External Static Pressure Settings

Change the “SECOND CODE No.” as shown in Table 6 
according to the external static pressure of the duct to be 
connected.

Table 6

11. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when 

an malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An 
explanation of malfunction codes and the corresponding 
trouble is provided in “CAUTION FOR SERVICING” of the 
outdoor unit.
If any of the items in Table 7 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 7

Setting

Mode No.

FIRST CODE 

No.

SECOND 

CODE No.

Standard 

E.S.P

13 (23)

6

1

High E.S.P

13 (23)

6

2

Remote control display

Content

“Concentrated Management” 

is lit up

• There is a short circuit at the 

FORCED OFF terminals (T1, T2).

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is 

off.

• The outdoor unit has not been 

wired for power supply.

• Incorrect wiring for the 

transmission wiring and / or 

FORCED OFF wiring.

No display

• The power on the indoor unit is 

off.

• The indoor unit has not been 

wired for power supply.

• Incorrect wiring for the remote 

controller wiring, the transmission 

wiring and / or the FORCED OFF 

wiring.

4PEN408655-1B_2016_02.book  Page 11  Friday, February 19, 2016  1:33 PM

Summary of Contents for FXTQ80A7VEB

Page 1: ...INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE MODELS Ceiling mounted Duct type FXTQ80A7VEB FXTQ100A7VEB SYSTEM Inverter Air Conditioners INSTALLATI...

Page 2: ...a tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A...

Page 3: ...leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In ad...

Page 4: ...to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an outdoo...

Page 5: ...the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit 4 PREPARATIONS BEFORE INSTALLATION 1 Relative positions of in...

Page 6: ...ant insulation 20 mm or thicker Condensation may form on the surface of the insulating material Before refrigerant piping work check which type of refrigerant is used Proper operation is not possible...

Page 7: ...contains fluorine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without...

Page 8: ...nit Selection of refrigerant branch kits Refnet headers and Refnet joints Refnet joints Outdoor unit FXTQ100 FXTQ80 RYYQ12T 4x O RYYQ14T 2x O 2x O RYYQ16T 4x O RXYQ12T 4x O RXYQ14T 2x O 2x O RXYQ16T 4...

Page 9: ...the drain pipes and corrode the heat exchanger 8 ELECTRIC WIRING WORK 8 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric works must conform to local codes Use copper wire on...

Page 10: ...through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the unit separ...

Page 11: ...id Make sure the lid closes tight Incomplete connections could result in overheating and in worse case electric shock or fire 9 2 WIRING EXAMPLE Fit the power supply wiring of each unit with a switch...

Page 12: ...rom the remote controller according to the installation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from...

Page 13: ...it If any of the items in Table 7 are displayed there may be a problem with the wiring or power so check the wiring again Table 7 Setting Mode No FIRST CODE No SECOND CODE No Standard E S P 13 23 6 1...

Page 14: ......

Page 15: ......

Page 16: ...4P408655 1B 2016 02 Copyright 2015 Daikin...

Reviews: