When using FXTQ (high efficiency range) indoor units in 
combination with VRV4 outdoor unit systems, please take into 
account the following rules.

(1) Combination table

FXTQ indoor units can only be used corresponding to below 
combination table.
FXTQ indoor units cannot be combined with any other indoor 
unit type compatible with the outdoor unit.

(2) Piping rules of the system

Following piping rules have to be observed:

(3) Piping connections

General layout (2 possibilities)

Piping between outdoor unit and (first) refrigerant branch 
kit: A

Choose from the following table in accordance with the outdoor 
unit total capacity type.

REYQ*T

RYYQ*T & RXYQ*T

Piping between refrigerant branch kits (or BS box): B

Choose from the following table in accordance with the indoor 
unit total capacity type, connected downstream. Do not let the 
connection piping exceed the refrigerant piping size chosen by 
the general system model name.

Piping between refrigerant branch kit and indoor unit: C

Pipe size for direct connection to indoor unit must be the same 
as the connection size of the indoor unit.

Selection of refrigerant branch kits: Refnet headers and 
Refnet joints

Refnet joints

Outdoor unit

FXTQ100

FXTQ80

RYYQ12T

-

4x O

RYYQ14T

2x O

2x O

RYYQ16T

4x O

-

RXYQ12T

-

4x O

RXYQ14T

2x O

2x O

RXYQ16T

4x O

-

REYQ12T

-

4x O

REYQ14T

2x O

2x O

REYQ16T

4x O

-

Maximum piping length

Longest pipe (actual)

120 m

After first branch

40 m

Total piping length

300 m

Maximum height difference

Indoor-outdoor (outdoor lowest)

40 m

Outdoor-indoor (outdoor highest)

50 m

Indoor-indoor

15 m

4

2

3

4

1

1

2

3

4

3

2

1

1.

2.

C

C

A

A

B

b

a1

a2

a2

 12HP 

FXTQ80 FXTQ80 FXTQ80 FXTQ80

 14HP 

FXTQ100 FXTQ80 FXTQ100 FXTQ80

 16HP 

FXTQ100 FXTQ100 FXTQ100 FXTQ100

Outdoor unit 
capacity type 
(HP)

Piping outer diameter size (mm)

Liquid pipe

Suction gas 

pipe

High 

pressure/low 
pressure gas 

pipe

12

12.7

28.6

19.1

14~16

12.7

28.6

22.2

Outdoor unit 
capacity type 
(HP)

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

12~16

28.6

12.7

8/10HP

HP/LP gas

RXYQ

-

RYYQ
REYQ

19.1

12HP

Liquid

Suction gas

HP/LP gas

RXYQ

12.7

28.6

-

RYYQ
REYQ

19.1

14/16HP

Liquid

Suction gas

HP/LP gas

RXYQ

15.9

28.6

-

RYYQ
REYQ

28.6

Indoor unit

Gas

Liquid

FXTQ80

19.1

9.5

FXTQ100

22.2

9.5

a1

a2

12HP

KHRQ22M64T or 
KHRQ23M64T

KHRQ22M64T or 
KHRQ23M64T

14HP

KHRQ22M64T or 
KHRQ23M64T

KHRQ22M64T or 
KHRQ23M64T

16HP

KHRQ22M64T or 
KHRQ23M64T

KHRQ22M64T or 
KHRQ23M64T

4PEN408655-1B_2016_02.book  Page 6  Friday, February 19, 2016  1:33 PM

Summary of Contents for FXTQ80A7VEB

Page 1: ...INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE MODELS Ceiling mounted Duct type FXTQ80A7VEB FXTQ100A7VEB SYSTEM Inverter Air Conditioners INSTALLATI...

Page 2: ...a tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A...

Page 3: ...leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In ad...

Page 4: ...to the unit When moving the unit at or after opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an outdoo...

Page 5: ...the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit 4 PREPARATIONS BEFORE INSTALLATION 1 Relative positions of in...

Page 6: ...ant insulation 20 mm or thicker Condensation may form on the surface of the insulating material Before refrigerant piping work check which type of refrigerant is used Proper operation is not possible...

Page 7: ...contains fluorine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If your brazing is done without...

Page 8: ...nit Selection of refrigerant branch kits Refnet headers and Refnet joints Refnet joints Outdoor unit FXTQ100 FXTQ80 RYYQ12T 4x O RYYQ14T 2x O 2x O RYYQ16T 4x O RXYQ12T 4x O RXYQ14T 2x O 2x O RXYQ16T 4...

Page 9: ...the drain pipes and corrode the heat exchanger 8 ELECTRIC WIRING WORK 8 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric works must conform to local codes Use copper wire on...

Page 10: ...through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the unit separ...

Page 11: ...id Make sure the lid closes tight Incomplete connections could result in overheating and in worse case electric shock or fire 9 2 WIRING EXAMPLE Fit the power supply wiring of each unit with a switch...

Page 12: ...rom the remote controller according to the installation state Carry out setting at 3 places Mode No FIRST CODE No and SECOND CODE No The settings shown by in the table indicate those when shipped from...

Page 13: ...it If any of the items in Table 7 are displayed there may be a problem with the wiring or power so check the wiring again Table 7 Setting Mode No FIRST CODE No SECOND CODE No Standard E S P 13 23 6 1...

Page 14: ......

Page 15: ......

Page 16: ...4P408655 1B 2016 02 Copyright 2015 Daikin...

Reviews: