
minimum of 1-1/4" past the finished interior wall.
2. The Recessed Louver Wall Sleeve must be installed so
that it is flush with the exterior face of the building and
the drip edge must extend 1/4" beyond the face
(
Figure 15
).
Figure 15: Recessed Louver Wall Sleeve Detail
Level the top of the wall
sleeve, NOT the base of the
wall sleeve (
see IMPORTANT
notice on page 14
)
Steel Lintel
(by others)
See Note
Room
Cabinet
16"
(406mm)
17"
(432mm)
8
1
/
4
"
(209mm)
Finished
Floor
or Carpet
Wall Receptacle
(by others)
Wall Sleeve
Extends 1/4"
beyond the
exterior face
of the building
15
7
/
8
"(403mm)
13
3
/
4
"
(349mm)
Drip Edge
Detail
5/16" (8mm)
Anchor Hole
Note:
Standard subbase is available in 3" or 4" (76 mm or
102 mm) height. Leveling legs provide adjustment of
1" (25 mm).
Installing Wall Sleeve Extension
Wall sleeve extensions are shipped in a separate carton and
tagged to match the proper unit. Be sure to check tagging of
the extension against that of the unit. Install the wall sleeve
extension as follows:
1. Position the extension with standard wall sleeve so
proper alignment with drain and mounting holes is
achieved.
2. Place a bead of caulk around the perimeter of the wall
sleeve and another bead around the mating side of the
wall sleeve extension so that the joint is watertight. Be
sure to use a resilient caulking such as silicone.
3. Assemble the wall sleeve extension to the wall sleeve.
Clean out weep holes to assure proper drainage.
4. Attach indoor drain kit (if used) according to the
instructions
"Indoor Drain Kit" on page 11
. Outdoor
drain kits must be installed after wall sleeve is in place.
5. Continue wall sleeve installation according to
instruction
#4 on page 14
.
Figure 13: Wall Sleeve Extension
Wall Sleeve Extension
6
7
/
8
"
11
1
/
8
"
42"
Room Side
Air Splitters
As Required
24"
16"
24"
Installing Louver Frame for Thin
Wall Construction Types
Louver frames should be used for panel wall and thin wall
applications to assure positive anchoring to the wall. Recess
the wall sleeve so that the louver is flush with the outside
of the building. Place louver frame around wall sleeve as
shown in
Figure 14
. Secure angles at side and top of walls.
CAUTION
DO NOT drill holes in the bottom of the wall sleeve as it will
cause leaks.