background image

5 Installation

Installation and operation manual

19

LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09

Charging refrigerant (with the compressor running)

The  remaining  additional  refrigerant  charge  can  be  charged  by
operating the outdoor unit.

13

Connect as shown. Make sure valve A is closed.

p< p>

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

14

Open the gas line stop valve all the way and adjust the opening
of the liquid line stop valve.

15

Take  all  the  precautions  mentioned  in 

"6  Configuration"  on

page 22

 and 

"7 Commissioning" on page 25

 into account.

16

Turn  on  the  power  of  the  outdoor  unit,  but  leave  the  operation
switch turned off (see 

"5.7.4 To connect the electrical wiring on

the outdoor unit" on page 21

).

17

Set  the  target  evaporating  temperature  with  settings  [2‑0]  and
[2‑1] (see 

"6.1.8 Mode 2: Field settings" on page 24

).

18

Turn on the power of the indoor units.

19

Turn on the operation switch.

Result: 

The unit will start operation.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"5.6.4  Error

codes  when  charging  refrigerant"  on  page  19

  and

solve the malfunction accordingly.

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

turning OFF the operation switch. The unit will stop and
return to idle condition.

20

Open valves B and C.

21

Charge  refrigerant  until  the  remaining  determined  additional
refrigerant  amount  is  added  (see 

"5.6.2  To  determine  the

additional  refrigerant  amount"  on  page  17

),  and  then  close

valves C and B.

INFORMATION

▪ When there is little refrigerant remaining in the cylinder,

the  cylinder's  internal  pressure  will  drop,  making  it
impossible to charge the unit, even if the opening of the
liquid  line  stop  valve  is  adjusted.  If  this  is  the  case,
replace the cylinder with one that has more refrigerant
remaining.

▪ If the piping length is long, replenishing while the liquid

line  stop  valve  is  fully  closed  may  lead  to  activation  of
the  protection  system,  causing  the  unit  to  stop
operation.

22

Check  the  sight  glass  of  the  outdoor  unit.  If  the  refrigerant  is
NOT  in  sealing  state,  charge  extra  refrigerant,  but  do  NOT
exceed  25%  of  the  determined  additional  refrigerant  amount
(see 

"5.6.2  To  determine  the  additional  refrigerant  amount"  on

page 17

)

b

a

c

d

O

Sealing state (= sufficient refrigerant)

X

Insufficient refrigerant

a

Sight glass

b

Full of liquid

c

A little foam in the liquid

d

A lot of foam in the liquid

23

Turn off the operation switch.

NOTICE

Make sure to open all stop valves after (pre-) charging the
refrigerant.

Operating  with  the  stop  valves  closed  will  damage  the
compressor.

NOTICE

Thread-locking  fluid

.  Before  reattaching  the  service  port

cover, apply thread-locking fluid to the screw thread (NOT
to  the  cover  or  sealing  part).  Otherwise,  condensation
water  might  enter  and  freeze. 

Possible  consequence:

Deformation, 

refrigerant 

leakage 

and 

compressor

malfunction.

c

b

a

a

Cover (do NOT apply thread-locking fluid)

b

Sealing part (do NOT apply thread-locking fluid)

c

Screw thread with thread-locking fluid

5.6.4

Error codes when charging refrigerant

INFORMATION

When a malfunction occurs, X3M outputs a caution (C/C1)
or  warning  (C/W1)  signal,  and  the  H2P  LED  on  the  main
PCB lights up.

If  a  malfunction  occurs,  close  valve  B  and  C  immediately.  Confirm
the  malfunction  code  and  take  corresponding  action, 

"8.1  Solving

problems based on error codes" on page 27

.

5.6.5

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Greenhouse gas emissions

 of the total refrigerant charge

expressed as tonnes CO

2

 equivalent

f

GWP = Global warming potential

Summary of Contents for LRLEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1 LRLEQ3BY1 LRLEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...ektiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek...

Page 6: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Page 7: ...igerant 19 5 6 5 To fix the fluorinated greenhouse gases label 19 5 7 Connecting the electrical wiring 20 5 7 1 Field wiring Overview 20 5 7 2 Guidelines when knocking out knockout holes 21 5 7 3 Guid...

Page 8: ...door unit on page 12 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precautions b Outdoor unit installation and operation manual c Fluorinated greenhouse gases l...

Page 9: ...n the following cases When the design pressure is insufficient Minimum design pressure 2 5 MPa or 25 bar When the path to the heat exchanger has been routed so that the flow of refrigerant is from bot...

Page 10: ...en the following into account Select the pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation...

Page 11: ...chnical information of the expansion valve manufacturer take into account the subcooling ratio K for the liquid refrigerant in the table below For LRMEQ3 4 Subcooling ratio K Te 20 C 15 C 10 C 5 C 0 C...

Page 12: ...cable 2 wires Vinyl cords 0 75 1 25 mm Maximum wiring length 130 m 5 Installation 5 1 Opening the units 5 1 1 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING 1 1 2 5 2 Mou...

Page 13: ...a hexagon wrench into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning 4 Install the stop valve cover Result The valve is now ope...

Page 14: ...ay blow off the pinched piping Failure to observe the instructions in procedure below properly may result in property damage or personal injury which may be serious depending on the circumstances Use...

Page 15: ...ingly 5 3 5 To connect the refrigerant piping to the outdoor unit NOTICE Be sure to use the supplied accessory pipes when carrying out piping work in the field Be sure that the field installed piping...

Page 16: ...may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been factory tested for leaks Only field installed ref...

Page 17: ...r first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 5 6 3 To charge refrigerant on page 18 for more information 5 5 To...

Page 18: ...erant until the determined additional refrigerant amount is reached or pre charging is not possible anymore and then close valves B and C 4 Do one of the following If Then The determined additional re...

Page 19: ...ylinder with one that has more refrigerant remaining If the piping length is long replenishing while the liquid line stop valve is fully closed may lead to activation of the protection system causing...

Page 20: ...use c Power supply including earth sheathed cable d Low noise switch e Remote operation switch f Transmission g Caution signal h Warning signal i Run signal j Operation signal NOTICE The operation out...

Page 21: ...mote 3 Connect the low noise switch as follows B A C F1 F2 X2M D NOTICE Low noise switch If you want to remotely turn ON OFF low noise operation see setting 2 18 you must install a low noise switch Us...

Page 22: ...nals c Remote operation switch low noise switch transmission 8 Route the wiring through the frame and connect it to it Routing through the frame a b a b 2 1 a Power supply cable and output signal cabl...

Page 23: ...2P X1M X3M X2M MULTI DEMAND L N O P SLAVE MASTER IND TEST HWL MODE BS1 BS5 Push buttons H1P H7P 7 LEDs display H8P NOT used for field settings ON OFF Flashing Push buttons Use the push buttons to make...

Page 24: ...m The system starts operating according to the setting BS2 X b a BS3 1 c BS3 1 d BS3 1 Action Button display 5 Quit mode 2 BS1 1 6 1 7 Mode 1 and default situation Monitoring settings In mode 1 and in...

Page 25: ...7 to set parameters for the low noise levels default Correction of evaporating temperature only setting 2 13 applies Adjustment of fan and compressor speed only setting 2 17 applies Correction of evap...

Page 26: ...the compressor for oil leakage If there is an oil leak try to repair the leak If the repairing is unsuccessful call your local dealer Air inlet outlet Check that the air inlet and outlet of the unit i...

Page 27: ...lfunction 4 Display the first character of the error code BS3 1 Possible characters E H F J L P U 5 Display the second character of the error code BS2 1 Possible characters 1 2 3 4 5 6 7 8 9 A C 6 Qui...

Page 28: ...n thermistor failure Open circuit or shortcircuit 0 Caution Faulty connection of sensor Defective sensor Connect the sensor properly Replace defective component Heat exchanger inlet thermistor failure...

Page 29: ...on the inside of the front cover Stacked units max 2 levels See figure 3 on the inside of the front cover A1 A2 A1 If there is danger of drainage dripping and freezing between the upper and lower unit...

Page 30: ...0 V F3U A1P Fuse T 6 3 A 250 V F4U Fuse T 1 0 A 250 V F4U A1P Fuse T 6 3 A 250 V F5U A1P Fuse T 6 3 A 250 V HAP A P Running LED service monitor is green H P A1P LED service monitor is orange K1M A2P M...

Page 31: ...and contact the dealer where you purchased the unit Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired 12 2 After sales service and warrant...

Page 32: ...point temperature too high Set the setpoint appropriately Check if there are no high temperature articles stored in the room showcase Always store articles after they have cooled down Check if the doo...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P545024 1 2018 09 Copyright 2016 Daikin 4P441336 1 0000000J 4P545024 1 0000000I...

Reviews: