5.  CAUTION AT INSTALLATION

5-1  HOW TO REPLACE PULLEY

<125-250 type>
(1)  Remove the suction grille.
(2)  Remove the protection net. Then remove the cushioning 

material on the protection net.

(3)  Remove the front panel (upper).
(4)  Remove the front panel (lower).
(5)  Put the iron plate, which must be wider than the fan 

motor, under the fan motor, and on the heat exchanger 

for protection for its fin. (Iron plate must be supplied in the 
field.)

(6)  Remove the terminal for the fan motor lead wire from the 

magnet switch.

(7)  Pull out the fan motor lead wire to the fan housing parts, 

and let it out of the unit from the opening part on the front 
plate (upper).

(8)  Remove the nuts of the motor base.
(9) 

Remove the belt. Hold the fan motor base firmly when 

working so that it may not move suddenly.

(10) Slide the fan housing assembly on the iron plate on which 

the fan motor is put (the above procedure (5)) frontward 
slowly. Work must be conducted by more than 3 persons. 
One of them must hold the motor base, and two or more 
of them must hold the fan housing.

(11) Move the fan housing assembly to the location where can 

be worked and replace the pulley.

(12) After replacing, follow the above procedure in the reverse 

order.

<400 · 500 type>
Follow the above procedure (1)-(4), (6), (7), (10), (11), (12) in 
the order.

(7)

(6)

(8)

(10)

(9)

(4)

Fan motor lead wire

(5) Iron plate

(Field supply)

(2) Protection net

(3) Front panel 

(upper)

(1) Suction 

grille

Front panel 

(lower)

Fan 

motor

Heat 

exchanger

5-2  PARALLELISM OF PULLEY

• 

Adjust the parallelism of the pulley between the fan and 
the motor so as to meet the standard as below.

K

K

K

K

K

Fan pulley

Motor pulley

K (arc-minute)

Note

Parallelism

Less than 10

Equivalent to 3 mm 
displacement per 1 m

5-3  TENSION OF V BELT

•  Tension of a V belt must meet the deflection load (W) as 

shown. 

Calculate the required deflection length (L) by the equation 

(1), its tolerance must be within the range as below.

C

L

(1)

Deflection load

L= 0.016 × C (mm)
C : Distance between the shafts of the pulley 

(

mm

)

W

Types of V belt

Deflection load W (N)

A type

13.7-20.6

B type

22.6-34.3

Note 

• 

It is recommended to check the tension as above after 24-
28 hours of the operation. 
When the new belts are used, it is preferable to adjust to 

about 1.3 times the maximum value of Deflection load (W).

6.  REFRIGERANT PIPING

• 

For the refrigerant piping of the outdoor unit, refer to the 
installation manual attached to the outdoor unit.

• 

Make sure to use R410A as refrigerant before the 

installation work. (Otherwise, the unit can not operate 

normally)

• 

Make sure to insulate the piping on both the liquid side and 
the gas side. Otherwise, water leakage may be caused. 

Use a heat insulating material sufficiently resistant to 

120 °C. Reinforce the refrigerant piping according to the 
installation environment. Otherwise, condensation may 
form on the surface of the insulation.

 CAUTION

This unit is for using R410A only.

Make sure to follow the items as shown in below when 

working.

•  Use the pipe cutter and the flaring tool that are 

exclusively used for R410A.

•  At flare connection, apply ETHER oil or ESTER oil to 

the flare section.

• 

Protect the piping by a pinch or taping to prevent invasion 
of contamination, moisture and dusts into the piping.

6-1  MATERIAL OF PIPING

• 

Use the copper tube according to the following table.

Indoor unit 

capacity

Piping size

Piping on gas side

Piping on liquid side

125 type

φ

15.9 × t1.0 mm

φ

9.5 × t0.8 mm

200 type

φ

19.1 × t1.0 mm

φ

9.5 × t0.8 mm

250 type

φ

22.2 × t1.0 mm

φ

9.5 × t0.8 mm

400 type

φ

28.6 × t1.0 mm

φ

12.7 × t0.8 mm

500 type

φ

28.6 × t1.0 mm

φ

15.9 × t1.0 mm

01_EN_3P345056-4F.indd   4

9/3/2015   15:00:23

Summary of Contents for FXVQ125MY1

Page 1: ...S Floor standing duct type FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16 SYSTEM Air Conditioners CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE ...

Page 2: ...out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation may result in an accident such as air conditioner falling Make certain that all electrical work is carried out by qualified personnel according to the applicable legislation note 1 and this installation manual using a separate circuit In addition even if the wiring is short make sure ...

Page 3: ...ap Insulation for Drain plug Clamp Hanging bolt for fan motor Quantity 1 pc 125 250 type For each 1 pc 400 500 type 1 pc 1 pc 3 pcs 1 pc Shape Gas piping Liquid piping only 500MY16 Gas piping Location Partition plate Name Bolts for flanges Quantity 14 pcs 125 200 type 30 pcs 250 type 18 pcs 400 type 36 pcs 500 type Shape M8 20 Location Partition plate However 2 bolts and 2 nuts are used for flange...

Page 4: ... control panel part Make sure to sling over the hanger 4 INSTALLATION SITE Note Do not apply force on the resin parts in case of carrying the indoor unit when and after unpacking 1 Select an installation site where the following conditions are satisfied and obtain the customer s approval before installation The foundation is strong enough to support the weight of the unit and the floor is flat to ...

Page 5: ... 3 mm displacement per 1 m 5 3 TENSION OF V BELT Tension of a V belt must meet the deflection load W as shown Calculate the required deflection length L by the equation 1 its tolerance must be within the range as below C L 1 Deflection load L 0 016 C mm C Distance between the shafts of the pulley mm W Types of V belt Deflection load W N A type 13 7 20 6 B type 22 6 34 3 Note It is recommended to ch...

Page 6: ...ION PIPING See the following table for the Processing connection piping For right side piping replace the partition bush fixed on the right side panel with the bush for hole fixed on the left side panel Left side piping connection Right side piping connection Piping on liquid side 125 250 type Pass the piping from the hole on the left side into the unit conduct sleeve flare process and brazed conn...

Page 7: ...t Drain plug Indoor unit Downward inclination 1 100 or more 50 mm or more Drain plug cap accessories 100 mm or more Drain piping for Left side connection CAUTION The connection of the drain piping Do not directly connect the drain piping to sewerage which odor may smell like ammonia Sewerage may contain it which may pass through the drain piping and result in corrosion of the indoor unit heat exch...

Page 8: ... type Wiring from right side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiring in one and fix them Terminal block for the wiring between indoor unit and outdoor unit Terminal block for power supply wiring Earth terminal for shield wire Wiring from left side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiri...

Page 9: ...al heat radiation Fig 2 Use wires the same in size if the air conditioner is in simultaneous multi operation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an improper screw driver i...

Page 10: ... when setting by group 4 Press the upper button and select FIRST CODE NO 5 Press the lower button and select the SECOND CODE NO 6 Press the button once and the present settings are SET 7 Press the TEST button to return to the NORMAL MODE SETTING TEST UNIT NO 3 4 5 6 7 1 2 UNIT NO MODE NO SECOND CODE NO FIRST CODE NO FIELD SET MODE Note 1 Setting is carried out in the group mode however set the mod...

Page 11: ...OPERATION 1 Confirm that the control box lid of the indoor units and the outdoor unit are closed 2 Perform the test run according to the installation manual attached to the outdoor unit If the operation lamp on the control panel is flashing it indicates malfunction Check the error code of the liquid crystal display and the malfunction source For the error code and the details refer to the operatio...

Page 12: ...3P345056 4F EM13A004B 1511 HT ...

Reviews: