Refnet headers

(4) Additional refrigerant charge

When using FXTQ indoor units, additional refrigerant needs to 
be charged to the system.

Total system refrigerant charge = 

Z

Z = O + R + P

O

: standard factory charge of outdoor unit

R

: additional refrigerant charge according to liquid piping 

diameter/length and outdoor unit specific amount defined in 
outdoor unit manual

P

: additional refrigerant charge due to use of FXTQ indoor units

P = 

Σ

T

1..4

T

: additional charge for each indoor unit used (depending on 

type)

7. DRAIN PIPING WORK

Rig the drain pipe as shown below and take measures 
against condensation. Improperly rigged piping could lead 
to leaks and eventually wet furniture and belongings.
Insulate the drain hose inside the building.

(1) Carry out the drain piping.

• A drain trap need not be installed.
• The drain pipe should be short with a downward slope 

lower than 1/100 and should prevent air pockets from 
forming.

• The diameter of the piping is the same as that of the 

connecting pipe (PS1B), and should be kept equal to or 
greater than that of the connecting pipe.

• If converging multiple drain pipes, install according to the 

procedure shown below. (Select an appropriate central 
drain pipe thickness for the units they will be connected 
to.)

(2) After piping work is finished, check drainage flows 

smoothly.
• Open the water supply port, add approximately 1 liter of 

water slowly into the drain pan and check drainage flow.
Pools of drainage can cause the drain pipes to clog.

CAUTION

• Drain piping connections.

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

8. ELECTRIC WIRING WORK 

8-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials and electric works must 

conform to local codes.

• Use copper wire only.
• For electric wiring work, refer to also “Wiring diagram label” 

attached to the control box lid.

• For remote controller wiring details, refer to the installation 

manual attached to the remote controller.

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B..., and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. 
If wiring and piping between the outdoor unit and an indoor 
unit are mismatched, the system may cause a malfunction.

• A main switch or other means for disconnection, having a 

contact separation in all poles, must be incorporated in the 
fixed wiring in accordance with relevant local and national 
legislation.
Note that the operation will restart automatically if the main 
power supply is turned off and then turned back on again.

• Refer to the installation manual attached to the outdoor unit 

for the size of power supply wiring connected to the outdoor 
unit, the capacity of the circuit breaker and switch, and wiring 
instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, 

lightning rods, or telephone ground wires.

• Gas pipes: might cause explosions or fire if gas leaks.
• Water pipes: no grounding effect if hard vinyl piping is 

used.

• Telephone ground wires or lightning rods: might cause 

abnormally high electric potential in the ground during 
lighting storms.

b

12HP

KHRQ22M75H or 
KHRQ23M75H

14HP

KHRQ22M75H or 
KHRQ23M75H

16HP

KHRQ22M75H or 
KHRQ23M75H

Indoor unit

T (kg)

Outdoor = 

RXYQ or RYYQ

T (kg)

Outdoor = REYQ

FXTQ80

0.9

0.9

FXTQ100

1.1

1.1

   

 

          

Water supply port

4PEN408655-1B_2016_02.book  Page 7  Friday, February 19, 2016  1:33 PM

Summary of Contents for FXTQ80A7VEB

Page 1: ...INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE MODELS Ceiling mounted Duct type FXTQ80A7VEB FXTQ100A7VEB SYSTEM Inverter Air Conditioners INSTALLATI...

Page 2: ...a tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A...

Page 3: ...leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In ad...

Page 4: ...to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an outdoo...

Page 5: ...the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit 4 PREPARATIONS BEFORE INSTALLATION 1 Relative positions of in...

Page 6: ...ant insulation 20 mm or thicker Condensation may form on the surface of the insulating material Before refrigerant piping work check which type of refrigerant is used Proper operation is not possible...

Page 7: ...contains fluorine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without...

Page 8: ...nit Selection of refrigerant branch kits Refnet headers and Refnet joints Refnet joints Outdoor unit FXTQ100 FXTQ80 RYYQ12T 4x O RYYQ14T 2x O 2x O RYYQ16T 4x O RXYQ12T 4x O RXYQ14T 2x O 2x O RXYQ16T 4...

Page 9: ...the drain pipes and corrode the heat exchanger 8 ELECTRIC WIRING WORK 8 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric works must conform to local codes Use copper wire on...

Page 10: ...through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the unit separ...

Page 11: ...id Make sure the lid closes tight Incomplete connections could result in overheating and in worse case electric shock or fire 9 2 WIRING EXAMPLE Fit the power supply wiring of each unit with a switch...

Page 12: ...rom the remote controller according to the installation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from...

Page 13: ...it If any of the items in Table 7 are displayed there may be a problem with the wiring or power so check the wiring again Table 7 Setting Mode No FIRST CODE No SECOND CODE No Standard E S P 13 23 6 1...

Page 14: ......

Page 15: ......

Page 16: ...4P408655 1B 2016 02 Copyright 2015 Daikin...

Reviews: