• If converging multiple drain pipes, install according to the 

procedure shown below.

Select converging drain pipes whose gauge is suitable for 
the operating capacity of the unit.

NOTE

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

• Keep in mind that it will become the cause of getting drain 

pipe blocked if water collects on drain pipe.

(2) After piping work is finished, check drainage flows 

smoothly.

• Open the water inlet lid, add approximately 61 in

3

 of water 

gradually and check drainage flow.

[ WHEN ELECTRIC WIRING WORK IS FINISHED ]

• Check drainage flow during COOL running, explained under 

“TEST OPERATION.”

[ WHEN ELECTRIC WIRING WORK IS NOT FINISHED 

]

• Remove the electric parts box lid, connect a power supply 

and remote controller to the terminals. 
(Refer to the “HOW TO CONNECT WIRINGS”)

Be sure attach the electric parts box lid before turning on the 
power.
Next, press the inspection/test operation button “

” on the 

remote controller. The unit will engage the test operation 
mode. Press the operation mode selector button “

” until 

selecting FAN OPERATION “

”. Then, press the ON/OFF 

button “

”. The indoor unit fan and drain pump will start 

up. Check that the water has drained from the unit. Press 

” to go back to the first mode.

• You can check whether drainage is satisfactory or not by 

removing the access opening lid and checking the water 
level of the drain pan through the access opening.

• Be careful when doing so because the fan is turning at 

the same time.

8. ELECTRIC WIRING WORK 

8-1 GENERAL INSTRUCTIONS 

• All field supplied parts and materials, electric works must 

conform to local codes.

• Use copper wire only.
• Follow the “WIRING DIAGRAM” attached to the unitbody to 

wire the outdoor unit, indoor units and the remote controller. 
For details on hooking up the remote controller, refer to the 
“INSTALLATION MANUAL OF REMOTE CONTROLLER.”

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B . . . , and be sure the terminal board 
wiring to the outdoor unit and BS unit are properly matched. If 
wiring and piping between the outdoor unit and an indoor unit 
are mismatched, the system may cause a malfunction.

• A circuit breaker capable of shutting down the power supply 

to the entire system must be installed.

8-2 ELECTRICAL CHARACTERISTICS

MCA:Min. Circuit Amps (A); MFA:Max. Fuse Amps (A) 

A (in.)

When canvas duct is installed

13 3/4 – 20 7/8

When air inlet panel is directly installed

10 13/16

Units

Power

supply

Fan motor

Model

Hz

Volts

Volt-

age 

range

MCA MFA

W

FLA

FXSQ12MVJU

60

208-

230

Max. 

253

Min.  

187

0.7

15

50

0.6

FXSQ18MVJU

1.0

15

85

0.8

FXSQ24MVJU

1.4

15

125

1.1

FXSQ30MVJU

1.8

15

225

1.4

FXSQ36MVJU

1.8

15

225

1.5

FXSQ48MVJU

2.4

15

225

2.0

Summary of Contents for FXMQ30MVJU

Page 1: ...in type FXSQ12MVJU FXSQ30MVJU FXSQ18MVJU FXSQ36MVJU FXSQ24MVJU FXSQ48MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in...

Page 2: ...RK 6 DRAIN PIPING WORK 7 ELECTRIC WIRING WORK 7 WIRING EXAMPLE AND HOW TO SET THE REMOTE CON TROLLER 8 SELECTING INSTALLATION SITE 11 PREPARATIONS BEFORE INSTALLATION 11 INDOOR UNIT INSTALLATION 12 RE...

Page 3: ...of refrig erant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Be sure to use only the specified accessories and pa...

Page 4: ...rts should be done in accordance with the relevant local and national regulations 2 BEFORE INSTALLATION When moving the unit while removing it from the carton box be sure to lift it by holding on to t...

Page 5: ...or and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of...

Page 6: ...e strong enough to bear the equipment s weight Use embedded inserts or anchor bolts with new buildings and hole in anchors with old buildings 5 INDOOR UNIT INSTALLATION Installing optional accessories...

Page 7: ...he installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tight...

Page 8: ...n the unit is running so be sure to provide condensate trap on the condensate outlet See the figure In order to prevent foreign matter from building up inside the piping you should avoid curves as muc...

Page 9: ...rmly When attaching the electric parts box lid make sure no wires get caught in the edges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring...

Page 10: ...he INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage...

Page 11: ...SAJ25K36 FXSQ18MVJU 16 3 4 or more BYBS45DJW1 Installation not required 13 3 4 or more KSAJ25K56 FXSQ24MVJU 16 3 4 or more BYBS71DJW1 Installation not required 13 3 4 or more KSAJ25K80 FXSQ30 36 48MVJ...

Page 12: ...res at least 3 5 ft away from televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the nois...

Page 13: ...force the ceiling to bearing the weight of the unit 5 INDOOR UNIT INSTALLATION Installing optional accessories except for the decoration panel before installing the indoor unit is easier As for the pa...

Page 14: ...he unit ventilate the room thoroughly right away 6 2 Connecting the refrigerant piping When connecting the flare nut coat the flare both inside and outside with ester oil or ether oil and initially ti...

Page 15: ...flared or a flanged connection Nitrogen should be set to 2 9psi with a pressure reducing valve if brazing while inserting nitrogen into the piping NOTE Do not use flux when brazing refrigerant piping...

Page 16: ...e unit Press to go back to the first mode You can check whether drainage is satisfactory or not by removing the access opening lid and checking the water level of the drain pan through the access open...

Page 17: ...remote controller is as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wiring length 6560 ft 2 Indoor unit Remote controller Max 1640 ft 2 Insulated thickness 1 16 or more Model Power supply wi...

Page 18: ...pply terminal Looseness in the connection may cause overheating Use the specified electric wire Connect the wire securely to the terminal Lock the wire down without applying excessive force to the ter...

Page 19: ...CONNECTOR According to the system static pressure requirement reposi tion the adaptors of PC board inside the electric parts box as shown in the below drawings NOTE The unit is factory set for standar...

Page 20: ...CONTROL BY 2 REMOTE CONTROLLERS Con trolling 1 indoor unit by 2 remote controllers When using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER 1 Insert a screw dr...

Page 21: ...ORCED OFF at factory set 11 TEST OPERATION Refer to the installation manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction...

Page 22: ...0403 HT 3P086156 9N EM03A042B Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: