background image

IM 934-5 

 

Page 25 of 48

Control Lockout Feature

 The control is placed in a lockout mode of operation when 

Mode button is held pressed for 10 seconds. Display will 

show “LC” to confirm Lockout Mode has been entered. 

Once in this Lockout Mode the control board will not take 

any commands at all. In Lockout, unit will continue to 

operate with the same settings just prior to Lockout Mode. 

This means the touchpad will no longer be able to pass 

commands to the control. User’s set point will normally be 

displayed. Any button pushed will bring “LC” on display for 

five seconds.
To exit the Lockout Mode and return to normal (regular) 

mode of operation, press the Mode button for 10 seconds. 

Display will show “nL” for five seconds to confirm normal 

mode has been resumed.

Sequence of Operation

Cool Mode

In Cool Mode, the compressor will start if the temperature 

at the space temperature sensor is 1°F or higher than the set 

point. It will stop if the space temperature sensor is 2°F or 

lower than the set point, subject to timing requirements.
In the Cool Mode, the indoor fan will operate according to 

the user settings for Fan Mode –  Continuous or Cycle and 

Speed.

Cold Start

Cold start is initiated when the control has not called for 
cooling for more than two (2) hours or during a power-
on-reset.

  During cold start, the set point is lowered by 4°F 

(Tset-4°F) if the differential calls for cooling. The unit will 

operate in cold start until the new set point is satisfied (+ 

or – 1°F) or until the unit has run in cold start for at least 20 

minutes.  After one or both conditions are met, the set point 

will be reset to the user setting and the unit will run in the 

regular cool mode.
The indoor fan will operate according to the user settings for 

mode – Continuous or Cycle and Speed.
Cold start is not available with the 

Sleep

 feature.

Sleep Function

Sleep time is adjustable by the user from 1 to 15 hours in 

one (1) hour increments in a closed loop. The sleep time is 

adjusted and set via the touchpad and by pressing the Sleep 

Button repeatedly. On the touchpad, the display will show 

the set time in numbers for five (5) seconds. Before the sleep 

time expires, the setting can be adjusted above the number of 

hours passed by pressing the Sleep Button. Pressing the On/

Off Button can terminate the Sleep Mode.
A changeover from Heat to Cool or another Mode will reset 

the Sleep Timer.
The Sleep Function will be deactivated by pressing the 

power-on-reset or any button (except sleep) on the touchpad 

or the Remote Control.

Cool Dry Mode 

Select the Cool Dry Mode when the standard Cool Mode 

does not provide sufficient dehumidification. In Cool Dry 

Mode, the unit must run in Cool Mode for 12 minutes or 

until the temperature differential between the room tempera-

ture and the set point is less than 2°F. This will also occur 

after a Cold Start or a Mode change from Cool to Cool Dry. 

During this time the fan will operate in the Mode and Speed 

selected.
Until one or both of the above conditions are met, the con-

trol will determine which Dry Mode (Zone) is initiated based 

on  the temperature differential between the room tempera-

ture (Tr) and the temperature set point (Ts):

Note:

  Cool Dry is not available with Sleep Function.

Figure 32: If Tr - Ts > 4°F, operation will be in Zone A

Compressor

L

ow Fan

12 mins

.

On

Off

On

Off

*

t

t

*

 = Zone Determination Time

Figure 33: If 2°F < Tr - Ts < 4°F, operation will be in Zone 
B

Compressor

L

ow Fan

t

On

Off

On

Off

30 secs

.

30 secs

.

8

 mins

.

4 mins

.

t

Summary of Contents for McQuay IM 934-5

Page 1: ...type of equipment Caution Sharp edges and coil surfaces are potential injury hazards Installation Maintenance Data IM 934 5 Group PTAC Part Number 910146417 Date August 2013 Applied Packaged Terminal...

Page 2: ...Operation 24 System Select Operation Using Remote Thermostat 24 Sequence of Operation 25 Heat Mode 26 Standard or Programmable Digital Touchpad LUI Control Set Up Mode Selection 26 Thermistor Error C...

Page 3: ...Unit terminals are not designed to accept other types of conductors Failure to do so can damage equipment Inspection When the equipment is received all items should be care fully checked against the b...

Page 4: ...g Type E Electric Heat H Hydronic A Hydronic w Intermediate Electric Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type T Steam Subbase Normally Closed J Hot Water Subbase Normally Ope...

Page 5: ...existing buildings The self contained refriger ant system delivers cooling to the desired space Heating can be accomplished with electric resistance with hydronic wa ter or steam hydronic with interme...

Page 6: ...1mm to 349mm See Electric Subbase on page 8 Hydronic 0 to 133 4 0mm to 349mm See Hydronic Subbase on page 9 Subbase Height Dimension Electric 3 to 4 76mm to 102mm with 0 to 1 0mm to 25m leveling screw...

Page 7: ...o 4 above the finished floor includ ing carpeting to match the height of the subbase selected The subbase is available in 3 or 4 heights and has adjust able leveling legs that provide up to an additio...

Page 8: ...wall sleeve using the clips provided with the subbase 5 The wiring should be roughed in and the conduit connected to the subbase junction box Complete the installation by wiring the receptacle to the...

Page 9: ...annels are predrilled to allow infinite adjustment 2 Subbase shown with louvered front panel removed Front panel is hinged to allow access to valve coil filter electrical junction box 3 Leveling legs...

Page 10: ...y the design engineer in the space provided under the heating coil Electrical The electrical supply can also be roughed in to the subbase heat section either through the holes provided in the base or...

Page 11: ...Place the drain kit against the chosen drain hole and fasten securely with screws provided Use either the 90 elbow or 6 straight fitting as required 4 Cover the unused drain hole with the block off p...

Page 12: ...s are supplied to assemble the chassis and the louver to the wall sleeve Wall Sleeve Extension for Thick Wall Construction Types The standard wall sleeve will accommodate a maximum wall thickness desc...

Page 13: ...and tagged to match the proper unit Be sure to check tagging of the extension against that of the unit Install the wall sleeve extension as follows 1 Position the extension with standard wall sleeve s...

Page 14: ...on the sides 6 Secure by anchoring with appropriate fastener s A 5 16 8mm hole is provided on each side 2 51 mm down from the top and 2 51mm in from the rear of the wall sleeve Additional holes may b...

Page 15: ...e The wall sleeve is not intended to replace the lintel 5 Level wall sleeve left to right and pitch 1 4 front to back pitch to the outside Secure by anchoring with appropriate fasteners A 5 16 8mm hol...

Page 16: ...be used for this purpose 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level wall sleeve left to right and pitch 1 4 front to back to the outside Secure by...

Page 17: ...g of all debris that may interfere with installation 2 If the unit is to be supplied with a subbase install subbase before installing wall sleeve See IM 936 x 3 If the optional drain kit is to be empl...

Page 18: ...unting Screws by installer Caulk Perimeter Steel Lintel by others Table 2 Maximum Wall Thickness Louver Type Stamped Architectural No Subbase Standard Subbase Hydronic Subbase Maximum Wall Thickness 1...

Page 19: ...ding facade treat ments that may affect normal operation of the unit or restrict free air discharge of condenser airflow A louver design that restricts the passage of condenser air or causes condenser...

Page 20: ...ng carton to cover installed conditioner until construction is complete 3 Check nameplate data on chassis to insure that the correct job site distribution has been made with respect to heating cooling...

Page 21: ...rvice or the like in the price of its equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected acciden...

Page 22: ...e Freely Without Striking Fan Housing Condenser Air Free of Obstruction Cycle Continuous Fan if so equipped Other Conditions Found ___________________________________________________________ _________...

Page 23: ...Slave Unit Touchpad Display Indicates Unit is Controlled by a Master Occurs when Slave Control Select Jumper is on SEC Pins rT Remote Thermostat Control tP Touchpad Control t Time Ts Temperature Setpo...

Page 24: ...eration on the touchpad When set for Continuous the CONT LED will be on and the fan will run continuously When set for Cycle the CYCLE LED will be on and the fan will turn on at a call for heat or coo...

Page 25: ...he unit will run in the regular cool mode The indoor fan will operate according to the user settings for mode Continuous or Cycle and Speed Cold start is not available with the Sleep feature Sleep Fun...

Page 26: ...Up Mode are as follows 1 Temperature Scale Selection Once in the Set Up Mode the temperature scale will be displayed To change the temperature scale to degree Celsius press the Up or Down button The d...

Page 27: ...once The display will show return air temperature 6 Indoor Coil Sensor Reading To advance from Indoor Air Sensor Reading to Indoor Coil Sensor Reading press the Mode Button once The display will show...

Page 28: ...indications of 5 F above or below set point will be consistent with the set up mode settings for minimum and maximum temperatures Temperature Limit Settings 1 To adjust the lower operating temperatur...

Page 29: ...from Cooling to Heating Heating to Cooling AUTO Available with the Programmable LUI 668003802 and Pre mium Board 667997303 only The Auto Changeover board has a new control set with a touchpad label th...

Page 30: ...shows both HEAT and COOL icons Temperature set point displays between the HEAT and COOL icons Setpoint is adjusted with Up and Down arrows Heating initiates when the room temperature falls one degree...

Page 31: ...mmed daily settings will be re tained in memory However the clock must be reset to the current time for the programmed daily settings to resume the correct schedule of operation See Clock Set Menu ins...

Page 32: ...ion with the compressor When requested all necessary relays and transformers are factory mounted and ready for attachment to field supplied low voltage wires All thermostats are 24 volt type and have...

Page 33: ...hangeover Two Stage Heat Two Stage Cool Specs Daikin McQuay Part No 910116774 1 Pk White with Wall Plate Specifications Electrical Rating 24 VAC 18 to 30 VAC 1 amp maximum per terminal 4 amp maximum t...

Page 34: ...emote must be aimed in a line of sight of the window in the upper right corner on the front panel at less than a 45 angle from center of the window T9000 Wireless Temperature Control The T9000 Wireles...

Page 35: ...t be in the SEC position If secondary units are to be employed see wiring connections in Figure 39 The number of secondary units that can be connected is limited to 32 units Remote Mounted Thermostat...

Page 36: ...Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SLAVE to select SLAVE Control by a master unit C Place jumper across T STAT to select remote wall mou...

Page 37: ...or Fan Motor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Reversing Valve EHC Electric Heat Contactor Standard Non Programma...

Page 38: ...nections can be spliced to substitute for the missing jumpers Legend DM Damper Motor HYV Hydronic Valve CM Compressor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS...

Page 39: ...nnections can be spliced to substitute for the missing jumpers Legend DM Damper Motor HYV Hydronic Valve CM Compressor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS...

Page 40: ...reas with high dirt and lint content or heavy usage of units require more frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction will occur...

Page 41: ...Chassis 2 Compressor Overload Device 2 Compressor Running Capacitor 2 Fan Motor Capacitor 2 Control Board 2 Thermostat 2 Control Relay if used 2 Damper Motor if auto damper 2 Electric Resistance Heat...

Page 42: ...board or heating medium 250 F Check for installation connection of HFLO sensor Should be on coil return line Protection Description Cause for the fault code CF Coil Freeze Protection Indoor coil tempe...

Page 43: ...mode and outdoor air 25 Compressor will cut out Slave Unit Set to be When slave unit jumper for Control Select is positioned over SEC slave unit is set to be controlled by Controlled by a Master Unit...

Page 44: ...cted discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e Wi...

Page 45: ...ustments to components f Check for proper adjustment Apply silicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap pa...

Page 46: ......

Page 47: ......

Page 48: ...2013 McQuay International 800 432 1342 www daikinmcQuay com IM 934 5 8 13 Page 48 of 48...

Reviews: