10 About the system
Installation and operation manual
30
LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09
English
Translation
**
/12.2
Connection ** continues on page
12 column 2
1
Several wiring possibilities
Option
Not mounted in switch box
Wiring depending on model
PCB
Notes:
1
Symbols: see above.
2
Refer to the installation or service manual on how to use
BS1~BS4 push buttons and DS1‑1~DS1‑2 switches.
3
Do not operate the unit by short-circuiting protection device
S1PH.
4
The capacity of this contact is 220~240 V AC – 0.5 A (total of
caution output, warning output, run output, and operation
output).
5
The initial setting is "0" (OFF). To operate, set to
"1" (REMOTE) or "2" (ON).
6
To use the remote switch, use a voltage-free contact for
microcurrent (<1 mA - 12 V DC). For instructions on how to
use the remote switch, refer to the technical engineering data.
7
The initial state of SW1 is "open" (normal mode). To activate
low‑noise mode, close the contact.
Legend for wiring diagram 4:
A1P
Printed circuit board (main)
A2P
Printed circuit board (inverter)
BS* (A1P)
Push buttons (MODE, SET, RETURN, TEST, RESET)
C* (A2P)
Capacitor
DS1 (A1P)
DIP switch
E, E1 (A1P) Connector
F1U (A1P)
Fuse (T 31.5 A / 500 V)
F1U (A2P)
Fuse (T 5 A / 250 V)
F2U (A1P)
Fuse (T 31.5 A / 500 V)
F3U
Fuse (T 1.0 A / 250 V)
F3U (A1P)
Fuse (T 6.3 A / 250 V)
F4U
Fuse (T 1.0 A / 250 V)
F4U (A1P)
Fuse (T 6.3 A / 250 V)
F5U (A1P)
Fuse (T 6.3 A / 250 V)
HAP (A*P)
Running LED (service monitor is green)
H*P (A1P)
LED (service monitor is orange)
K1M (A2P)
Magnetic contactor
K*R (A*P)
Magnetic relay
L1R
Reactor
L*A
Connector
M1C
Motor (compressor)
M1F
Motor (fan) (upper)
M2F
Motor (fan) (lower)
NA (A1P)
Connector
P1, P2
(A2P)
Connector
PS (A2P)
Power supply
Q1DI
Earth leakage circuit breaker (field supply)
R1T
Thermistor (air)
R2T
Thermistor (M1C discharge)
R3T
Thermistor (suction)
R4T
Thermistor (liquid pipe)
R5T
Thermistor (subcool heat exchanger outlet)
R6T
Thermistor (subcool heat exchanger inlet)
R10T
Thermistor (fin)
R* (A2P)
Resistor
S1NPH
Pressure sensor (high)
S1NPL
Pressure sensor (low)
S1PH
Pressure switch (high)
S1S
Operation switch (REMOTE/OFF/ON)
SW1
Low‑noise mode switch
SW2
External operation switch
U, V, W
(A2P)
Connector
V1R (A2P)
IGBT power module
V2R, V3R
(A2P)
Diode module
X*A
PCB connector
X*M
Terminal strip
X*Y
Connector
Y1E
Electronic expansion valve (subcool)
Z*C
Noise filter (ferrite core)
Z*F (A1P)
Noise filter
For the user
10
About the system
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future
system extensions) is available in technical engineering
data and should be consulted. Contact your installer to
receive more information and professional advice.
10.1
System layout
c
b
d
a
a
Outdoor unit (ZEAS condensing unit)
b
Refrigerant piping
c
Indoor unit (Blower coil)
Summary of Contents for LRLEQ3BY1