Install the air conditioner, power supply wiring, remote 
controller wiring and transmission wiring at least 1 
meter away from televisions or radios to prevent image 
interference or noise.
(Depending on the radio waves, a distance of 1 meter may 

not be sufficient to eliminate the noise.)

• 

Do not install the air conditioner in places such as the 
following:
1.  Where there is mist of oil, oil spray or vapour for 

example a kitchen.
Resin parts may deteriorate, and cause them to fall out 
or water to leak.

2.  Where corrosive gas, such as sulfurous acid gas, is 

produced.

Corrosion of copper pipings or brazed parts may cause 
the refrigerant to leak.

3.  Where there is machinery which emits electromagnetic 

waves.

Electromagnetic waves may disturb the control system, 
and cause malfunction of the equipment.

4.  Where flammable gases may leak, where carbon fibre 

or ignitable dust is suspended in the air or where volatile 

flammables, such as thinner or gasoline, are handled.

If the gas should leak and remained around the air 
conditioner, it may cause ignition.

2.  BEFORE INSTALLATION

• 

Make sure to use the R410A refrigerant before the 
installation work. 
(Otherwise, the unit can not operate normally.)

• 

For installation of outdoor unit, refer to the installation 
manual attached to the outdoor unit.

• 

Do not throw away the accessories required for installation 

until the installation is finished.

2-1  PRECAUTION

• 

Be sure to instruct the customer how to properly operate 

the system (particularly the cleaning of air filter, operation 

method, temperature adjusting method) showing the 
attached operation manual to the person.

• 

Do not install the unit where the atmosphere is salty 
such as near the seaside, where the voltage frequently 

fluctuates or in a vehicle or a boat.

2-2  ACCESSORIES

Check if the following accessories are included in the indoor 
unit.

Name

Connection pipings

Drain 

plug cap

Insulation 

for Drain 

plug

Clamp

Hanging 

bolt for fan 

motor

Quantity

1 pc. 

(125-250 type)

For each 1 pc. 

(400 · 500 type)

1 pc.

1 pc.

3 pcs.

1 pc.

Shape

(Gas 

piping)

(Liquid 
piping)

(only 

500MY16)

(Gas 

piping)

Location

Partition plate

Name

Bolts (for flanges)

Quantity

14 pcs.

(125 · 200 type)

30 pcs.

(250 type)

18 pcs.

(400 type)

36 pcs.

(500 type)

Shape

  M8×20

Location

Partition plate (However, 2 bolts and 2 nuts are used for 

flange temporary fixing.)

Name

Nuts (for flanges)

[Others]

•  

Operation 
manual

• 

 Installation 
manual

Quantity

14 pcs.

(125 · 200 type)

30 pcs.

(250 type)

18 pcs.

(400 type)

36 pcs.

(500 type)

Shape

  M8

Location

Partition plate (However, 2 bolts and 2 nuts 

are used for flange temporary fixing.)

Stay for 
control panel

2-3  

CARRY OUT THE WORK GIVING 

CAUTION TO THE FOLLOWING ITEMS 

AND AFTER THE WORK IS COMPLETED 

CHECK THESE AGAIN.

1.  Items to be checked after the installation work is 

completed

Items to be checked

In case of defective

Check

column

Are the air conditioner rigidly 

fixed? 

Drop · vibration · noise

Are the installation work of the 

air conditioner complete?

Does not operate · burnout

Have you carried out a 
leakage test with the test 

pressure specified in the 

outdoor unit installation 

manual?

Does not cool / Does not 
heat

Is the insulation of refrigerant 

piping and drain piping 

completely carried out?

Water leakage

Does the drain flow out 
smoothly?

Water leakage

Is the power supply voltage 
identical to that stated in the 
manufacturer’s label on the air 

conditioner?

Does not operate · burnout

Are you sure that there is no 

wrong wiring nor piping or no 

loose wiring?

Does not operate · burnout

Is earthing completed?

Danger in case of leakage

Are the sizes of electric wiring 

according to the specification?

