![background image](http://html.mh-extra.com/html/daikin/fxvq125my1/fxvq125my1_installation-manual_2460209008.webp)
7
English
<Method of wiring for the wiring between indoor unit
and outdoor unit, the earth wiring and the power supply
wiring>
(1) Remove the front panel (lower).
(2) Fix the each wire on the control box with the attached
clamp.
(3)
For wiring specifications, refer to the [DETAILS OF
STANDARD DEVICES].
CAUTION
Apply putty or insulation material (Field supply) without
any clearance on the wiring intake section to prevent small
animals from entering the unit.
(If small animals such as insects enter the inside of the unit, it
may cause short circuit in the control box.)
Connect the wire securely using designated wire and fix it
with attached clamp without applying external pressure on
the terminal parts.
Make sure the wiring and the control box lid do not stick up
above the structure, and close the control box lid firmly.
8-1
REMOVE THE FRONT PANEL (LOWER)
When removing the front panel (lower), there is the control
box.
Front panel (lower)
Screw
Remove the screw attached
front panel (lower).
Front panel
(lower)
8-2
EXTERNAL WIRING METHOD
<125-250 type>
Wiring from right side
Earth terminal
Control box
Pass the attached clamp through
the resin clamp, and bundle each
wiring in one and fix them.
Terminal block for the
wiring between indoor
unit and outdoor unit
Terminal block
for power
supply wiring
Earth terminal for shield wire
Wiring from left side
Earth terminal
Control box
Pass the attached clamp through
the resin clamp, and bundle each
wiring in one and fix them.
Terminal block for the
wiring between indoor
unit and outdoor unit
Terminal block
for power
supply wiring
Earth terminal for
shield wire
<400 · 500 type>
Wiring from right side
Earth terminal
Control box
Pass the attached clamp through
the resin clamp, and bundle each
wiring in one and fix them.
Terminal block for the
wiring between indoor
unit and outdoor unit
Terminal block for
power supply wiring
Earth terminal for
shield wire
Wiring from left side
Earth terminal
Control box
Pass the attached clamp through
the resin clamp, and bundle each
wiring in one and fix them.
Terminal block for the
wiring between indoor
unit and outdoor unit
Terminal block for
power supply wiring
Earth terminal
for shield wire
8-3 EXAMPLE OF WIRING
•
The control panel is the standard built-in.
Ex1. When using in pairs
Prohibited
Indoor unit A
OUT-OUT
Outdoor unit
F1 F2 F1 F2
IN-OUT
Control box
Control panel
Earth
Power
supply
Branch switch
Overcurrent
circuit breaker
L2L3 N
L1
P1
or
P
P2
or
N
F1F2 T1T2
The wiring between indoor
unit and outdoor unit
Never to connect
high-voltage electricity such
as power supply cables.
Ex2. For multiple indoor units
Prohibited
Final indoor
unit
Indoor unit B
Outdoor unit
IN-OUT
Control box
OUT-OUT
Indoor unit A
Earth
Control panel
Control panel
Control panel
Power
supply
Branch switch
Overcurrent
circuit breaker
F1
F2 F1
F2
The wiring between indoor
unit and outdoor unit
The wiring between indoor
unit and indoor unit
P1
or
P
P2
or
N
F
1
F
2
T
1
T
2
P1
or
P
P2
or
N
F
1
F
2
T
1
T
2
P1
or
P
P2
or
N
F
1
F
2
T
1
T
2
Earth
Earth
Never to connect
high-voltage
electricity such as
power supply cables.
L2 L3 N
L1
L2 L3 N
L1
L2 L3 N
L1
CAUTION
Do not have low-voltage wires (wiring between units) and other
high-voltage run through the same locations, and there must
be min. 50 mm distance between wires outside of the unit.
Or it may cause a malfunction or a breakdown of the unit by
receiving electrical noise (external noise).
01_EN_3P345056-4F.indd 7
9/3/2015 15:00:26