Troubleshooting
SiENBE04-925_A
102
Service Diagnosis
4.19 CT or Related Abnormality (35 Class)
Remote Control
Display
H8
Method of
Malfunction
Detection
A CT or related error is detected by checking the compressor running frequency and CT-
detected input current.
Malfunction
Decision
Conditions
The compressor running frequency is more than 55 Hz, and the CT input current is below
0.5 A.
If the error repeats 4 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Breakage of wiring or disconnection
Defective reactor
Defective outdoor unit PCB
SIENBE04-925_A_FRONT.pdf 117
24/02/2011 13:53:57