background image

English

5

CAUTION

Over-tightening may damage the flare and cause a 
refrigerant leakage.

Use “ Table 3 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will 
suddenly increase. From that position, tighten the nut to the 
angle shown on “ Table 3 ”.
The turning torque of the hexagon head bolts (Accessory) to 
connect the attached pipe (Accessory) to the unit is 21.5 – 
28.9 N·m.

• After checking the pipe-connection for gas leakage, be sure 

to insulate the liquid and gas piping, referring to the figure 
below.

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

NOTE

• Attached piping is needed for connecting gas piping. 

When connecting the included piping, use the included 
piping flange hex bolts (2) and spring washers (2).

• Connect refrigerant piping and branching according to the 

attached installation manuals that come with the outdoor 
unit.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING 
REFRIGERANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filler metal (BCuP-2: JIS Z 
3264/B-Cu93P-710/795: ISO 3677) which does not require 
flux.
(Flux has extremely harmful influence on refrigerant piping 
systems. For instance, if the chlorine based flux is used, it 
will cause pipe corrosion or, in particular, if the flux contains 
fluorine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, 
connect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow the 
installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below:

Table 3

Apply ester oil or ether oil only inside

Torque wrench

Spanner

Piping union

Flare nut

 

 

 

 

 

 

 

  

  

 

 

  

 

 

  

   

      

 

 

 

 !

Indoor units to be 

connected

Gas piping diameter

Liquid piping 

diameter

FXTQ80

φ

19.1

Use attached piping.

φ

9.5

FXTQ100

φ

22.2

Use attached piping.

φ

9.5

Pipe size

Further tightening 

angle

Recommended arm length of 

tool

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressure-reducing valve

Hands 
valve

Nitrogen

4PEN408655-1B_2016_02.book  Page 5  Friday, February 19, 2016  1:33 PM

Summary of Contents for FXTQ80A7VEB

Page 1: ...INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE MODELS Ceiling mounted Duct type FXTQ80A7VEB FXTQ100A7VEB SYSTEM Inverter Air Conditioners INSTALLATI...

Page 2: ...a tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A...

Page 3: ...leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In ad...

Page 4: ...to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an outdoo...

Page 5: ...the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit 4 PREPARATIONS BEFORE INSTALLATION 1 Relative positions of in...

Page 6: ...ant insulation 20 mm or thicker Condensation may form on the surface of the insulating material Before refrigerant piping work check which type of refrigerant is used Proper operation is not possible...

Page 7: ...contains fluorine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without...

Page 8: ...nit Selection of refrigerant branch kits Refnet headers and Refnet joints Refnet joints Outdoor unit FXTQ100 FXTQ80 RYYQ12T 4x O RYYQ14T 2x O 2x O RYYQ16T 4x O RXYQ12T 4x O RXYQ14T 2x O 2x O RXYQ16T 4...

Page 9: ...the drain pipes and corrode the heat exchanger 8 ELECTRIC WIRING WORK 8 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric works must conform to local codes Use copper wire on...

Page 10: ...through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the unit separ...

Page 11: ...id Make sure the lid closes tight Incomplete connections could result in overheating and in worse case electric shock or fire 9 2 WIRING EXAMPLE Fit the power supply wiring of each unit with a switch...

Page 12: ...rom the remote controller according to the installation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from...

Page 13: ...it If any of the items in Table 7 are displayed there may be a problem with the wiring or power so check the wiring again Table 7 Setting Mode No FIRST CODE No SECOND CODE No Standard E S P 13 23 6 1...

Page 14: ......

Page 15: ......

Page 16: ...4P408655 1B 2016 02 Copyright 2015 Daikin...

Reviews: