background image

5 Installation

Installation and operation manual

17

LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P545024-1 – 2018.09

5.4.4

To perform a leak test

The leak test must satisfy the specifications of EN378‑2.

To check for leaks: Vacuum leak test

1

Evacuate  the  system  from  the  liquid  and  gas  piping  to
–⁠100.7 kPa (–⁠1.007 bar)(5 Torr absolute) for more than 2 hours.

2

Once  reached,  turn  off  the  vacuum  pump  and  check  that  the
pressure does not rise for at least 1 minute.

3

Should  the  pressure  rise,  the  system  may  either  contain
moisture (see vacuum drying below) or have leaks.

To check for leaks: Pressure leak test

1

Break  the  vacuum  by  pressurising  with  nitrogen  gas  to  a
minimum gauge pressure of 0.2 MPa (2 bar).

▪ Never set the gauge pressure of the 

high pressure section

of  the  system  higher  than  the  maximum  operation  pressure
of 4.0 MPa (40 bar).

▪ Never set the gauge pressure of the 

low pressure section

of the system higher than the design pressure of the indoor
unit.

2

Test  for  leaks  by  applying  a  bubble  test  solution  to  all  piping
connections.

3

Discharge all nitrogen gas.

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

5.4.5

To perform vacuum drying

To remove all moisture from the system, proceed as follows:

1

Evacuate the system for at least 2 hours to a target vacuum of
–⁠100.7 kPa (–⁠1.007 bar)(5 Torr absolute).

2

Check  that,  with  the  vacuum  pump  turned  off,  the  target
vacuum is maintained for at least 1 hour.

3

Should  you  fail  to  reach  the  target  vacuum  within  2  hours  or
maintain  the  vacuum  for  1  hour,  the  system  may  contain  too
much moisture. In that case, break the vacuum by pressurising
with  nitrogen  gas  to  a  gauge  pressure  of  0.05  MPa  (0.5  bar)
and repeat steps 1 to 3 until all moisture has been removed.

4

Depending  on  whether  you  want  to  immediately  charge
refrigerant  through  the  service  port  of  the  liquid  stop  valve,  or
first  pre-charge  a  portion  of  refrigerant  through  the  liquid  line,
either  open  the  outdoor  unit  stop  valves,  or  keep  them  closed.
See 

"5.6.3  To  charge  refrigerant"  on  page  18

  for  more

information.

5.5

To insulate the refrigerant piping

After  finishing  the  leak  test  and  vacuum  drying,  the  piping  must  be
insulated. Take into account the following points:

▪ Make sure to insulate the connection piping and refrigerant piping

branching entirely.

▪ Be sure to insulate the liquid and gas piping (for all units).

▪ Take  the  following  into  account  when  determining  the  insulation

thickness:

LRMEQ*

LRLEQ*

Liquid pipe minimum temperature

5°C

0°C

LRMEQ*

LRLEQ*

Gas pipe minimum temperature

–20°C

–45°C

Condensation might form on the surface of the insulation.

▪ If  there  is  a  possibility  that  condensation  on  the  stop  valve  might

drip  down  into  the  indoor  unit  through  gaps  in  the  insulation  and
piping  because  the  outdoor  unit  is  located  higher  than  the  indoor
unit,  this  must  be  prevented  by  sealing  up  the  connections.  See
below figure.

a

b

a

Insulation material

b

Caulking etc.

5.6

Charging refrigerant

5.6.1

Precautions when charging refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global  warming  potential  (GWP)  value  is  2087.5.  Do
NOT vent these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

NOTICE

If  the  power  of  some  units  is  turned  off,  the  charging
procedure cannot be finished properly.

NOTICE

Before  starting  charging  procedures,  check  if  the  7‑LEDs
display is as normal (see 

"6.1.4 To access mode 1 or 2" on

page  23

).  If  a  malfunction  code  is  present,  see

"8.1 Solving problems based on error codes" on page 27

.

NOTICE

In case of maintenance and the system (outdoor unit+field
indoor  units)  does  not  contain  any  refrigerant  any
more (e.g., after refrigerant reclaim operation), the unit has
to  be  charged  with  its  original  amount  of  refrigerant  (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.

5.6.2

To determine the additional refrigerant
amount

INFORMATION

For  final  charge  adjustment  in  a  test  laboratory,  contact
your dealer.

INFORMATION

If  only  showcase  units  are  used,  parameter 

B=0

.  If  only

blower coils will be used, parameter 

A=0

.

INFORMATION

If 

R≤0

,  there  is  no  need  to  charge/recover  additional

refrigerant.

Summary of Contents for LRLEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1 LRLEQ3BY1 LRLEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...ektiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek...

Page 6: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Page 7: ...igerant 19 5 6 5 To fix the fluorinated greenhouse gases label 19 5 7 Connecting the electrical wiring 20 5 7 1 Field wiring Overview 20 5 7 2 Guidelines when knocking out knockout holes 21 5 7 3 Guid...

Page 8: ...door unit on page 12 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precautions b Outdoor unit installation and operation manual c Fluorinated greenhouse gases l...

Page 9: ...n the following cases When the design pressure is insufficient Minimum design pressure 2 5 MPa or 25 bar When the path to the heat exchanger has been routed so that the flow of refrigerant is from bot...

Page 10: ...en the following into account Select the pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation...

Page 11: ...chnical information of the expansion valve manufacturer take into account the subcooling ratio K for the liquid refrigerant in the table below For LRMEQ3 4 Subcooling ratio K Te 20 C 15 C 10 C 5 C 0 C...

Page 12: ...cable 2 wires Vinyl cords 0 75 1 25 mm Maximum wiring length 130 m 5 Installation 5 1 Opening the units 5 1 1 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING 1 1 2 5 2 Mou...

Page 13: ...a hexagon wrench into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning 4 Install the stop valve cover Result The valve is now ope...

Page 14: ...ay blow off the pinched piping Failure to observe the instructions in procedure below properly may result in property damage or personal injury which may be serious depending on the circumstances Use...

Page 15: ...ingly 5 3 5 To connect the refrigerant piping to the outdoor unit NOTICE Be sure to use the supplied accessory pipes when carrying out piping work in the field Be sure that the field installed piping...

Page 16: ...may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been factory tested for leaks Only field installed ref...

Page 17: ...r first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 5 6 3 To charge refrigerant on page 18 for more information 5 5 To...

Page 18: ...erant until the determined additional refrigerant amount is reached or pre charging is not possible anymore and then close valves B and C 4 Do one of the following If Then The determined additional re...

Page 19: ...ylinder with one that has more refrigerant remaining If the piping length is long replenishing while the liquid line stop valve is fully closed may lead to activation of the protection system causing...

Page 20: ...use c Power supply including earth sheathed cable d Low noise switch e Remote operation switch f Transmission g Caution signal h Warning signal i Run signal j Operation signal NOTICE The operation out...

Page 21: ...mote 3 Connect the low noise switch as follows B A C F1 F2 X2M D NOTICE Low noise switch If you want to remotely turn ON OFF low noise operation see setting 2 18 you must install a low noise switch Us...

Page 22: ...nals c Remote operation switch low noise switch transmission 8 Route the wiring through the frame and connect it to it Routing through the frame a b a b 2 1 a Power supply cable and output signal cabl...

Page 23: ...2P X1M X3M X2M MULTI DEMAND L N O P SLAVE MASTER IND TEST HWL MODE BS1 BS5 Push buttons H1P H7P 7 LEDs display H8P NOT used for field settings ON OFF Flashing Push buttons Use the push buttons to make...

Page 24: ...m The system starts operating according to the setting BS2 X b a BS3 1 c BS3 1 d BS3 1 Action Button display 5 Quit mode 2 BS1 1 6 1 7 Mode 1 and default situation Monitoring settings In mode 1 and in...

Page 25: ...7 to set parameters for the low noise levels default Correction of evaporating temperature only setting 2 13 applies Adjustment of fan and compressor speed only setting 2 17 applies Correction of evap...

Page 26: ...the compressor for oil leakage If there is an oil leak try to repair the leak If the repairing is unsuccessful call your local dealer Air inlet outlet Check that the air inlet and outlet of the unit i...

Page 27: ...lfunction 4 Display the first character of the error code BS3 1 Possible characters E H F J L P U 5 Display the second character of the error code BS2 1 Possible characters 1 2 3 4 5 6 7 8 9 A C 6 Qui...

Page 28: ...n thermistor failure Open circuit or shortcircuit 0 Caution Faulty connection of sensor Defective sensor Connect the sensor properly Replace defective component Heat exchanger inlet thermistor failure...

Page 29: ...on the inside of the front cover Stacked units max 2 levels See figure 3 on the inside of the front cover A1 A2 A1 If there is danger of drainage dripping and freezing between the upper and lower unit...

Page 30: ...0 V F3U A1P Fuse T 6 3 A 250 V F4U Fuse T 1 0 A 250 V F4U A1P Fuse T 6 3 A 250 V F5U A1P Fuse T 6 3 A 250 V HAP A P Running LED service monitor is green H P A1P LED service monitor is orange K1M A2P M...

Page 31: ...and contact the dealer where you purchased the unit Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired 12 2 After sales service and warrant...

Page 32: ...point temperature too high Set the setpoint appropriately Check if there are no high temperature articles stored in the room showcase Always store articles after they have cooled down Check if the doo...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P545024 1 2018 09 Copyright 2016 Daikin 4P441336 1 0000000J 4P545024 1 0000000I...

Reviews: