REMOTE CONTROLLER AND 

CENTRALIZED CONTROL

<When operating forced OFF or ON/OFF control from the 

terminal block (X3M)>

1.  Method of wiring and specifications

• 

Remote control can be carried out by connecting input 
from outside to terminals T1 and T2 of the terminal block.

Class of wire

Vinyl cord with sheath or 2-wire cable

Wire gauge

0.75-1.25 mm

2

Wire length

MAX 100 m

Outside contact 

specifications

Contact that guarantees minimum applicable 
load DC15V · 1 mA

Input A

F2

T1

T2

FORCED 

OFF

2.  Operation procedures

• 

Operation is as given in the table below for input A of 
forced OFF, and ON/OFF control.

For forced OFF

For ON/OFF control

Forced OFF (control panel 
rejection) by input A “ON”

Operate by switching input A 
from “OFF” to “ON”

Control panel acceptance by 
input A “OFF”

Stop by switching input A from 
“ON” to “OFF”

3.  For selecting Forced OFF and ON/OFF control

• 

Select input by control panel after turning on the power 
supply.

•  Set to the field set mode by control panel.

 

(For field setting, refer to the procedure shown on 

previous page.)

•  After entering the field set mode, select mode No.12, set 

the first code No.1, and set the second code No. to “01” 

for forced OFF, or to “02” for ON/OFF control. 
(Factory setting is set to forced OFF)

<When operating forced OFF, ON/OFF control, operation 

display, and malfunction display from the wiring adaptor 

for electrical appendices (A2P).>
Refer to “For remote control” in the “VRV Engineering Data”.

<Operation by centralized control>

• 

When using with the centralized control, remove the 
jumper of the group remote control printed circuit board 
mounted in the control box.

• 

If controlled by the centralized control equipment (the 
central control panel (optional accessory)), the group NO. 
must be set by the control panel. 
For details, refer to the instruction of each centralized 
control equipment.

10. TRIAL OPERATION

(1) 

Confirm that the control box lid of the indoor units and the 

outdoor unit are closed.

(2)  Perform the test run according to the installation manual 

attached to the outdoor unit.

•  If the operation lamp on the control panel is flashing, it 

indicates malfunction. 
Check the error code of the liquid crystal display and 
the malfunction source. 
For the error code and the details, refer to the 
operation manual attached to the indoor unit. 
In particular, if an error in the 

table 1 is displayed, it 

may be the error of wiring work or the power supply 
may not be turned ON.

(3)  Carry out test run according to installation manual 

attached to the outdoor unit.

Table 2

Control panel 

(remote 

controller) 

display

Content

Solution

“Under 
centralized 
control” 

flashing

• 

Terminal for forced OFF 
(T1·T2) may be short 
circuiting.

• 

Fix not to short 
circuit.

“U4” 

flashing 

“UH” 

flashing

• 

The power supply of the 
outdoor unit may not turned 
ON.

• 

The power supply of the 
outdoor unit may not be 
installed yet.

• 

Misconnection between the 
transmission wiring, and the 
control panel wiring or the 
forced OFF wiring.

• 

Disconnection of the 
transmission wiring.

• 

Turn on the power 
of outdoor unit.

• 

Proceed installation 
work for power 
supply.

• 

Fix the wiring.

NOT 
display

• 

The power supply of the 
indoor unit is not turned ON.

• 

The power supply of the 
indoor unit may not be 
installed yet.

• 

Misconnection between the 
transmission wiring, and the 
control panel wiring or the 
forced OFF wiring.

• 

Disconnection of the control 
panel wiring.

• 

Turn on the power 
of indoor unit.

• 

Proceed installation 
work for power 
supply.

• 

Fix the wiring.

E4

• 

A test run is carried out from 
outdoor unit in a wrong mode 
(other than “standard” mode).

• 

Select the 
“standard” mode, 
then test run again 
from outdoor unit.

 WARNING

Even though the test run is finished, if the interior finish work 

is not completed, instruct the user not to operate until the 
work is completed for protecting the indoor unit.