Does not operate · burnout

Is any of air outlets or inlets of 
the air conditioner blocked with 

obstacles?

(It may lead to capacity drop 
due to fan speed drop or 
malfunction of equipment.)

Does not cool / Does not 
heat

Have you recorded the 
refrigerant piping length and 

the refrigerant charge added?

Refrigerant charge amount 
is not clear

Make sure to recheck the items of “SAFETY 
PRECAUTIONS”.

01_EN_3P345056-4F.indd   2

9/3/2015   15:00:22

Summary of Contents for FXVQ125MY1

Page 1: ...S Floor standing duct type FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16 SYSTEM Air Conditioners CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE ...

Page 2: ...out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation may result in an accident such as air conditioner falling Make certain that all electrical work is carried out by qualified personnel according to the applicable legislation note 1 and this installation manual using a separate circuit In addition even if the wiring is short make sure ...

Page 3: ...ap Insulation for Drain plug Clamp Hanging bolt for fan motor Quantity 1 pc 125 250 type For each 1 pc 400 500 type 1 pc 1 pc 3 pcs 1 pc Shape Gas piping Liquid piping only 500MY16 Gas piping Location Partition plate Name Bolts for flanges Quantity 14 pcs 125 200 type 30 pcs 250 type 18 pcs 400 type 36 pcs 500 type Shape M8 20 Location Partition plate However 2 bolts and 2 nuts are used for flange...

Page 4: ... control panel part Make sure to sling over the hanger 4 INSTALLATION SITE Note Do not apply force on the resin parts in case of carrying the indoor unit when and after unpacking 1 Select an installation site where the following conditions are satisfied and obtain the customer s approval before installation The foundation is strong enough to support the weight of the unit and the floor is flat to ...

Page 5: ... 3 mm displacement per 1 m 5 3 TENSION OF V BELT Tension of a V belt must meet the deflection load W as shown Calculate the required deflection length L by the equation 1 its tolerance must be within the range as below C L 1 Deflection load L 0 016 C mm C Distance between the shafts of the pulley mm W Types of V belt Deflection load W N A type 13 7 20 6 B type 22 6 34 3 Note It is recommended to ch...

Page 6: ...ION PIPING See the following table for the Processing connection piping For right side piping replace the partition bush fixed on the right side panel with the bush for hole fixed on the left side panel Left side piping connection Right side piping connection Piping on liquid side 125 250 type Pass the piping from the hole on the left side into the unit conduct sleeve flare process and brazed conn...

Page 7: ...t Drain plug Indoor unit Downward inclination 1 100 or more 50 mm or more Drain plug cap accessories 100 mm or more Drain piping for Left side connection CAUTION The connection of the drain piping Do not directly connect the drain piping to sewerage which odor may smell like ammonia Sewerage may contain it which may pass through the drain piping and result in corrosion of the indoor unit heat exch...

Page 8: ... type Wiring from right side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiring in one and fix them Terminal block for the wiring between indoor unit and outdoor unit Terminal block for power supply wiring Earth terminal for shield wire Wiring from left side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiri...

Page 9: ...al heat radiation Fig 2 Use wires the same in size if the air conditioner is in simultaneous multi operation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an improper screw driver i...

Page 10: ... when setting by group 4 Press the upper button and select FIRST CODE NO 5 Press the lower button and select the SECOND CODE NO 6 Press the button once and the present settings are SET 7 Press the TEST button to return to the NORMAL MODE SETTING TEST UNIT NO 3 4 5 6 7 1 2 UNIT NO MODE NO SECOND CODE NO FIRST CODE NO FIELD SET MODE Note 1 Setting is carried out in the group mode however set the mod...

Page 11: ...OPERATION 1 Confirm that the control box lid of the indoor units and the outdoor unit are closed 2 Perform the test run according to the installation manual attached to the outdoor unit If the operation lamp on the control panel is flashing it indicates malfunction Check the error code of the liquid crystal display and the malfunction source For the error code and the details refer to the operatio...