Paint or adhesive used for interior finish work may stain the 

indoor unit, which may result in water splash or leak.

01_EN_3P345056-4F.indd   10

9/3/2015   15:00:29

Summary of Contents for FXVQ125MY1

Page 1: ...S Floor standing duct type FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16 SYSTEM Air Conditioners CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE ...

Page 2: ...out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation may result in an accident such as air conditioner falling Make certain that all electrical work is carried out by qualified personnel according to the applicable legislation note 1 and this installation manual using a separate circuit In addition even if the wiring is short make sure ...

Page 3: ...ap Insulation for Drain plug Clamp Hanging bolt for fan motor Quantity 1 pc 125 250 type For each 1 pc 400 500 type 1 pc 1 pc 3 pcs 1 pc Shape Gas piping Liquid piping only 500MY16 Gas piping Location Partition plate Name Bolts for flanges Quantity 14 pcs 125 200 type 30 pcs 250 type 18 pcs 400 type 36 pcs 500 type Shape M8 20 Location Partition plate However 2 bolts and 2 nuts are used for flange...

Page 4: ... control panel part Make sure to sling over the hanger 4 INSTALLATION SITE Note Do not apply force on the resin parts in case of carrying the indoor unit when and after unpacking 1 Select an installation site where the following conditions are satisfied and obtain the customer s approval before installation The foundation is strong enough to support the weight of the unit and the floor is flat to ...

Page 5: ... 3 mm displacement per 1 m 5 3 TENSION OF V BELT Tension of a V belt must meet the deflection load W as shown Calculate the required deflection length L by the equation 1 its tolerance must be within the range as below C L 1 Deflection load L 0 016 C mm C Distance between the shafts of the pulley mm W Types of V belt Deflection load W N A type 13 7 20 6 B type 22 6 34 3 Note It is recommended to ch...

Page 6: ...ION PIPING See the following table for the Processing connection piping For right side piping replace the partition bush fixed on the right side panel with the bush for hole fixed on the left side panel Left side piping connection Right side piping connection Piping on liquid side 125 250 type Pass the piping from the hole on the left side into the unit conduct sleeve flare process and brazed conn...

Page 7: ...t Drain plug Indoor unit Downward inclination 1 100 or more 50 mm or more Drain plug cap accessories 100 mm or more Drain piping for Left side connection CAUTION The connection of the drain piping Do not directly connect the drain piping to sewerage which odor may smell like ammonia Sewerage may contain it which may pass through the drain piping and result in corrosion of the indoor unit heat exch...

Page 8: ... type Wiring from right side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiring in one and fix them Terminal block for the wiring between indoor unit and outdoor unit Terminal block for power supply wiring Earth terminal for shield wire Wiring from left side Earth terminal Control box Pass the attached clamp through the resin clamp and bundle each wiri...

Page 9: ...al heat radiation Fig 2 Use wires the same in size if the air conditioner is in simultaneous multi operation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external force may not apply to the terminals Use a proper screw driver for tightening the terminal screws If an improper screw driver i...

Page 10: ... when setting by group 4 Press the upper button and select FIRST CODE NO 5 Press the lower button and select the SECOND CODE NO 6 Press the button once and the present settings are SET 7 Press the TEST button to return to the NORMAL MODE SETTING TEST UNIT NO 3 4 5 6 7 1 2 UNIT NO MODE NO SECOND CODE NO FIRST CODE NO FIELD SET MODE Note 1 Setting is carried out in the group mode however set the mod...

Page 11: ...OPERATION 1 Confirm that the control box lid of the indoor units and the outdoor unit are closed 2 Perform the test run according to the installation manual attached to the outdoor unit If the operation lamp on the control panel is flashing it indicates malfunction Check the error code of the liquid crystal display and the malfunction source For the error code and the details refer to the operatio...

Page 12: ...3P345056 4F EM13A004B 1511 HT ...

Reviews: